eyc-tech FTE120-I Inline Type Air Flow Transmitter Instruction Manual

June 12, 2024
eyc-tech

FTE120
Inline Type Air Flow Transmitter
Operation-Manual **
eyc-tech FTE120-l**

FTE120-I Inline Type Air Flow Transmitter

eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
1

Safety Precautions

  • Before using this product, the user must to read the details of this user’s manual, then use this product with correct steps.
  • This user’s manual is for reference while using / Setting this product, and required to conserve properly.
  • This product is improperly to use in explosion-proof area, do not use this product in dangerous situation where human health & life may be threaten & affected.
  • Ifthe user install this product in special environments as Dust-Free Room, Breed Environment for Animals, etc., please initiate a specialized product consultation to our professional sales of our company.
  • If the improper & dangerous results which result from improper operator or improper environment, our company will not bear any legal responsibility.

Warning

  • Please ensure the outlook / outbox do not have any damage which result from improper transportation, or malfunction which results from lost attachments.

  • In order to prevent the GM from damages. This product must be used in the proper environment which specified in this user’s manual.

  • Please implement the wiring operation under power-off status; otherwise it will cause electric shock, or become the root cause of machinery breakdown.

  • For prevent equipment damage, disconnect the power supply from the product before performing any wiring and installation.

  • This product must be operated under ruled power supplying value, and be operated under the ruled normal operation conditions which described in the user’s manual ; otherwise it may cause the disasters as fire accident or be the root cause of machinery breakdown.

  • This product must be operated under the operating conditions specified in manual to prevent equipment damage.

  • Installation and wring must be performed by qualified personnel in accordance with all applicable safety standards, According to applicable safety standards all wiring must comply with local codes of indoor wiring and electric installation rules.

  • All wiring must comply with the rule for indoor wiring and electrical installation rules. The screw must be tight for upper cover & lower base.

  • Inorder to prevent the interferences from frequency converter, etc., and avoid error signal to result in the product damage, please use the isolated conducting wire.

  • Please use crimp type terminal.
    To prevent personal injury, do not touch the moving part of product in operation.
    It may cause high humidity atmosphere during the product was breakdown. Please take safety strategy.

  • While discard this product, the user must to comply with the related rules for industrial domestic wastes for different country / location.

Connection Diagram

eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
2

Installation

Installation instructions:

90° pipe (flow passes through the pipe turn)| Continuous 90° pipes in different horizontal planes (vertical flow and through curved pipes)
---|---
eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
3|
Tube expanding state (flow becomes large from small)| Control valve status (switch switching / flow adjustment)
eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
5|
Shrinking tube state (flow from large to small)| The flows continuously through the 90° bend in the same horizontal plane
eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
7|

RS-485 and Modbus

FTE120-l integrate a RS-485 interface for digital communication as an option feature. Based on Modbus protocol makes the general convenience on PLC, HMI and PC connection. For Modbus protocol information please download the file from website. Besides the PLC, HMI application, the user software provide the device setting and data logging function, it also can free download from website.
Technical Data:

  1. Max. network size: 32 transmitters
  2. Communication: with COM-Port (serial interface) of PC
  3. Max. network expansion: 1200m (3937ft) total length at 9600 baud
  4. Transmission rate: 9600, 19200, 38400, 57600, 115200 Baud
  5. Parity: None, Even, Odd
  6. Data length: 8bit
  7. Stop bit: 1or2 bit
  8. Factory default Station address = 1, Data format= 9600, N81

Software and calibration operation step

User may download the configuration software on eyc web site. Please decompress the application prior to execute it. Operating System requirements: above Windows XP. Other application program requirements: above Microsoft Office 2003

  1. Hardware connection: Connect the FTE120-I to PC through USB to RS-485 or RS-232 to RS-485 converter

  2. Check the COM port number from Device Manager in Computer Management. e.g. COML1 in illustrationeyc-tech FTE120-I Inline Type Air Flow Transmitter - fig 9

  3. Open the FTE120-1 U, go to function “Interface” , clickitem ” Config” and then setting COM port, BAUD rate, data format and Station ID, pressed ” Apply ” for connectioneyc-tech FTE120-I Inline Type Air Flow Transmitter - fig 10

  4. Scan RS-485 connection
    Open the FTE120- Ul, go to function “Interface” ,clickitem ” Config” and then setting COM port, pressed ” Scan” bottom for scan devices and pressed ” Close and Export ” when the interested devices found.eyc-tech FTE120-I Inline Type
Air Flow Transmitter - fig 11Pick up the device that you want to connect to and then press “Apply” to go.

  5. Setting on Analog Output
    In the group of OUT1, Output tab. The outputl related setting could be found.
    (1) Quantity : Flow Volume
    (2) Responserate: 0…100 » 100: filter off » 90: filter =60 second» 80: filter = 120 second, etc.
    (3) Analogtype :0…20 mA/4…20 mA (if output current)/ 0 … 10 V (if output voltage)
    (4) Range for Upper and Lower
    (5) Alarm Mode: Check the box if analog output pretend a alarm switch output
    (6) Alarm Trigger Point: Upper and Lower
    (7) Alarm Output Level: Upper and Lowereyc-tech FTE120-I Inline Type Air
Flow Transmitter - fig 12

  6. Setting on Frequency Output (Optional, Only Available if Function Equipped) In the group of OUT2, Output tab. The Frequency output related setting could be found.
    (1) Quantity: Flow Velocity, Flow Volume and Sensor Temperature
    (2) Responserate: 0…100 > 100: filter off» 90: filter = 60 second> 80: filter = 120 second, etc.
    (3) Frequency : Upper and Lower
    (4) Measures: Upper and Lower
    (5) Alarm Mode: The output would be switch between upper and lower correspond to measures
    (6) Alarm Point: Upper and Lower
    (7) Alarm Output : Upper and Lowereyc-tech FTE120-I Inline Type Air Flow
Transmitter - fig 13

  7. Setting on Impulse Output (Optional, Only Available if Function Equipped) In the group of OUT2, Output tab. The Impulse output related setting could be found.
    (1) Quantity: Flow Velocity, Flow Volume and Sensor Temperature
    (2) Responserate: 0…100 > 100 : filter off » 90 : filter = 60 second > 80 : filter = 120 second, etc.
    (3) Impulse Duration : High and Low
    (4) Measures: Upper and Lower
    (5) Impulse Value: The valence of single impulse quantity
    (6) Impulse Unit: m3, Liter, mL, mm3, ft3,inch3, gal,us (Gallon, us), gal,uk (Gallon, uk)eyc-tech FTE120-I Inline Type Air Flow Transmitter - fig
14

  8. Setting on RS-485, Process Parameters and offset adjustment
    Offset Adjustment:
    (1) Volume offset
    (2) Volume cut off
    Modbus Protocol:
    (3) stationID
    (4) Baud Rate
    (5) Date Frame
    (6) Flash memory write protecteyc-tech FTE120-I Inline Type Air Flow
Transmitter - fig 15

  9. Data display and logging
    (1) Assign Volume Unit : m3/h, L/min, m3/min
    (2) Display Decimals
    (3) Clear Measure Plot Chart
    (4) Time scale of plot
    (5) Vertical scale of plot
    (6) Exportall logging data since device is connected
    (7) Start/Stop data loggingeyc-tech FTE120-I Inline Type Air Flow
Transmitter - fig 16

  10. Device Information
    (1) Model Name of Device
    (2) Firmware Version of Device
    (3) Serial Number of Device
    (4) Firmware Checksum
    (5) Calibration Date
    (6) Flow Offset
    (7) Flow Calibration Range![eyc-tech FTE120-I Inline Type Air Flow Transmitter

Inspection and maintenance

  1. Maintenance
    Since this product is inspected and calibrated for high accuracy at the factory before shipment, no calibration on the installation site is necessary when this product is installed For inspection and maintenance follow the instructions below:
    (a) Periodic inspection
    Periodically inspect this product for its sensing accuracy, and clean the cover Set the period between inspections based on atmospheric dust and other contaminants in the installation environment
    (b) Sensor maintenance
    Do not damage sensor surface during maintenance process
    (c) Troubleshooting
    If any problem occurs during operation, refer to the table below for appropriate solutions

  2. Troubleshooting:
    Problem| Cleck items| Soluations
    ---|---|---
    • No output
    • Unstable output| • Disconnected wiring
    • Loose wiring
    • Power supply voltage
    • Sensor damages| • Re-perform wiring
    • Crew on terminal tightly or replace wires
    • Replace the sensor
    • Slow response to output
    • Error in output| • Moisture / Condensation on the product
    • Check installed location
    • Check installed angle
    • Check dust and contamination on the sensor| • Remove the sensor and filter dry power-off state sensor in clean air seasoning
    • Refer to the section
    • Align measurement head with flow direction
    • Cleaning the filter
    • Changing the filter
    • Calibrate
    • Replace the sensor

Sustainable | Green | Professional
Temp. & Humid. / Dew Point / Air Velocity & Volume / Flow / Pressure
Measuring Specialist
Tel.: 886-2-8221-2958
Web: www.eyc-tech.com
e-mail: [email protected]
www.eyc-tech.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

eyc-tech User Manuals

Related Manuals