BEGA 24 172 Wall Luminaire With PIR Motion And Light Sensor Instruction Manual

June 1, 2024
BEGA

14.22 · Technical amendments reserved

24 172

Wall luminaire with PIR motion and light sensor

  IP 65

BEGA 24 172 Wall Luminaire With PIR Motion 1

Instructions for use

Application
Unshielded wall luminaire with integral passive infrared motion and light sensor for use in an existing DALI system.
A luminaire made of aluminium alloy and crystal glass.

Lamp
Module connected wattage          23.9 W
Luminaire connected wattage      27.2 W
Rated temperature                       ta = 25 °C
Ambient temperature                   ta ma = 35 °C

24 172 K3
Module designation                          LED-0993/830
Colour temperature                          3000 K
Colour rendering index                     CRI > 80
Module luminous flux                       3975 lm
Luminaire luminous flux                   2131 lm
Luminaire luminous efficiency          78,3 lm / W

24 172 K4
Module designation                           LED-0993/840
Colour temperature                           4000 K
Colour rendering index                     CRI > 80
Module luminous flux                       4180 lm
Luminaire luminous flux                   2241 lm
Luminaire luminous efficiency          82,4 lm / W

Safety
The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Product description
Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Colour graphite or silver
Crystal glass, white inside
2 mounting holes ø 4.5 mm
Distance apart 325 mm
2 screw cable glands with strain relief for through-wiring power connecting cable ø 7­-12 mm
1 screw cable gland closed at the factory with a dummy plug
Connection terminal 2.5
Earth conductor connection
Passive infrared motion sensor (PIR)
Range up to 10 m
Horizontal opening angle 110°
Vertical opening angle 93°
Minimum temperature difference between moving object and environment 4 °C
Object speed 1 m/s
Light sensor
Measuring range adjustable using
DALI Cockpit 0-2500 lx, Resolution 1 lx
Power consumption on the DALI bus:
Sensor: 3.5 mA
Power supply unit: 2 mA
Time hysteresis for suppressing rapid fluctuations in brightness
Complies with flicker requirements in accordance with IEEE 1789, DIN IEC/TR 63158, DIN IEC/TR 61547-1
LED power supply unit
220-240 V 0/50-60 Hz
DC 170-280 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Switch®
Temporary thermal shutdown to protect temperature-sensitive components
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK05
Protection against mechanical
impacts < 0.7 joule
-­ Conformity mark
Weight: 4.7 kg
This product contains light sources of energy efficiency class(es) C, D

Range / Detection area
The specifications for the range and detection area of the PIR motion sensor are reference values. The detection area is up to 110° horizontally and 93° vertically, with a depth of max. 10 m depending on the direction of motion (see sketch).
Too minor temperature difference between the moving object and the ambient temperature can influence the detection range. Local conditions and external heat sources may affect both the range and the detection area.

 BEGA 24 172 Wall Luminaire With PIR Motion 2

Installation

Please note:
A separate DALI power supply is required to operate the luminaire.
If this is not provided by the customer, we recommend using DALI power supply 71 094 or 70 866 (see accessories).
Undo hexagon socket head screws (wrench size 3 mm) through the opening in the luminaire housing up to the stop and lift luminaire top.
Disconnect the earth conductor connection from the plug connection.
Disconnect plug-connection of the LED connecting cable.

Orientation of the sensor
The sensor is factory-configured for the maximum detection area.
In order to avoid the unintentional adjustment of the sensor in public areas, the alteration of the factory setting must be made before the luminaire base is mounted.
To do so, loosen the two rear screws (Torx driver T10) slightly and rotate the sensor ball to the desired position (see Fig. A ). In the process, make sure that the light sensor embedded in the sensor ball is not directed upwards or covered by the edge of the surrounding housing! (see Fig. B )
Tighten the mounting screws evenly.

BEGA 24 172 Wall Luminaire With PIR Motion 3

  1. Light sensor with status LED

Lead the mains supply cable through the screw cable gland into the luminaire back housing. Notice position of use “arrow down” of the luminaire back plate.

The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).

BEGA 24 172 Wall Luminaire With PIR Motion 4

  1. Thrust screw
  2. Synthetic cone-thrust collar
  3. Gasket insert

Notice position of use “arrow down” of the luminaire back plate.
Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
Tighten screw cable gland.

Make the earth conductor connection and the electrical connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.

In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.

Connect the LED connection cable by means of a plug connector.
Make earth conductor connection between luminaire top and luminaire base.
Push plug into coupler as far as it will go.
Make sure that gasket is positioned correctly. Install luminaire top and tighten.

Functions and settings
A combination of several DALI motion and light sensors in one DALI line is possible.
Following installation, the PIR motion and light sensor can be immediately operated in its factory settings; configuration is not required in this case.

The factory settings as are follows:
Holding time: 5 min
Brightness threshold: almost dark /100 lx
Target address: broadcast
Constant light control: off
Status display: Green LED off (can be activated and deactivated using the DALI Cockpit software)
Time hysteresis: 1 min
Threshold hysteresis: 0 lx

Function testing:
After the power supply and the DALI power supply have been switched on, the luminaire is switched on for the duration of hysteresis (factory setting 1 min).
After this period has expired, the lighting switches off automatically.
If the lighting does not switch on again automatically (after the end of hysteresis) during commissioning or on the return of power, the light sensor must be darkened for the duration of hysteresis.
If the brightness threshold is exceeded (factory setting “almost dark /100 lx”), a movement in the detection area does not cause the lighting to switch itself on.
For function testing, the light sensor must be darkened.
Brightness must be below the threshold for the duration of hysteresis; only then does a movement in the detection area cause the lighting to switch itself on.
The lighting now remains switched on for the duration of the holding time (factory setting 5 min).
If there are any more movements in the detection area, the holding time starts over again.
Movement in the detection area does not cause the lighting to switch itself on when the holding time has expired and the brightness threshold has been exceeded for the duration of hysteresis.

DALI configuration
To adjust the settings and for additional functions such as basic brightness (luminaire switches to adjustable dimming value 1 if the brightness threshold is not reached and to adjustable dimming value 2 if movement is detected), a DALI USB interface (71 024 or 71 054) and the DALI Cockpit software are additionally required. DALI Cockpit is available as a free download from our website at www.bega.com.
Configuration is also possible via smartphone and tablet using the BEGA Tool app in conjunction with Bluetooth DALI gateway 71 075 or 71 151.
Resetting to factory settings is done via DALI reset in the DALI Cockpit software or in the BEGA Tool app.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71 320.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Accessories

71 094 DALI Power supply 30 mA in device boxes or installed cable connection box
70 866 DALI Power supply 240 mA for DIN rail mounting

71 024 DALI USB interface for installations in device boxes or preexisting connection boxes
71 054 DALI USB interface for DIN rail mounting

71 075 Bluetooth DALI gateway for DIN rail mounting

71 151   Bluetooth DALI gateway for installation in device boxes

A separate instructions for use can be provided upon request.

Spares

Spare glass                               11 003 519
PIR Light sensor                     61 001 632
LED power supply unit           DEV-0365/700
LED module 3000 K               LED-0993/830
LED module 4000 K               LED-0993/840
Gasket glass                             83 001 927
Gasket wall plate                      83 002 166 B1

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>