BEGA 85 154 Performance Floodlight Instruction Manual
- June 1, 2024
- BEGA
Table of Contents
BEGA 85 154 Performance Floodlight
Specifications
- Luminaire made of aluminum alloy, aluminum, and stainless steel
- Silicone gasket with reflector surface made of pure aluminum
- LED power supply unit: 220-240 V x 0/50-60 Hz DC 176-280 V
- DALI-controllable with one DALI address
- Safety class I, Protection class IP 65
- Impact strength IK06
- Weight: 1.3 kg
- Energy efficiency class: E
Product Usage Instructions
Safety Precautions
The installation and operation of the luminaire must adhere to national
safety regulations. Only a qualified electrician should handle installation
and commissioning to prevent damage due to improper use or installation. Any
modifications made to the luminaire should be the responsibility of the
modifier.
Mounting Instructions
Ensure proper torque for connections to prevent loosening. Secure screw
connections and check the earth conductor connection.
Anzugsdrehmomente: Innensechskantschraube = 7 Nm, Sechskantmutter = 35 Nm.
Torque hexagon socket screw = 7 Nm.
Electrical Connection:
Connect the electrical components with matching protection class and safety
class. Ensure strain relief and use suitable connection terminals at the
luminaire power supply cable. Follow the correct wire configuration: green-
yellow (1) for the earth conductor, brown (L) for phase, and blue (N) for the
neutral conductor.
Control Cables Connection:
Connect control cables using leads marked with DALI. If unused, secure them
appropriately to prevent any hazards.
DIMENSION
Instructions for use
Application
Performance floodlight with G½ mounting bush.
The floodlight can be bolted together with any female thread G½ according to
ISO 228 supplied by others or to BEGA accessories. For a variety of interior
and exterior lighting applications.
Product Description
-
Luminaire made of aluminum alloy, aluminum, and stainless steel
-
BEGA Unidure® coating technology
-
Color graphite or silver
-
Clear safety glass
-
Silicone gasket
-
Reflector surface made of pure aluminum BEGA Hybrid Optics®
-
The rotation range of floodlight is 350°
-
Swivel range -30°/+100°
-
Mounting bracket with G½ threaded connection
-
Thread length: 14 mm
-
Connecting cable X05BQ-F 5 G 1 mm²
-
Cable length 1 m
-
BEGA Ultimate Driver®
-
Complies with flicker requirements by IEEE 1789,
-
DIN IEC/TR 63158, DIN IEC/TR 61547-1 LED power supply unit 220-240 x 0/50-60 Hz
-
DC 176-280 V
-
DALI-controllable
-
Number of DALI addresses: 1
-
Basic insulation is provided between the mains and control cables
-
BEGA Thermal Control®
-
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
-
Safety class I
-
Protection class IP 65
-
Dust-tight and protection against water jets Impact strength IK06
-
Protection against mechanical
-
impacts < 1 joule
CE Conformity mark- Wind catching area: 0.014 m²
- Weight: 1.3 kg
-
This product contains light sources of energy efficiency class(es) E
Safety
- The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Installation
- Screw the floodlight G½ threaded connection firmly into the on-site G½ female thread or BEGA accessory.
- G½ threaded connection torque = 40 Nm. Secure the screw connection from loosening on site (if provided with locking screw S, see fig. A).
- Check the earth conductor connection between the G½ threaded connection and the on-site G½ female thread.
Adjust floodlight
- Undo the hexagon socket screw (wrench
- size 5 mm) and hexagon nut (wrench
- size 27 mm) and set the desired beam direction (see sketches B, and C).
Torque
- Hexagon socket screw = 7 Nm
- Hexagon nut = 35 Nm
- Secure bolted connection Gß against loosening by tightening the hexagon socket screws (wrench size 2 mm).
The electrical connection must be carried out with matching protection class
and safety class, strain-relieved, with suitable connection terminals (not
included in the scope of delivery) at the luminaire power supply cable.
Note the correct configuration of the main supply cable. The earth conductor
is connected at the green-yellow ( ), the phase to the brown (L), and the
neutral conductor to the blue (N) marked wire.
The connection of the control cables is achieved using both leads marked with
DALI. In case these leads are not used the luminaire will be operated at full
light output.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage under DIN EN 61547.
- To achieve additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at: www.bega.com.
- The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71 320.
SPECIFICATION
Lamp
- Module connected wattage 10.2 W
- Luminaire connected wattage 11.8 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 50 °C
85 154 K3
- Module designation LED-1148/930
- Color temperature 3000 K
- Color rendering index CRI > 90
- Module luminous flux 1500 lm
- Luminaire luminous flux 1098 lm
- Luminaire luminous efficiency 93,1 lm / W
85 154 K4
- Module designation LED-1148/940
- Color temperature 4000 K
- Color rendering index CRI > 90
- Module luminous flux 1575 lm
- Luminaire luminous flux 1153 lm
- Luminaire luminous efficiency 97,7 lm / W
Light technique
- Symmetrical wide beam light distribution Half beam angle 20°
- For special lighting applications, an optical filter can be used to change the symmetrical light cone into a flat beam light distribution.
Cleaning and Maintenance
- Clean the luminaire regularly with solvent-free cleansers from dirt and deposits.
- Do not use high-pressure cleaners.
Maintenance
The connecting cable between the mounting box and floodlight has to be
inspected for obvious damages and has to be replaced by a qualified
electrician only
Please note
- Do not remove the desiccant bag from the luminaire housing.
- It is needed to remove residual moisture.
Replacing the LED module
- The designation of the LED module is noted on a separate label in the luminaire or on the underside of the specific LED module.
- The light color and light output of BEGA replacement modules correspond to those of the modules originally fitted. The replacement can be carried out by a qualified person using standard tools.
- Disconnect the system from the power supply. Open the floodlight:
- Remove the trim ring along with the safety glass and reflector by twisting it anti-clockwise. Replace the LED module.
- Please follow the installation instructions for the LED module.
- Inspect and, if necessary, replace the luminaire gaskets.
- The defective glass must be replaced.
- Place the trim ring with glass and reflector on the floodlight housing so that the notches in the trim ring and luminaire housing sit on top of each other.
- Twist on the trim ring clockwise as far as the stop.
Accessories
- 71 289 Optical filter flat beam
- 71 331 Shield
- 71 336 Cylindrical shield
- 70 214 Pole cap for pole ø 48 mm
- 70 248 Pole cap for pole ø 60 mm
- 70 245 Mounting box
- 70 252 General fastener
- 70 280 Tube clamp G½
- 70 283 Screw clamp
- 70 379 Crossbeam G½
- 70 889 Tension belt
For the accessories, separate instructions for use can be provided upon request.
Spares
- Trim ring graphite with glass 25 000 273
- Trim ring silver with glass 25 000 274
- LED power supply unit DEV-0515/300i
- LED module 3000 K LED-1148/930
- LED module 4000 K LED-1148/940
- Reflector 75 005 130
- Gasket housing 83 000 486
- Gasket trim ring 83 002 169
MORE INFORMATION
- BEGA Gantenbrink-Leuchten KG · Postfach 31 60
- 58689 Menden
- info@bega.com
- www.bega.com
FAQ
- Q: Can the luminaire be used for both interior and exterior lighting applications?
- A: Yes, the luminaire is suitable for a variety of interior and exterior lighting applications.
- Q: What is the weight of the luminaire?
- A: The luminaire weighs 1.3 kg.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>