BEGA 24481 Wall Luminaire Instruction Manual

June 13, 2024
BEGA

24 481
Wall luminaireBEGA 24481 Wall Luminaire Instructions for use

Application

Wall luminaire with two-sided light output.
For illumination and design tasks in architecture.
The light directed downwards is intended to illuminate the wall and the horizontal surface in front of it.
The light directed upwards is intended to illuminate the wall and ceiling surfaces.

Product description

Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Matt safety glass
Reflector surface made of pure aluminium
Mounting plate with 4 elongated holes, width 5.4 mm, distance 70 x 125 mm
2 screw cable glands with strain relief for through-wiring power connecting cable
ø 7–12 mm
1 screw cable gland closed at the factory with a dummy plug
Connecting terminal 2.5@ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK03
Protection against mechanical
impacts < 0.35 joule
– Safety mark
– Conformity mark
Weight: 3.7 kg
This product contains light sources of energy efficiency class(es) D

Lighting technology

Wall luminaire with broad spread light distribution.
Half beam angle of the light distribution in both half spaces 70°.

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage
Luminaire connected wattage
Rated temperature
Ambient temperature

Module connected wattage 35.4 W
Luminaire connected wattage 39 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 35 °C

24 481 K3
Module designation| 2x LED-0800/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 5960 lm
Luminaire luminous flux| 4249 lm
Luminaire luminous efficiency| 108,9 lm / W
24 481 K4
Module designation| 2x LED-0800/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 6120 lm
Luminaire luminous flux| 4363 lm
Luminaire luminous efficiency| 111,9 lm / W

Installation

Undo hexagon socket head screws (wrench size 3 mm) up to the stop and disassemble the mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).

BEGA 24481 Wall Luminaire - Installation

Fix the mounting plate with enclosed two fixing screws diagonally on the mounting surface.
Tighten screw cable gland.
Make earth conductor connection and electrical connection to the connecting terminal (plug connection).
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.
Make sure that gasket is positioned correctly.
Push plug into coupler as far as it will go.
Place the luminaire onto the mounting plate and fix it.

Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.

Cleaning Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares

LED power supply unit DEV-0270/1050i
LED module 3000 K LED-0800/830
LED module 4000 K LED-0800/840
Reflector wide beam 76 001 978
Gasket housing 83 002 076
Gasket mounting box 83 002 077

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>