24 189
Ceiling and wall luminaire IP 65
Instructions for use
Application
Unshielded ceiling and wall luminaire with high protection class.
A luminaire made of die cast aluminium and with an impact resistant synthetic
diffuser.
The colour temperature of the luminaire can be set optionally to 3000 K and
4000 K.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure®
coating technology Colour graphite or silver Impact-resistant synthetic cover
2 mounting holes ø 4.5 mm Distance apart 236 mm 2 screw cable glands with
strain relief for through-wiring power connecting cable ø 7–12 mm 1 screw
cable gland closed at the factory with a dummy plug Connection terminal 2.5@
Earth conductor connection Complies with flicker requirements in accordance
with IEEE 1789, DIN IEC/TR 63158, DIN IEC/TR 61547-1 LED power supply unit
220-240 V x 0/50-60 Hz DC 170-280 V BEGA Thermal Switch® Temporary thermal
shutdown to protect temperature-sensitive components Safety class I
Ballproof – The testing of ball impact safety was carried out exclusively with
handballs in accordance with DIN 18032-3: 2018-11.
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK10
Protection against mechanical impacts < 20 joule
– Safety mark
– Conformity mark
Weight: 1.8 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
The ideal protection of all electronic components installed in the luminaires
is achieved by using bounce-free switching contacts such as an electronic
relay (solid-state relay), e.g. BEGA 71 320.
Installation
Undo hexagon socket head screw (wrench size 3 mm) through the opening in the
luminaire housing up to the stop and lift luminaire top. Disconnect the earth
conductor connection from the plug connection.
Disconnect plug-connection of the LED connecting cable.
Lead the mains supply cable through the screw cable gland into the luminaire
back housing.
The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the
enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket
insert and thrust screw (wrench size 22 mm) (see sketch).
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface.
Tighten screw cable gland.
Make the earth conductor connection and the electrical connection.
In order to guarantee the maximum service life of the electrical components,
the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the
position marked by the red information label immediately before finally
closing the luminaire.
The LED module can optionally be operated with a colour temperature of 3000 K
or 4000 K.
Check the labelling to ensure a correct socket match when connecting the plug-
in device to the LED connecting cable.
Connect the green and yellow protective earth conductor from the luminaire top
to the terminal marked in the luminaire base.
In order to ensure the tightness of the luminaire, the grub screw for fixing
the luminaire upper part must not lie in the marked area.
Make sure that gasket is positioned correctly.
Tighten grub screw firmly.
Lamp
Module connected wattage | 12.9 W |
---|---|
Luminaire connected wattage | 14.5 W |
Module designation | LED-1511/83040 |
Colour rendering index | CRI > 80 |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 40 °C |
Operation at colour temperature | 3000 K |
Module luminous flux | 2155 lm |
Luminaire luminous flux | 1717 lm |
Luminaire luminous efficiency | 118,4 lm / W |
Operation at colour temperature | 4000 K |
Module luminous flux | 2265 lm |
Luminaire luminous flux | 1804 lm |
Luminaire luminous efficiency | 124,4 lm / W |
Cleaning · Maintenance
Clean dirt and debris from the luminaire regularly with a clean, soft, lint-
free cloth that is kept damp throughout the cleaning.
If possible, please use water for this, adding a little commercial dishwashing
detergent.
For lacquered surfaces we recommend the use of BEGA Lacquer Care Set 71 179.
Cleaning agents containing solvents and highpressure cleaners are unsuitable
for cleaning and maintenance.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those ofthe modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass | 15 000 580 |
---|---|
LED power supply unit | DEV-0342/350 |
LED module | LED-1511/83040 |
Gasket glass | 83 001 907 |
Gasket housing | 83 002 167 B1 |
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com