BEGA 24 914 Ceiling and Wall Luminaire Instruction Manual
- July 27, 2024
- BEGA
Table of Contents
BEGA 24 914 Ceiling and Wall Luminaire
Dimension
Application
Unshielded luminaire with high protection class for installation under
ceilings and on walls.
A luminaire made of die cast aluminium and impact resistant synthetic diffuser
made of BEGA NeoGlass®.
For interior and exterior lighting applications.
Product description
Luminaire made of aluminium alloy
and stainless steel
BEGA Unidure® coating technology
Colour graphite
Impact resistant synthetic diffuser,
BEGA NeoGlass® · diffuse white
Silicone gasket
2 mounting holes ø 5mm
Distance apart 195mm
2 cable entries for through-wiring of mains
supply cable ø 7-10.5mm
Connection terminal 2.5@
Earth conductor connection
Complies with flicker requirements in
accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V 0/50-60 Hz
DC 170-276 V
BEGA Thermal Switch®
Temporary thermal shutdown to protect
temperature-sensitive components
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Conformity mark
This product contains light sources of energy
efficiency class(es) B
Lamp
Module connected wattage 11.6 W
Luminaire connected wattage 13.5 W
Rated temperature ta=25 °C
Service life criteria 50000 h/L70
24 914K3
Module designation LED-1633/830
Colour temperature 3000 K
Colour rendering index CRI > 80
Module luminous flux 2440 Im
Luminaire luminous flux 1300 Im
Luminaire luminous efficiency 96,3 Im/W
- preliminary data
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate overvoltage protection components.
You can find them on our website at www.bega.com.
The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71320.
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Undo screws.
Remove luminaire top and polycarbonate diffuser with gasket.
Lead the mains supply cable through the cable entry of the luminaire base. For wall installation note the position of application “arrow down”.
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface.
Be sure to use the gasket rings supplied.
Make the earth conductor connection and the electrical connection.
In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
Make sure that gasket is positioned correctly.
Insert polycarbonate diffuser with gasket and luminaire top.
Tighten the screws evenly.
Cleaning · Maintenance
Clean dirt and debris from the luminaire regularly with a clean, soft, lint-
free cloth that is kept damp throughout the cleaning.
If possible, please use water for this, adding a little commercial dishwashing
detergent.
For lacquered surfaces we recommend the use of BEGA Lacquer Care Set 71 179.
Cleaning agents containing solvents and high pressure cleaners are unsuitable
for cleaning and maintenance.
Replacing the LED module
The designation of the LED module is noted on a separate label in the
luminaire or on the underside of the specific LED module.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Synthetic cover 15 000 856
LED power supply unit DEV-0341/350
LED module 3000 K LED-1633/830
Gasket 83 000 514
Customer Support
Ceiling and wall luminaire
IP 65
BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com