BEGA 50 069.6 Wall Luminaire Instruction Manual
- August 5, 2024
- BEGA
Table of Contents
BEGA 50 069.6 Wall Luminaire Instruction Manual
Wall luminaire for indoor use
Instructions for use
Application
Free radiating wall luminary · indoor luminary with hand-blown three-ply opal
glass for a soft and uniform light distribution.
The elongated design of this wall luminary particular provides suitability for
installation on pillars, columns and for the front surface of walls, as well
as for recesses or profiles.
The luminary may be installed horizontally or vertically.
Product description
Metal luminary housing, finish Colour velvet copper Hand-blown opal glass
The electrical equipment can be hinged
2 mounting holes ø 6mm
Distance apart 400mm
Jointing sleeve with cable entry for mains supply cable up to
ø 14 mm, max. 5 x 1.5@
Connecting terminals 2.5@
Earth conductor terminal
Complies with flicker requirements in accordance with IEEE 1789, DIN IEC/TR
63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V x 0/50-60 Hz DC 176-276 V
During DC operation the LED power is reduced to 15%
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminary Safety class I
Protection class IP 65
Dust-tight and protection against water jets Impact strength IK04
Protection against mechanical impacts < 0.5 joule
Safety mark
Conformity mark
Weight: 3.4 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Over voltage protection
The electronic components installed in the luminaire are protected against
over voltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate over voltage protection components.
You can find them on our website at www.bega.com.
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or revamping.
Undo hexagon socket (wrench size 5) in the locking cap and remove it.
The opal glass can now be hinged together with the electrical equipment to the front.
Remove opal glass.
Note position of application of the luminaire »arrow down«.
Drill mounting holes into the mounting surface – spacing 400mm and turn in enclosed or suitable fixing screws.
For the electrical connection undo the screw connection at the line connector and remove terminal block.
Make earth conductor connection and electrical connection.
Make connection of the phase with the L marked, the neutral wire at the N marked and earth conductor at the PE marked connecting terminal.
For digital actuation please use the two connecting terminals DA. If these terminals are not assigned, the luminaire will work with full light output.
Bolt together both screw cable glands firmly.
Hook luminaire into the fixing screws and tighten.
Slide opal glass over the lamp and fasten with the locking cap.
Make sure that the gaskets are positioned correctly.
Lamp
Module connected wattage: 23.2 W
Luminary connected wattage : 27 W
Rated temperature : ta=25 °C
Ambient temperature: ta max=45 °C
50 069.6K3
Module designation: 4x LED-0627/930
Colour temperature: 3000 K
Colour rendering index: CRI >90
Module luminous flux: 3860 lm
Luminary luminous flux: 2840 lm
Luminary luminous efficiency: 105,2 lm/W
50 069.6K4
Module designation: 4x LED-0627/940
Colour temperature: 4000 K
Colour rendering index: CRI >90
Module luminous flux: 4020 lm
Luminary luminous flux: 2958 lm
Luminary luminous efficiency: 109,6 lm/W
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a separate label in the
luminaire or on the underside of the specific LED module.
The light colour and light output of BEGA replacement modules correspond
to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass: 11 002 764 .1RG
LED power supply unit: DEV-0470/700i
LED module 3000 K: LED-0627/930
LED module 4000 K: LED-0627/940
Gasket glass 2x: 83 000 788