Application

Pole-top luminaire with asymmetrical flat beam light distribution.
For mounting heights 3500 – 6000 mm.

Dark Sky

The light from this luminaire is directed evenly and highly efficiently onto the surface to be illuminated. Less than 1 % of the luminaire luminous flux is emitted into the upper halfspace of the luminaire.

Product description

Luminaire made of cast aluminium, aluminium and stainless steel
BEGA Unidure® coating technology
Colour graphite or silver
Clear, impact-resistant synthetic sphere
For pole top ø 76 mm
Slip fitter insert depth 65 mm
Connecting cable X05BQ-F 4 × 1 mm²
Cable length 6 m
BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI controllable
Number of DALI addresses: 1
A basic isolation exists between power cable and control line
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class II 2
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK07
Protection against mechanical impacts < 2 joule
c – Conformity mark
Horizontal wind catching area: 0.16 m²
Weight: 4.7 kg
This product contains light sources of energy efficiency class(es) C, D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71 320.

Lamp

Module connected wattage 24 W
Luminaire connected wattage 26 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 50 °C

85 099 K3

Module designation LED-1282/830
Colour temperature 3000 K
Colour rendering index CRI > 80
Module luminous flux 3970 lm
Luminaire luminous flux 2803 lm
Luminaire luminous efficiency 107,8 lm / W

85 099 K4

Module designation LED-1282/840
Colour temperature 4000 K
Colour rendering index CRI > 80
Module luminous flux 4170 lm
Luminaire luminous flux 2944 lm
Luminaire luminous efficiency 113,2 lm / W

Installation

Lead luminaire connecting cable into the pole and put on the luminaire.
Align the luminaire with optical system to the traffic surface.
Note the arrow on the reflector.
Secure lateral hexagon socket head screws (wrench size 4) firmly.

The electrical connection of the luminaire must be made with the appropriate protection class and safety class using suitable connection terminals (not included in the scope of delivery) on the luminaire power supply cable.
We recommend you use BEGA connection boxes for this purpose.

Note correct configuration of the mains supply cable. The phase is connected to the brown wire (L) and the neutral conductor to the blue wire (N). The connection of the control cables is achieved by means of the both leads marked with DALI. In case these leads are not used the luminaire will be operated at full light output.

Please note:

Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by a qualified person using commercially available tools. Disconnect the system from the power supply. Loosen the hexagon socket screws (wrench size 4) in the cover of the synthetic sphere and lift off the cover.
Undo the three mounting screws (Torx drive T20) on the LED carrier and remove the LED carrier.
Disconnect the plug connector of the LED connecting cable.
Unclip the grey synthetic cover on the LED carrier.
Replace LED module. Please follow the installation instructions for the LED module. Inspect and, if necessary, replace the luminaire gaskets. A defective synthetic sphere must be replaced.
Install the luminaire in reverse order.

Accessories

For this luminaire we recommend the followingBEGA luminaire poles: Tapered aluminium poles · lacquered with access door and C-clamp

70 913 Pole with anch.section H 3500 mm
70 914 Pole with anch.section H 4000 mm
70 725 Pole with anch.section H 4500 mm
70 915 Pole with anch.section H 5000 mm
70 916 Pole with anch.section H 6000 mm

70 789 Pole with baseplate H 3500 mm
70 791 Pole with baseplate H 4000 mm
70 792 Pole with baseplate H 4500 mm
70 794 Pole with baseplate H 5000 mm

Cylindrically stepped aluminium poles lacquered · with door und C rail

70 901 Pole with anch.section H 4000 mm
70 903 Pole with anch.section H 5000 mm
70 905 Pole with anch.section H 6000 mm

Please see the instructions for use of the luminaire poles for suitable connection boxes.

Spares

Clear synthetic sphere 15 000 798
LED power supply unit DEV-0270/700i
LED module 3000 K LED-1282/830
LED module 4000 K LED-1282/840
Reflector 76 001 924
Gasket screw head 7x 83 000 807
Gasket bottom interior 83 001 990
Gasket bottom exterior 83 002 047
Gasket globe top 83 002 274

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

Specifications:

  • Application: Pole-top luminaire with asymmetrical flat beam light distribution

  • Mounting Heights: 3500 – 6000 mm

  • Lamp Module Connected Wattage: 24 W

  • Luminaire Connected Wattage: 26 W

  • Rated Temperature: 25 – 50 °C

FAQ:

Q: Can I install the luminaire myself?

A: No, installation and commissioning must be carried out by a qualified electrician to ensure compliance with safety regulations.

Q: What should I do if I need additional overvoltage protection?

A: Separate overvoltage protection components are recommended for additional protection. You can find them on our website at www.bega.com.