Schneider Electric RM17TG00 Harmony 3 Phase Control Relay Instruction Manual
- June 16, 2024
- Schneider Electric
Table of Contents
Schneider Electric RM17TG00 Harmony 3 Phase Control Relay
Introduction
This product must be installed, connected and used in compliance with
prevailing standards and/or installation regulations.
As standards, specifications and designs develop from time to time, always ask
for confirmation of the information given in this publication.
Product Feature
- Relay output status (yellow) LED R/R1/R2
- 35mm rail clip-in spring
- Power supply status (green) LED. Un/Dial pointer
- Voltage range selection switch (RM22TR – with ON/OFF Delay selector)
- Time delay adjustment potentiometer. Tt/Tt1/Tt2
- Overvoltage threshold adjustment potentiometer. >U
- Undervoltage threshold adjustment potentiometer. <U
- Overvoltage & Undervoltage threshold adjustment potentiometer. ΔU
- Asymmetry threshold adjustment potentiometer. Asy/Asym
- Fault detection status (yellow) LED. Def
- Diagnostic button
For product comparison, refer to Harmony Control Relays Catalog or datasheet for more information.
Dimension
Safety Information
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power before servicing equipment.
- Confirm that the product power supply voltage and its tolerances are compatible with those of the network.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION OR INADEQUATE OVERCURRENT PROTECTION
- Do not use in safety critical system.
- Do not disassemble, repair or modify the product.
- Install the product in the operating environment conditions described in this document.
- Install properly rated fuses as recommended in this document.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences
arising out of the use of this material.
Mounting & Installation
Recommended Distance
Connection Example
-
A fuse. UL…Class CC ; IEC…gG
-
Warning: Do not connect 3 phase control relay to monitor output of Variable Speed Drive (VSD).
-
Light indicator
Setting Example
R/R1/R2 Closed
R/R1/R2 Open
L1/L2/L3 is referring to line-line voltage except for RM35UB3N30
Example 1: To set 3 phase voltage monitoring at 220VAC L-L +/-12 %, Asymmetry monitoring 5 %, Fault delay = 5 s using RM17TE00
1| 2| 3| 4|
---|---|---|---|---
|
220V * 12% = 26.4V >U: 220V + 26.4 = 246.4V
|
Asy: 220V * 5% = 11V
| | Hysteresis (H): >U/
H = 2% V: 220V * 2% = 4.4V
Example 2: To set 3 phase voltage monitoring at 415VAC L-L, >U at 18 %, <U at 16 %, On delay = 5 s using RM22TR33
1| 2| 3| 4|
---|---|---|---|---
|
415V * 18% = 74.7V
U: 415V + 74.7 = 489.7V
|
415V * 16% = 66.4V
<U: 415V – 66.4 = 348.6V
| | **Hysteresis (H):
U/<U*H = 2% V:
415V 2% = 8.3V
Example 3: To set 3 phase voltage monitoring at 220VAC L-N,>U at 18 %, U Fault delay = 12 s, <U Fault delay = 9 s using RM35UB3N30
1| 2| 3| 4|
---|---|---|---|---
|
220V * 18% = 39.6V
U: 220V + 39.6 = 259.6V
|
220V * 16% = 35.2V
<U: 220V – 35.2V = 184.8V
| | **Hysteresis (H):
U/<U*H = 2%
V: 220V 2% = 4.4V
Setting Change & Reset
If the voltage range selection switch position is changed while the device is
operating, all the LEDs will blink, but the product continues to operate with
the voltage selection preceding the change of position. The product has to be
powered off and on again for the new selection to take effect. All LED’s
return to their normal state if the switch is returned to the original
position.
Function Diagram
R/R1/R2 Closed / R/R1/R2 Fermé / R/R1/R2 Geschlossen /
R/R1/R2 Open / R/R1/R2 Ouvert / R/R1/R2 Geöffnet /
Phase Loss & Phase Sequence
Table 1
RM35UB3N30 | – |
---|---|
RM35UB330 | – |
RM35TF30 | 150V |
RM22TA33 | 30%Us/250V* (2) |
RM22TA31 | 30%Us/150V* (2) |
RM22TU23 | 250V |
RM22TU21 | 150V |
RM22TR33 | 250V |
RM22TR31 | 150V |
RM22TG20 | 100V |
RM17UB310 | – |
RM17TE00 | 150V |
RM17TA00 | 150V |
RM17TU00 | 150V |
RM17TT00 | 30%Us/150V* (2) |
RM17TG20 | 100V |
RM17TG00 | 100V |
Phase Loss Threshold /
- Refer to Table 1 for phase loss threshold
- Phase loss threshold will follow whichever of higher value
- Refer to Table 2 for Response time (Tr). Time Delay (Tt) does not apply to phase loss or phase sequence.
Voir le tableau 2 pour le temps de réponse (Tr). La temporisation (Tt) ne s’applique pas à la perte de phase ni
Undervoltage
Overvoltage & Undervoltage
Overvoltage & Undervoltage
Asymmetry
Table 2
| RM17TG00| RM17TG20| RM17TT00| RM17TU00| RM17TA00| RM17TE00| RM17UB310|
RM22TG20| RM22TR31| RM22TR33| RM22TU21| RM22TU23| RM22TA31| RM22TA33|
RM35TF30| RM35UB330| RM35UB3N30
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Response Time (Tr)| <300ms
ON/OFF Delay (Tt/Tt1/Tt2)| –| –| –| 0.1…10s| 0.1…10s|
0.1…10s| 0.3…30s| –| 0.1…30s| 0.1…30s| –| –|
0.1…30s| 0.1…30s| 0.1…10s| 0.3…30s| 0.3…30s
Hysteresis (H)| 2% V
Refer to Table 2 for Response time (Tr). Time Delay (Tt) does not apply to
phase loss or phase sequence.
Response Time (Tr) not shown together with Time Delay (Tt).
LED Indication
- Off
- On
- Slow Blink
- Fast Blink
Phase Loss & Phase sequence
- Only RM22TG20 has 2 relay outputs / 2 sorties relais pour RM22TG20 uniquement
Except RM22TG20
Undervoltage ( <U)
Overvoltage & Undervoltage (>U & <U)
Overvoltage & Undervoltage (>U & <U)
Absence of Neutral/Phase (N?/N)
Asymmetry
Time delay in progress
Diagnostic
For RM22 only (Except RM22TG20)
Power Supply| Input monitoring condition| Diagnostic Button| Output Relays
Status
---|---|---|---
| | |
| |
| |
| | |
Time delay in progress
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>