| System light output (Lm)| System light output Emergency mode (Lm)|
---|---|---|---
WT120C G2 LED27S/840 PSU ELB3 L1200| 2700| 500| 1,4
WT120C G2 LED40S/840 PSU ELB3 L1200| 4000| 500| 1,4
WT120C G2 LED34S/840 PSU ELB3 L1500| 3400| 500| 1,8
WT120C G2 LED60S/840 PSU ELB3 L1500| 6000| 500| 1,8
WT120C G2 LED80S/840 PSU ELB3 L1500| 8000| 500| 1,8
WT120C G2 LED27S/840 PSD ELB3 L1500| 2700| 500| 1,5
WT120C G2 LED40S/840 PSD ELB3 L1500| 4000| 500| 1,5
WT120C G2 LED34S/840 PSD ELB3 L1500| 3400| 500| 1,9
WT120C G2 LED60S/840 PSD ELB3 L1500| 6000| 500| 1,9
WT120C G2 LED40S/840 IA1 ELB3 L1200| 4000| 500| 1,5
WT120C G2 LED60S/840 IA1 ELB3 L1500| 6000| 500| 1,8
WT120C G2 LED40S/840 WIA ELB3 L1200| 4000| 500| 1,5
WT120C G2 LED65S/840 WIA ELB3 L1500| 6500| 500| 1,8
|
Dimension(mm)
| Nr. of clips
---|---|---
A| B| C| D| E| Emin| Fmax
WT120C G2 LED27S L1200| 76| 1215| 80| 38| 538| 1062| 85| 10
WT120C G2 LED40S L1200
WT120C G2 LED34S L1500| 1515| 838| 1362| 12
WT120C G2 LED60S L1500
WT120C G2 LED80S L1500
Switch off the power supply before installation
PSU & IA1 & WIA versions
Switch off the power supply before installation
PSD versions
Through wiring
Use only optical sub-assembly that is delivered with housing in one box!
SERVICE
Light source (LED) is non-user replaceable. The light source contained in this
luminaire shall only be replaced by the manufacturer or his agent or a
similarly qualified person.
Do not touch electronic components!
Electronic components may be under high voltage. Caution, risk of electric
shock
9a **10![PHILIPS WT120C G2 EL CoreLine Waterproof
- FIG 16](https://manuals.plus/wp-content/uploads/2022/09/PHILIPS-WT120C-G2 -EL-CoreLine-Waterproof-FIG-16.png)**
The batteries have a life expectancy of 4 years. Do not touch electronic
components!
Electronic components may be under high voltage.
LED27S | LED34S | LED40S | LED60S/65S | LED80S |
---|---|---|---|---|
Driver type | PSU | PSD | PSU | PSD |
Speak [A] | 3.58 | 19.4 | 5.16 | 19.4 |
20.9
Tref [µs]| 40| 200| 47| 200| 47| 200| 270| 47| 192| 270| 230| 58| 192
Max. Nr of products
Drivers / MCB 16A type B [max.]| 80| 30| 60| 30| 60| 30| 22| 45| 29| 22| 24|
30| 29
Drivers / MCB 10A type B [max.]| 50| 18| 37| 18| 37| 18| 13| 28| 18| 13| 15|
18| 18
Drivers / MCB 16A type C [max.]| 136| 51| 102| 51| 102| 51| 37| 76| 49| 37|
40| 51| 49
Drivers / MCB 10A type C [max.]| 80| 31| 62| 31| 62| 31| 22| 46| 30| 22| 24|
31| 30
Light intensity distribution curves
Emergency mode
Battery Unit
Manufacturer:| Philips
Unit:| TrustSight 6.4V 4cell
3000mAh battery LFP
Technology:| Lithium-ion
Luminous flux:| 500 lm
Capacity:| 3000 mAh
Power:| 3 W
Duration:| 3 h
Nominal voltage:| 6,4 V
Maintenance instructions
To assure the lighting quality of this unique LED lighting concept there are only a few instructions regarding the maintenance of this LED luminaire:
- Do not stare into the LED light beam.
- The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or national requirements.
- Above an average concentration of sulfur affects the useful lifetime of the product.
E.g: Light color changes from white to blue. Typically in chicken & pig farms.
Functional Notice for Emergency Lighting
Automatic emergency time selection
After installation and power up the driver will detect the battery and
start the automatic detection process.
- During automatic detection, the indicator LED will light up with short green
- Between a minimum of 6 and a maximum of 30 seconds, the TrustSight driver will set the battery type (number of cells) and will set the emergency output power accordingly.
After that, the system is defined and fully operational. The battery type
definition has an influence on the performance during the self-test and on the
battery charge method. When the automatic battery detection process is
disrupted, e.g. by switching off the permanent mains, the detection process is
stopped and the TrustSight emergency driver will go into the emergency mode
with the lowest output power. At the next power-up, the automatic detection
process will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to
EN50172 clauses 7.2.3 and 7.2.4. Switch on in the emergency mode each month by
simulation of a failure of the supply to the normal lighting for a period
sufficient to ensure that each lamp is illuminated. Twice per year, each
luminaire shall be tested for its full rated duration (at least 3hrs).
For more information please consult the TrustSight Gen 3 Design guide. The
latest version is available online.
LED indicator (color/ flashing)| Error condition| Cause|
Solution
---|---|---|---
Green / no flashing| | System OK battery fully charged
Off| | Mains off EM mode, Rest mode, test in progress
Green / slow (0.25s on, 1.25s off)| | System OK battery is charging
Green / fast (0.25s on, 0.25s oft)| | System OK recently tested (< 5 days,
Australia mode only)
Red / no flashing| Battery voltage too high or too low| No battery connected|
Connect battery
| Wrong or bad battery connected| Replace battery
Red / fast (0.25s on, 0.25s off)| Output voltage too low or too high| Wrong
LED load connected| Connect the right load and perform a functional test
No load connected or output shorted| Wrong connection| Connect the right load
and perform a functional test
Red /slow (0.25s on, 1.25s off)| Failed test due to battery| Battery end-of-
life Charger failure| Replace the battery and perform a duration test. Replace
driver
Red-green / fast
Fast flashing: (on-time = 025s, off-time = 025s)
Slow flashing: (on-time = 0.25s, off-time = 1.25s)| | DALI device
identification|
Green/short
on-time = 50ms, off-time = 095s)| | Battery detection|
Disconnect before servicing
Luminaire has basic insulation between Low Voltage supply and control
conductors
GB The light source and/or control gear and/or the external flexible cable
contained in this luminaire shall only be replaced by the manufacturer or his
service agent or a similarly qualified person.
Storage, installation, use, operation, and maintenance of the products need to
be performed exactly according to the instructions in this manual and/or other
instructions as may be provided by us to guarantee the safe use of the product
over its entire lifetime. Failure to adhere to these instructions will
invalidate your entitlement to a warranty. Bolts with an indication of torque
strength on the drawing need to be tightened using a calibrated torque wrench.
Pre-assembled bolts need to be retightened again to the required torque
specification to assure maximum strength over a lifetime
This product contains a light source of energy efficiency class: see table or
label.
Zhaga-D4i and SR-certified compatibility – For Zhaga-D4i/SR-Certified
based luminaires only Zhaga-D4i/SR-Certified components/sensors are to be used
(see also: https://www.lighting.philips.co.uk/oem-emea/products/driving-
connected-lighting / https://www.lighting.philips.co.uk/oem-
emea/products/driving-connected-lighting). The functional compatibility of
two SR-certified and/or Zhaga-D4i controllers/sensors to be used in
combination, as well as the override possibility of any line-switch function
used in an SR-based/Zhaga-D4i luminaire, is to be released by the master
controller/sensor supplier. If using a NEMA 7-pin socket on an SR-based
luminaire, a full system verification is required. Not following this advice
can/will cause a risk of damage and non-compliance for which Signify cannot
take any responsibility.
© 2021 Signify Holding
All rights reserved. Reproduction in whole or in part is prohibited without
the prior written consent of the copyright owner. The information presented in
this document does not form part of any quotation or contract, is believed to
be accurate and reliable, and may be changed without notice. No liability will
be accepted by the publisher for any consequence of its use. Publication
thereof does not convey nor imply any license under patent- or other
industrial or intellectual property rights.
Signify Holding The Netherlands
References
- Sustainable LED lighting solutions | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Driving connected lighting | Philips lighting
- Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>