BEGA 85221K3 Shielded Pole Top Luminaire Instruction Manual

June 1, 2024
BEGA

**BEGA 85221K3 Shielded Pole Top Luminaire Instruction Manual

**

Technical amendments reserved

Pole top luminary
Pole top luminaire

Instructions for use

Application
Shielded pole-top luminaire with symmetrical light distribution.
The light of the LED is guided indirectly via the top reflector towards the ground surface with uniform and very wide beam light.
For mounting heights 3500 – 6000mm.

Dark Sky
The light from this luminaire is directed evenly and highly efficiently onto the surface to be illuminated. Less than 1% of the luminaire luminous flux is emitted into the upper halfspace of the luminaire

Product description

Luminaire made of cast aluminium, aluminium and stainless steel BEGA Unidure® coating technology
Colour graphite or silver
Clear, impact-resistant synthetic sphere Reflector made of pure anodised aluminium
For pole top ø 76mm
Slip fitter insert depth 60mm
Connecting cable X05BQ-F 4G1 mm²
Cable length 6m
BEGA Ultimate Driver®
Complies with flicker requirements in accordance with IEEE 1789,
DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V 0/50-60 Hz
DC 176-264 V
DALI controllable
Number of DALI addresses: 1
A basic isolation exists between power cable and control line
Safety class : II
Protection class : IP 65
Dust-tight and protection against water jets :
– Conformity mark
This product contains light sources of energy efficiency class(es) D

Lamp
Module connected wattage : 37.5 W
Luminaire connected : wattage 41 W
Rated temperature : ta=25 °C
Service life criteria : 50000 h/L70

85 221K3
Module designation : LED-0800/830
Colour temperature : 3000 K
Colour rendering index : CRI >80
Module luminous flux : 5670 lm
Luminaire luminous flux : 2750 lm
Luminaire luminous efficiency :
67,1 lm/W

85 221K4
Module designation : LED-0800/840
Colour temperature : 4000 K
Colour rendering index : CRI >80
Module luminous flux : 5815 lm
Luminaire luminous flux : 2820 lm
Luminaire luminous efficiency :
68,8 lm/W

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71320.

Installation

Lead luminaire connecting cable into the pole and put on luminaire.
Align luminaire and fix it.
Fix lateral hexagon socket head screws M8 firmly.
The electrical connection of the luminaire must be made with the appropriate protection class and safety class using suitable connection terminals (not included in the scope of delivery) on the luminaire power supply cable.
We recommend you use BEGA connection boxes for this purpose.
Note correct configuration of the mains supply cable. The phase is connected to the brown wire (L) and the neutral conductor to the blue wire (N). The connection of the control cables is achieved by means of the both leads marked with DALI. In case these leads are not used the luminaire will be operated at full light output.

Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by a qualified person using commercially available tools.
Disconnect the system from the power supply.
Undo the four hexagon socket screws (wrench size 4) in the sphere receptacle. Rotate the sphere by 45° and lift it out.
To replace the LED module, the receptacle housing must be dismantled from the pole cap.
To do so, fully unscrew the four hexagon socket screws (wrench size 4).
To dismantle the reflector, guide a screwdriver
into the four openings at the edge of the housing that are offset by 90° and disengage the side lugs from the reflector.
Remove the reflector and replace the
LED module. Please follow the installation instructions for the LED module.
Insert the reflector.
Position the receptacle housing on the pole cap and secure with the four hexagon socket screws.

Check the gasket and replace, if necessary.
A defective synthetic sphere must be replaced.
Insert the synthetic sphere and rotate by 45°.
Tighten the hexagon socket screws evenly.

Accessories

For this luminaire we recommend the followingBEGA luminaire poles:
Tapered aluminium poles · lacquered with access door and C-clamp

70 913 Pole with anch.section H 3500 mm
70 914 Pole with anch.section H 4000 mm
70 725 Pole with anch.section H 4500 mm
70 915 Pole with anch.section H 5000 mm
70 916 Pole with anch.section H 6000 mm

70 789 Pole with baseplate H 3500 mm
70 791 Pole with baseplate H 4000 mm
70 792 Pole with baseplate H 4500 mm
70 794 Pole with baseplate H 5000 mm

Cylindrically stepped aluminium poles lacquered · with door und C rail

70 901 Pole with anch.section H 4000 mm
70 903 Pole with anch.section H 5000 mm
70 905 Pole with anch.section H 6000 mm

Please see the instructions for use of the luminaire poles for suitable connection boxes.

Spares

Globe top : 25 000 294
LED power supply unit : DEV-0270/1050i
LED module : 3000 K LED-0800/830
LED module : 4000 K LED-0800/840
Reflector : 76 001 957
Gasket : 83 000 417

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com 3/3