eyc-tech FTM06D Inline Type Air Flow Meter User Manual
- June 12, 2024
- eyc-tech
Table of Contents
- eyc-tech FTM06D Inline Type Air Flow Meter
- Product Information
- Product Usage Instructions
- Safety Precautions
- Panel Operation Flow
- Connection Diagram
- Installation instructions
- RS-485 and Modbus
- Technical Data
- Software and calibration operation step
- Device Information
- Inspection and maintenance
- Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
eyc-tech FTM06D Inline Type Air Flow Meter
Product Information
- The eyc-tech Measuring Specialist is a versatile product that enhances your capability with sensor technology.
- It is designed to measure various parameters including air flow, humidity, dew point, differential pressure, liquid flow, temperature, pressure, level, air quality, and signal meter.
Product Usage Instructions
- Ensure that the device is properly connected to a power source.
- Familiarize yourself with the different measurement parameters and their corresponding symbols indicated in the user manual.
- To measure air flow, place the sensor in the desired location and follow the specific instructions provided in the user manual.
- For humidity measurement, ensure that the sensor is properly calibrated and follow the instructions for accurate readings.
- To measure dew point, differential pressure, liquid flow, temperature, pressure, level, air quality, or signal meter, refer to the corresponding sections in the user manual for detailed instructions.
- When using the device, make sure to follow all safety precautions and guidelines provided in the user manual.
- If you encounter any issues or require further assistance, please refer to the troubleshooting section of the user manual or contact our customer support at www.eyc-tech.com.
Note: The above instructions are a general guide. Please refer to the complete user manual for detailed instructions specific to your model.
Safety Precautions
- Please read this Specification carefully, prior to use of this, and keep the manual properly, for timely reference.
Solemn Statement :
- This product can not be used for any explosion-proof area.
- Do not use this product in a situation where human life may be affected. eyc-tech will not bear any responsibility for the results produced by the operators!
Warning!
- Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.
- This product must be operated under the operating conditions specified in manual to prevent equipment damages.
- Please using the product under the ordinary pressure, or it will influence safe problem.
- This product must be operated under the operating condition specified in this manual to prevent equipment damages.
- This product must be operated under the normally atmospheric condition to prevent equipment damages.
- To prevent products damage, always disconnect the power supply from the product before performing any wiring and installation.
- All wiring must comply with local codes of indoor wiring and electrical installation rules.
- Please use crimp type terminal.
- To prevent personal injury, do not touch the moving part of product in operation.
- It may cause high humidity atmosphere during the product was breakdown. Please take safety strategy.
Panel Operation Flow
Connection Diagram
Installation instructions
RS-485 and Modbus
- FTM06D-I integrate a RS-485 interface for digital communication as an option feature.
- Based on Mod bus protocol makes the general convenience on PLC, HMI and PC connection. For Mod bus protocol information please download the file from website.
- Besides the PLC, HMI application, the user software provide the device setting and data logging function, it also can free download from website.
Technical Data
- Max. network size : 32 transmitters
- Communication : with COM-Port (serial interface) of PC
- Max. network expansion : 1200m (3937ft) total length at 9600 baud
- Transmission rate : 9600, 19200, 38400, 57600, 115200 Baud
- Parity : None, Even, Odd
- Data length : 8 bit
- Stop bit : 1 or 2 bit
- Factory default Station address= 1, Data format= 9600, N81
Software and calibration operation step
User may download the configuration software on eye web site. Please decompress the application prior to execute it. Operating System requirements: above Windows XP. Other application program requirements : above Microsoft Office 2003
- Hardware connection: Connect the FTM06D-I to PC through USB to RS-485 or RS-232 to RS-485 converter
- Check the COM port number from Device Manager in Computer Management. e.g. COMl in illustration
- Open the FTM06D-I UI, go to function II Interface 11 , click item Config and then setting COM port, BAUD rate, data format and Station ID, pressed Apply 11 for connection
- Scan RS-485 connection
- Open the FTMO6D-I UI, go to function ” Interface” , click item “Config” and then setting COM port, pressed “Scan” bottom for scan devices and pressed ” Close and Export” when the interested devices found.
- Pick up the device that you want to connect to and then press “Apply” to go .
- Setting on Analog Output
In the group of OUT1, Output tab. The output1 related setting could be found.
- Quantity: Flow Velocity, Flow Volume and Sensor Temperature
- Response rate: 0 … 100 100 : filter off , 90 : filter = 60 second 80 : filter = 120 second, etc.
- Analog type : 0… 20 mA / 4… 20 mA (if output current) / 0 … 10 V (if output voltage)
- Range for Upper and Lower
- Alarm Mode: Check the box if analog output pretend a alarm switch output
- Alarm Trigger Point: Upper and Lower
- Alarm Output Level: Upper and Lower
Setting on PNP/PNP Output (Optional, Only Available if Function Equipped)
In the group of OUT2, Output tab. The PP/PP switch output related setting could be found.
- Quantity: Flow Velocity, Flow Volume and Sensor Temperature
- Response rate: 0 … 100 • 100 : filter off › 90 : filter = 60 second • 80 : filter = 120 second, etc.
- Alarm Mode: High Activate or Low Activate
- Range for Upper and Lower
- Alarm Point: Upper and Lower
- Delay Time : On Delay Time and Off Delay Time (seconds)
- Setting on Frequency Output (Optional, Only Available if Function Equipped)
In the group of OUT2, Output tab. The Frequency output related setting could be found.
- Quantity: Flow Velocity, Flow Volume and Sensor Temperature
- Response rate: 0…100 › 100 : filter off › 90 : filter = 60 second • 80 : filter = 120 second, etc.
- Frequency: Upper and Lower
- Measures: Upper and Lower
- Alarm Mode: The output would be switch between upper and lower correspond to measures
- Alarm Point: Upper and Lower
- Alarm Output : Upper and Lower
- Setting on Impulse Output (Optional, Only Available if Function Equipped)
In the group of OUT2, Output tab. The Impulse output related setting could be found.
- Quantity: Flow Velocity, Flow Volume and Sensor Temperature
- Response rate: 0…100 • 100 : filter off • 90 : filter = 60 second • 80 : filter = 120 second, etc.
- Impulse Duration : High and Low
- Measures: Upper and Lower
- Impulse Value: The valence of single impulse quantity
- Impulse Unit: m°, Liter, mL, mm?, ft°, inch?, gal,us (Gallon, us), gal,uk (Gallon, uk)
Setting on RS-485, Process Parameters and offset adjustment
There are 4 groups in setting tab. The description of each item as below.
Process Parameters:
- Temperature of normalcondition
- Pressure of working condition
- Relative Humidity of working condition % Offset Adjustment :
- flow rateoffset
- temperature offset
- flow ratecut off
- flow rate slope adjustment, default 1 Modbus Protocol:
- station ID
- Baud Rate
- Date Frame
- Flash memory write protect Miscellaneous:
- Password of keypad menu
- LED brightness
- Display Alternate Period: the first field for quantity unitduration, the seconds field for quantity measure duration (seconds)
Data display and logging
- Assign Temperature Unit: °C / °F
- Assign Flow Volume Unit : Nm3/h, L/min
- Display Decimals
- Clear Measure Plot Chart
- Time scale of plot
- Vertical scale of plot
- Export all logging data since device is connected
- Start/Stop data logging
Device Information
- Model Name of Device
- Firmware Version of Device
- Serial Number of Device
- Firmware Checksum
- Calibration Date
- Flow Offset
- Temperature Offset
- Flow Calibration Range
- Temperature Calibration Points
Totalizer
- Flow Volume Rate
- Volume Accumulation Totalizer 1
- Volume Accumulation Totalizer 2
- unit of counter 1
- unit of counter 2
- Main switch of totalizer
- Function switch of totalizer 1
- Function switch of totalizer 2
- Ser/Reset Totalizer 1
- Set/Reset Totalizer 2
Inspection and maintenance
Maintenance
- Since this product is inspected and calibrated for high accuracy at the factory before shipment, no calibration on the installation site is necessary when this product is installed
- For inspection and maintenance follow the instructions below:
- (a) Periodic inspection
- Periodically inspect this product for its sensing accuracy, and clean the cover Set the period between inspections based on atmospheric dust and other contaminants in the installation environment
- (b) Sensor maintenance
- Do not damage sensor surface during maintenance process
- (c) Troubleshooting
- If any problem occurs during operation, refer to the table below for appropriate solutions
Troubleshooting
eyc-tech Measuring Specialist
- enhance your capability with sensor technology
- Air flow Humidity Dew point Differential pressure Liquid flow
- Temp. Pressure Level Air quality Signal meter
- Tel.: 886-2-8221-2958
- Web :www.eyc-tech.com
- e-mail :info@eyc-tech.com