CONTROL UNIT BIOS2 ECO
Programmable Control board for wings gates Manual for
installation
Introduction
The control unit BIOS2 ECO is particularly indicated for the installation of 1
or 2 wing gates with 230 Vac motors with maximum power absorbed of700W.The
control unit equipped with a display that allows a precise regulation of the
thrust of the gate. It is also possible to adjust the delay in closureof the
second wing in the base settings menu. The control unit can memorize up to
1000 transmitters with the external memory, with the step by steppartial
opening, open and close functions. It is supplied with inputs for internal and
external photocells, possibility to connect the buttons for step bystep,
partial opening, open, close and stop. The outputs include a 230 Vac flashing
light, electrical lock and courtesy light/open gate light by theexpansion card
R2 (not supplied) with dry contacts 230 Vac 5A max/30 Vdc 5A max, 24 Vdc
accessories power supply.
ATTENTION: DO NOT INSTALL THE CONTROL UNIT WITHOUT READING THE INSTRUCTIONS
FIRST !!!
THE INSTALLATION SHOULD BE PERFORMED ONLY BY QUALIFIED PERSONNEL.
For a correct functioning of the system, it is absolutely indispensable the
use of mechanical stops in opening and closing.
Configuration
Connections
POWER SUPPLY
Connect the power supply cable between clamp 1 and 2 of the control unit
Power supply 230 Vac 50 Hz
Do not connect the card directly to the electric network. Put a device which
can ensure the disconnection of each pole from the power supply of the control
unit.
MOTOR 1 OUTPUT
Connect the common of the motor 1 to the clamp 5 of the control unit.
Connect the phase 1 of the motor 1 to the clamp 3 of the control unit.
Connect the phase 2 of the motor 1 to the clamp 4 of the control unit.
MOTOR 2 OUTPUT
Connect the common of the motor 2 to the clamp 8 of the control unit.
Connect the phase 1 of the motor 2 to the clamp 6 of the control unit.
Connect the phase 2 of the motor 2 to the clamp 7 of the control unit.
Connect to the MOTOR 1 output the wing which beats. Install an aventual
electrical lock on this wing.
MOTOR 1 is always activated first during opening phase and in second during
closing phase.
Motor condensers 230 Vac
!!Risk of electric shock!!
In the event of use of not Allmatic motors, insert a fuse in series to the
common of the motor (see paragraph 9) FLASHING LIGHT OUTPUT
Connect the flashing light to the clamps 9 and 10.
Use a flashing light without self flashing card 230Vac 60W MAX ACCESSORIES OUTPUTS
Accessories output 24Vdc, to the clamps 11 e and 12 of the control unit 6 W
max. OPENING PHOTOCELL INPUT
Connect the NORMALLY CLOSED contact of the photocell (PHOTO) between the
clamps 13 and 20 of the control unit.
If not used set the DIP switch PH2 ON.
Functioning:
– Closing: Stops the movement and waits until the beam is freed, then moves in
opening
– Opening: stops the movement and waits until the beam is freed, then moves in
opening. CLOSING PHOTOCELL
INPUT
Connect the NORMALLY CLOSED contact of the photocell (PHOTO) between the
clamps 14 and 20 of the control unit.
If not used set the DIP switch PH1 ON.
Functioning:
– Closing: immediate inversion of movement.
– Opening: no intervention during the movement.
STOP INPUT
Connect the contact NORMALLY CLOSED of the STOP between the clamps 15 and 20
of the control unit.
If not used set the DIP switch STOP ON. OPEN INPUT
Connect the button OPEN between the clamps 16 and 20 of the control unit.
CLOSE INPUT
Connect the button CLOSE between the clamps 17 and 20 of the control unit.
PARTIAL OPENING INPUT
Connect the button PED between the clamps 18 and 20 of the control unit.
STEP BY STEP INPUT
Connect the button SS between the clamps 19and 20 of the control unit.
ANTENNA
Connect the signal cable of the antenna to the clamp 22 and the ground of the
antenna to the clamp 21 of the control unit.
The presence of the metallic parts or humidity in the walls could have
negative influences on the range of the system. We suggest therefore to not
place the receiving antenna and/or transmitters near big metallic objects,
near the floor or on the ground.
13 CONNECTION OF RELAY CARD R2 (optional)
If the courtesy light is present, the functioning of courtesy light/open gate
lamp is controlled in the advanced menu .
Maximum load 230 Vac 5A, 30 Vdc 5A max.The contact for electrical lock is enabled with the
parameter in the advanced menu
Maximum load 230 Vac 5A, 30 Vdc 5A max.
Remote control learning
4.1 Learning of one transmitter
The 1st memorized key performs the STEP by STEP function (opening and closing
of the gate), the 2nd key performs the partial opening, the 3rd performs the
OPEN function, 4th key performs the CLOSE function.
The control unit exits from the learning phase if no new key or trasnmitter
command is given in 10 seconds.
1 Make sure that the board is out of any menus, press the button UP[+]| On the
display will appear and the flashing light lights on
---|---
2 Press one key of the transmitter
If you want to memorize another key or a new transmitter repeat the procedure|
On the display will appear .
If the transmitter was already memorized will appear .
After 2 seconds the display will show the memory location of the memorized
transmitter, for example
4.2 Learning with the hidden key of an already memorized transmitter
With the hidden key of a transmitter it is possible to enter the learning
phase in order to memorize new keys or new transmitters.
With the automation still, with the aid of a clip press the hidden button of
an already memorized transmitter, the flashing light lights on, now it is
possible to memorize new keys or transmitters.
4.3 Cancellation of one transmitter
Enter the learning phase with the UP[+] button or with the hidden key of a
memorized transmitter (see 5.1 or 5.2).
Press in the same time the hidden key and 1st key of the transmitter that you
want to cancel.
The flashing light bilnks 4 times and on the display will appear
Setting the wing stroke
For a correct functioning of the system, it is absolutely indispensable the
use of mechanical stops in opening and closing.
5.1 Easy settings of the wings stroke (parameter
Connect to the MOTOR 1 output the wing which beats.Install an aventual
electrical lock on this wing. MOTOR 1 is always activated first during opening
phase and in second during closing phase. In this procedure it is necessary to
provide the limits positions of the wings with a step by step command (SS).
1 Unlock the motors, move the wings in the middle of the
stroke and relock the motors.| |
---|---|---
2 Press and keep pressed the buttons UP[+] e MENU
for at least 5 seconds.| The wing 1 moves in opening.
If the wing moves in closing press the DOWN[-] button to stop and reverse the
direction of movement and give a step by step command (SS) to resume the
procedure|
3 When the wing 1 reaches the opening mechanical
stop give a step by step command (SS)| The wing 1 stops and the wing 2 moves
in opening.
If the wing moves in closing press the DOWN[-] button to stop and reverse the
direction of movement and give a step by step command (SS) to resume the
procedure|
4 When the wing 2 reaches the opening mechanical stop
give a step by step command (SS)| Wing 2 stops, after 2 seconds the wing 2
moves in closing|
5 When the wing 2 reaches the closing mechanical stop
give a step by step command (SS)| Wing 2 stops, after 2 seconds the wing 1
movesin closing|
6 When the wing 1 reaches the closing mechanical stop
give a step by step command (SS)| Wing 1 stops, after 2 seconds the wing 1
moves in opening|
7 When the wing 1 reaches the the opening mechanical
stop give a step by step command (SS)| Wing 1 stops, after 2 seconds the wing
2 moves in opening|
8 When the wing 2 reaches the the opening mechanical
stop give a step by step command (SS)| Wing 2 stops, after 2 seconds the gate
closes with the settings of delay between the wings and slowing downs set in
the menu. When the gate is closed the learning phase is ended.|
Warning: in case of intervention of a safety device, the learning is
stopped and will appear on the display the written Press Step by Step key to
start again the learning from the 2nd point.
For a correct functioning of the system, it is absolutely indispensable the
use of mechanical stops in opening and closing.
5.2 Advanced settings of the wings stroke (parameter )
Connect to the MOTOR 1 output the wing which beats. Install an aventual
electrical lock on this wing. MOTOR 1 is always activated first during opening
phase and in second during closing phase. In this procedure it is necessary to
provide also the positions where the slowing downs begin with a step by step
command (SS).
1| Unlock the motors, move the wings in the middle of the
stroke and relock the motors.| |
---|---|---|---
2| Press and keep pressed the buttons UP[+] e MENU
for at least 5 seconds.| The wing 1 moves in opening.
If the wing moves in closing press the button DOWN to stop and reverse the
direction of movement and give a step by step command (SS) to resume the
procedure|
3| When the wing 1 reaches the opening mechanical
stop give a step by step command (SS)| The wing 1 stops and the wing 2 moves
in opening.
If the wing moves in closing press the button DOWN to stop and reverse the
direction of movement and give a step by step command (SS) to resume the
procedure|
4| When the wing 2 reaches the opening mechanical stop
give a step by step command (SS)| Wing 2 stops, after 2 seconds the wing 2
moves in closing|
5| When the wing 2 reaches the desired position of
beginning of slowing down give a step by step
command (SS)| The wing 2 begins the slowing down
6| When the wing 2 reaches the closing mechanical stop
give a step by step command (SS)| Wing 2 stops, after 2 seconds the wing 1
moves in closing|
7| When the wing 1 reaches the desired position of beginning of slowing down
give a step by step
command (SS)| The wing 1 begins the slowing down
8| When the wing 1 reaches the closing mechanical stop
give a step by step command (SS)| Wing 1 stops, after 2 seconds the wing 1
moves in opening|
9| When the wing 1 reaches the desired position of
beginning of slowing down give a step by step
command (SS)| The wing 1 begins the slowing down
10| When the wing 1 reaches the the opening mechanical
stop give a step by step command (SS)| Wing 1 stops, after 2 seconds the wing
2 movesin opening|
11| When the wing 2 reaches the desired position of
beginning of slowing down give a step by step
command (SS)| The wing 2 begins the slowing down
12| When the wing 2 reaches the the opening mechanical
stop give a step by step command (SS)| Wing 2 stops, the gate closes with the
slowing downs set during the learning phase and the delay between the wings
set in the menu. When the gate is closed the learning phase is ended.|
Warning: in case of intervention of a safety device, the learning is stopped and will appear on the display the written Press Step by Step key to start again the learning from the 2nd point.
Menu
Entering the menu:
To enter the base menu settings keep pressed the MENU button for at least one
second
To enter the advanced menu settings keep pressed the MENU button for at least
five seconds Navigation into the menu:
It is possible to move from an entry to another one using UP[+] e DOWN[-]
buttons, To change a parameter keep pressed the MENU button for at least 1
second until the parameter begins blinking, so release the key.
Use UP[+] and DOWN[-] buttons to change the parameter At the end keep pressed
MENU for al least 1 second until the parameter stops blinking to save the
change.
A quick pressure of the menu key is enough to leave a menu 6.1 Base settings
menu:
MENU| DESCRIPTION| SELECTABLE VALUES
min-max| DEFAULT| UNITS
---|---|---|---|---
| Auto reclosing time (0 = disabled)| 0-900| 0| s
| Auto reclosing time after transit(0 = disabled)| 0-30| 0| s
| Motor torque (running torque)| 10-100| 100|
| Slowing down mode
0 = normal
1 = fast with more torque| 0-1| 1| %
| Step by step configuration
0 – normal (OP-ST-CL-ST-OP-ST…)
1 = alternated STOP (OP-ST-CL-OP-ST-CL…)
2 = alternated (OP-CL-OP-CL…)
3 = condominium – timer
4 = condominium with immediate auto reclosing| 0-4| 0|
| Soft start
0 = disabled 1 = enabled| 0-1| 0|
| Second wing delay| 0-300| 2| s
| Amplitude of slowing down (0 = disabled)
P = personalized during learning
0…100% = percentage of stroke| 0-100| 15| %
| Anti slip| 0-300| 0| s
| Number of motors
1 = 1 motor
2 = 2 motors| 1-2| 2|
6.2 Advanced menu:
MENU| DESCRIPTION| SELECTABLE
VALUES min-max| DEFAULT| UNITS
---|---|---|---|---
| Partial opening| 0-100| 30| %
| Pre-flashing time (0 = disabled)| 0-10| 0| s
| Courtesy ligth settings
0 = At the end of movement for a TCY time
1 = Open gate light on/off| 0-1| 0|
| Courtesy light time| 0-900| 180| s
| Dead-man
0 = disabled
1 = enabled| 0-1 0| 0|
| Water-hammer in opening phase (0 = disabled)| 0-100| 0| x100 ms
| Water-hammer in closing phase (0 = disabled)| 0-100| 0| x100 ms
| Time of pressure in closed for hydraulic motors (0 = disabled)| 0-480| 0|
minuti
| Electrical lock mode
0 = disabled
1 = Active Electrical lock without preventive activation
2 = Active Electrical lock with preventive activation
3 = Magnetic Electrical Lock| 0-3| 0|
| Viewing of the memory location for a single transmitter| 0-999| |
| Cancellation of a single transmitter| 0-999| |
| Restore default settings, enter to modify the parameter and then keep
pressed the
MENU button, a count down appears that ends with don on the display| | |
| Cancelling all transmitters, enter to modify the parameter and then keep
pressed
the MENU button, a count down appears that ends with don on the display| | |
6.3 Menu description:
6.3.1 Base settings menu
Auto reclosing time
Active when the gate is in the completely open position, the gate
automatically closes after seconds. In this phase the display shows with the
blinking dash, that during the last 10 seconds will be replaced by the count
down.
Auto reclosing time after transit
If in the opening phase or in the completely open position the beam of the
photocells is obscured and freed, the gate automatically closes after seconds
when the completely open position is reached, In this phase the display shows
with the blinking dash, that during the last 10 seconds will be replaced by
the count down.
Motor torque
Adjust the motor torque to ensure a correct functioning of the gate, it is
possible to adjust the percentage of torque between 10% to 100%. After the
adjustment of this parameter it is recommended to perform a complete
movimentation (opening and closing) to ensure a correct functioning of the
gate.
Slowing down mode
The control unit has 2 different type of slowing downs : standard or with
higher torque and speed, for heavier gates.
Step by step configuration (SS)
-
= 0 Normal (OP-ST-CL-ST-OP-ST…)
Typical functioning of Step by Step. During the movement a SS command stops the gate. -
= 1 Alternated STOP (OP-ST-CL-OP-ST-CL…)
Alternated functioning with STOP during the opening. During the opening phase a SS command stops the gate. -
= 2 Alternated (OP-CL-OP-CL…)
The user cannot stop the gate during the movement with a SS command.
A SS command during the movement inverts the movement. -
= 3 Condominium – timer
A SS command only opens the gate. When the gate is completely open, if the command persist the control unit will wait until the opening of the contact before beginning the contdown of the automatic reclosing (if enabled), onother SS command in this phase will restart the contdown of the automatic reclosing. -
= 4 Condominium with immediate auto reclosing
Soft start
The movement begins with reduced torque, used in light gates.
Second wing delay
This is the setting of the delay of the second wing to ensure a correct
overlapping of the wings; the delay is the same in opening and closing. If 0
is set the control unit will remove completely the delay. Warning overlapping
of the wings.
Amplitude of slowing down
With this parameter it is possible to adjust the amplitude of the slowing down
and eventually disable it ( =0). If you need more precise or different slowing
down between opening and closing it is possible to set the parameter LSI on P
(personalized) and perform an advanced learning of strokes (5.2) providing
also the beginning of slowing downs during the learning.
Antislip
This parameter is used if the motor slips, the control unit adds seconds to
movimentation to ensure a complete movements of the wings also in the worst
condition.
Number of motors
This parameter is used to set the number of motors, the learning operations
and the functionality will be modified depending on this parameter.
6.3.2 Advanced menu
Partial opening
Partial opening can be performed only starting from closed. The parameter sets
the opening like a percentage of the total stroke of the first wing.
Pre-flashing time
Pre-flashing before each movement in both directions, seconds of pre-flashing
Courtesy light settings
The control unit has 4 different functionings for courtesy light:
- = 0 the light switches off at the end of a movement after seconds
- = 1 open gate light – the light switches off immediately when the gate reaches the closed position
Courtesy light timer
Courtesy light activation timer
Dead man
During dead man functioning mode the gate moves only with a permanent command.
The enabled commands are OPEN and CLOSE. SS and PED are disabled. During dead
man functioning all the automatic movements are disabled, like short or total
inversions. All safety devices are disabled except for STOP.
Water-hammer in opening phase
This functioning is used with an electrical lock. The gate before opening
closes shortly on the mechanical stop with the electrical lock activated, to
ensure the correct declutching. The parameter is the time of pressure on the
mechanical stop before opening, settable from 0.1s to 10 s.
The sequence done by the control unit before opening is the following:
- preventive activation of the electrical lock [1,5s]. ATTENTION! Necessary enable electrical lock on the advanced menu parameter:
- motor activation in closing with maximum torque. The duration of this phase is setted by the parameter
- inversion of direction with another 2 seconds of activation of the electrical lock. Necessary enable electrical lock on the advanced menu parameter:
Water-hammer in closing phase
- This functioning is used with an electrical lock. When the gate reaches the closing mechanical stop the control unit perform a strong pressure, seconds long, to ensure the locking of the electrical lock. Necessary enable the electrical lock from the advanced menu parameter elm (if used)
Time of pressure in closed position for hydraulic motors
This function is used to keep high the pressure of hydraulic motors, done only
with closed gate, the control unit performs 1 minute of closing every minutes
to keep high the pressure into the motors and the correct closed position.
. Electrical Lock mode
= 0 disable
= 1 The electrical lock is activated when the automation performs an opening
movement.
= 2 The electrical lock is activated when the automation performs an opening
movement. In the opening phase it is activated with a safety advance time of
1.5 seconds.
= 3 In case of use of magnetic electric lock, always active when the gate is
closed (except when the motor is in pressure in closed position), disable when
the gate is not closed.
Viewing of the memory position for a single transmitter
With the item of the menu it is possible to view the memory location in which
a transmitter is memorized.
To perform the function, move to and then confirm by pressing the button MENU.
Keep pressed MENU button untill the display will show then release the button.
At this point press a button of the memorized transmitter (it does not active any command). The display shows:
- the memory location for 2 seconds, if is memorized;
- the written for 2 seconds, if is not memorized.
After 2 seconds the display returns to the screen and it will be possible to perform this function with another transmitter. To exit from the function, press MENU button. Otherwise after 15 seconds without transmission, the control unit exits from the function and shows the written
Cancellation of a single transmitter
With the item of the menu it is possible to delete a single transmitter from
the memory.
To perform the function, move to . and then confirm by pressing the button
MENU. Keep pressed MENU button untill the display will show 0, then release
the button. Select the memory location of the transmitter. Press and keep
pressed MENU button untill the display will show , then release the button.
To exit from the function, press MENU button. If the display shows the written
, there are problems with the memory (for example empty position or
disconnected memory).
Restore default settings
With this parameter it is possible to restore the default settings of the
control unit. The reset will restore all the parameters of the base and
advanced menu, but doesn’t modify the learnt strokes, the directions of motors
and the transmitters.
Move to then keep pressed MENU button until the display shows 0, release the
button. Press again and keep pressed MENU button, the display will show a
count down ,don’t release the button until the display showns tr.f. Erasing of
all transmitters
With this parameter it is possible to erase all the transmitters learnt.
Move to then keep pressed MENU button until the display shows 0, release the
button. Press again and keep pressed MENU button, the display will show a
count down ,don’t release the button until the display showns
Erasing of all transmitters
With this parameter it is possible to erase all the transmitters learnt.
Move to then keep pressed MENU button until the display shows 0, release the
button. Press again and keep pressed MENU button, the display will show a
count down ,don’t release the button until the display showns
Display and control unit state
7.1 Normal functioning:
| Standby – Gate closed
---|---
| Opening phase
| Closing phase
| Gate closed by user during opening
| Gate closed by user during closing
| Gate stopped by an external event (fotocellule, stop)
| Gate opened without automatic reclosing
| Gate opened in partial opening position without automatic reclosing
| Gate opened waiting for auto reclosing, last 10 seconds the dash will be
replaced by the countdown
| Gate opened in partial opening position waiting for auto reclosing, last 10
seconds the dash will be replaced by the countdown
| During the normal functioning and out from any menu, the pression of the
DOWN[-] button lets you see the number of cycles done, you will see units with
dots on the bottom of display and thousand without dot, another pression of
DOWN[-] or MENU button let you to leave the cycles visualization
| Visualized during the learning of transmitters
| Visualized when memorized a new transmitter or at the and of a reset
| Visualized when memorized a key of a transmitter already memorized
| Visualized when a trasmitter is erased
| Visualized during the learnign of strokes to indicate that the control unit
is opening the gate and waiting for the command of opening mechanical stop
| Visualized during the learning of strokes to indicate that the control unit
is clkosign the gate and waiting for the command of closing mechanical stop
| Visualized during the learning of strokes if there is an intervention of
safety devices
| Visualized when the control unit waits a transmitter signal, during the
function of viewing of the memory location.
| Visualized when the transmitter is not stored on the memory, during the
function of viewing of the memory location.
| Visualized when the control unit exits from the function of viewing of the
memory location for inactivity.
7.2 Errors:
| Limit switches error (both opening and closing electrical limit switches
busy in the same time)
---|---
| Malfunctioning of photocells
| Memory error
| Full memory
| Memory error during functions viewing memory location or cancellation of a
single transmitter
The visualization of an error on the display persist until another command is given
Technical features
POWER SUPPLY AND CONSUMPTION
Power supply voltage | 230 Vac – 50/60 Hz |
---|
Absorption from line (Standby)
Standard configuration (2 couple of photocells, RX radio safety edge)| 55 mA @
230 Vac
Line fuse| F6.3A
MOTOR POWER SUPPLY
Number of motors | 1 / 2 |
---|---|
Motor power supply voltage | 230 Vac – 50/60 Hz |
Maximum power absorbed from motors | 2 x 700W |
ACCESSORIES POWER SUPPLY
Accessories power supply voltage | 24Vdc |
---|---|
Maximum current absorbed from accessories | 250 mA |
Maximum power absorbed from accessories | 6 W |
Accessories fuse | F0.5A |
Uscita lampeggiante | 230 Vac 60W max |
Courtesy light output / open gate light | with R2 card (optional) |
230 Vac 5A, 30 Vdc 5A max
Electrical lock| with R2 card (optional)| dry contact
230 Vac 5A, 30 Vdc 5A max
FUNCTIONALITY
433 MHz radio receiver | Rolling code |
---|---|
Maximum transmitters | 1000 |
Motors
The correct functioning is guaranteed only in the event of Allmatic motors.
For a greater safety, it is suggested to insert a fuse (T 3,15A) in series to
the common of both the motors.
It is available a pre-wired kit (optional) that can be inserted as shown in
the drawing below.
WARNING AND ADVICES
Avoid putting the connection cables of buttons, security devices and inputs
close to those of the power supply of the control unit and of the motor.
Some parts of the control unit are subject to dangerous voltage. The control
unit must be installed and programmed only by qualified professionals. Always
use a device that ensures the disconnection of all poles of the control unit’s
power supply.
This device can be:
– A switch (connected directly to the power supply terminals) with a contact’s
minimum distance of 3 mm for each pole.
– A device connected to the power network.
For connecting the card and the motors we recommend to use cables with double
isolation as in compliance to the laws in force; the minimum cross section of
the single conductor must not be less than 1,5 mm² and not more than 2.5mm².
WEEE – Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this
means the product must not be included with other general waste at the end of
its working life. The user must take the worn product to a sorted waste
center, or return it to the retailer when purchasing a new one. Products for
disposal can be consigned free of charge (without any new purchase obligation)
to retailers with a sales area of at least 400 m2 , if they measure less than
25 cm. An efficient sorted waste collection for the environmentally friendly
disposal of the used device, or its subsequent recycling, helps avoid the
potential negative effects on the environment and people’s health, and
encourages the re-use and/or recycling of the construction materials.
ALLMATIC S.r.l
32026 Borgo Valbelluna (BL) – Italy
Via dell’Artigiano, n°1 – Z.A.
Tel. 0437 751175 – 751163 r.a. Fax 0437 751065
http://www.allmatic.com – E-mail:
info@allmatic.com
GUARANTEE – In compliance with legislation, the manufacturer’s guarantee is valid from the date stamped on the product and is restricted to the repair or free replacement of the parts accepted by the manufacturer as being defective due to poor quality materials or manufacturing defects. The guarantee does not cover damage or defects caused by external agents, faulty maintenance, overloading, natural wear and tear, choice of incorrect product, assembly errors, or any other cause not imputable to the manufacturer. Products that have been misused will not be guaranteed or repaired. Printed specifications are only indicative. The manufacturer does not accept any responsibility for range reductions or malfunctions caused by environmental interference. The manufacturer’s responsibility for damage caused to persons resulting from accidents of any nature caused by our defective products, are only those responsibilities that come under Italian law.
6-1622176 – rev. 8.1 – 04/07/2023