BEGA 24 892 Ceiling and Wall Luminaire Instruction Manual

July 17, 2024
BEGA

BEGA 24 892 Ceiling and Wall Luminaire Instruction Manual

Ceiling and wall luminaire

Instructions for use

Application

Unshielded ceiling and wall luminaire with high protection class.
A luminaire made of die cast aluminium and with an impact resistant synthetic diffuser.

Product description

Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Impact resistant synthetic diffuser,
BEGA NeoGlass® · diffuse white
2 mounting holes ø 4.8 mm
Distance apart 150 mm
2 cable entries for through-wiring of mains supply cable ø 7-12 mm
Connecting terminal and earth conductor terminal 2.5▫
BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit 220-240 V x 0/50-60 Hz
DC 176-280 V
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
 – Conformity mark
This product contains light sources of energy efficiency class(es) C

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71 320.

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

The synthetic cover is fastened to the luminaire base via 4 spring-locking mechanisms. To remove the synthetic cover, unlock the 4 spring-locking mechanisms (as illustrated in the diagram) one after another by applying light pressure with a screwdriver.
Lift off the synthetic cover.

For mounting the luminaire base and the electrical connection, loosen the 2 screws (Torx drive T10) of the LED PCB and remove the LED PCB upwards (keyholes).
While doing so, make sure that the LED PCB was not mechanically damaged.
Lead the mains supply cable through the cable entry of the luminaire base.
Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
Make the earth conductor connection and the electrical connection.

In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.

Insert the LED PCB into the luminaire base and tighten the mounting screws uniformly.
Make sure that gasket is positioned correctly. Guide the synthetic cover with the 4 mounting brackets into the recesses on the luminaire base and press down evenly until all 4 mounting brackets engage audibly.

Lamp

Module connected wattage  6.5 W
Luminaire connected wattage  7.6 W
Rated temperature  = 25 °C
Service life criteria  50 000 h / L₇₀

24 892 K3

Module designation  LED-1539/830
Colour temperature  3000 K
Colour rendering index  CRI > 80
Module luminous flux  1435 lm
Luminaire luminous flux  920 lm
Luminaire luminous efficiency 
121,1 lm / W

  • preliminary data

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module

The designation of the LED module is noted on a separate label in the luminaire or on the underside of the specific LED module.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares

Synthetic cover  15 000 818
LED power supply unit  DEV-0451/350
LED module 3000 K  LED-1539/830
Gasket  83 002 314

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com