eyc-tech TP01-14 Temperature Transmitter Instructions

June 12, 2024
eyc-tech

Temperature-TP01
www.eyc-tech.com
Temperature Transmitter
(2-Wire RTD Head-Mounting Type)
Instructionseyc-tech TP01 14 Temperature
Transmitter

Features

  • High quality, good anti-interference, high cost performance
  • Large round head installation
  • -50 … 400°C or special range
  • 4 … 20 mA
  • ZERO / SPAN adjustable
  • Polarity protection ; Over-voltage ; Short-circuit

Introduction

  • Linearised temperature measurement with Pt100 sensor
  • To avoid temperature signal attenuation during long-distance transmission, it converts Pt100 into standard analog current output DC 4 … 20 mA(2-wire)
  • In this way, a stable and accurate figure can be collected and shown on the display of terminal instrument. The instrument includes PLC, digital display, industrial computer, etc

Applications

Integrated with thermocouple / Cooling system / Environment / Agriculture / Air conditioning engineering / Heating engineering / Storage tank / Equipment

Specification

Input|
---|---
Input signal| RTD Pt100 Ω(3-wire)
Cable resistance| ≦50 Ω(3 wires with the same resistance)
PT100Ω sensor current| <0.8 mA
ZERO adjustment range| ±10%
SPAN adjustment range| ±10%

Output

Signal|
---|---
Load resistance| DC 4 … 20 mA(2-wire)
Load resistance stability| ≦(Supply voltage – 8 V) / 0.02 A Ω
Pt100Ω signal disconnection| ±0.05% / 100 Ω
protection & output| >23 mA

Accuracy

Accuracy ±0.1% of F.S.

Temperature

Temperature drift <±0.015%F.S. / °C
Calibration temperature 20 … 28°C
Response time <250 ms

| Dimension |eyc-tech TP01 14 Temperature Transmitter -
Dimension Connection Diagrameyc-tech TP01 14
Temperature Transmitter - Connection Diagrameyc-tech TP01 14 Temperature Transmitter - Ordering
Guide

Additional Option Test Repor

■ILAC / TAF
YUDEN-TECH CO.,LTD. Calibration Laboratory – ( ILAC / TAF ) Test report.
(TAF accreditation:3032, complying with ISO / IEC 17025 ) TAF has mutual recognition arrangement with ILAC MRA

Project Measurand level or range
Resistance thermometer -40°C … +300°C
Thermocouple thermometer -20°C … +300°C

※Need to cooperate with Pt100 temperature sensor
■ ISO 9001

| Measurand level or range
---|---
RTD / Thermocouple| Resistance thermometer:-40°C … +300°C
Thermocouple thermometer:-20°C … +300°C

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

eyc-tech User Manuals

Related Manuals