eyc-tech THR23 CO2 Temperature and Humidity Transmitter Instruction Manual

June 12, 2024
eyc-tech

eyc-tech THR23 CO2 Temperature and Humidity Transmitter Instruction Manual
Temperature and Humidity Transmitter

Safety Precautions

  • Before using this product, the user must to read the details of this user’s manual, then use this product with correct steps.
  • This user’s manual is for reference while using / Setting this product, and required to conserve properly.
  • This product is improperly to use in explosion-proof area, do not use this product in dangerous situation where human health & life may be threaten & affected.
  • If the userinstalls this product in special environments as Dust-Free Room, Breed Environment for Animals, etc., please initiate a specialized product consultation to our professional sales of our company.
  • If the improper & dangerous results which result from improper operator or improper environment, our company will not bear any legal responsibility.

Warning

  • Please ensure the outlook / outbox do not have any damage which result from improper transportation, or malfunction which results from lost attachments.
  • Inorder to prevent the GM from damages. This product must be used in the proper environment which specified in this user’s manual.
  • Please implement the wiring operation under power-off status; otherwise, it will cause electric shock, or become the root cause of machinery breakdown.
  • For prevent equipment damage, disconnect the power supply from the product before performing any wiring and installation.
  • This product must be operated under ruled power supplying value, and be operated under the ruled normal operation conditions which described in the user’s manual ; otherwise, it may cause the disasters as fire accident or be the root cause of machinery breakdown.
  • This product must be operated under the operating conditions specified in manual to prevent equipment damage.
  • Installation and wring must be performed by qualified personnel in accordance with all applicable safety standards, according to applicable safety standards all wiring must comply with local codes of indoor wiring and electric installation rules.
  • All wiring must comply with the rule for indoor wiring and electrical installation rules. The screw must be tight for upper cover & lower base.
  • In order to prevent the interferences from frequency converter, etc., and avoid error signal to result in the product damage, please use the isolated conducting wire.
  • Please use crimp type terminal To prevent personal injury, do not touch the moving part of product in operation. It may cause high humidity atmosphere during the product was breakdown. Please take safety strategy.
  • While discard this product, the user must to comply with the related rules for industrial domestic wastes for different country / location.

Connection Diagram

Connection Diagram

Dimension

Dimension

RS-485 and Modbus

THGO3, THR23, GS23 integrate a RS-485 interface for digital communication as an option feature. Based on Modbus protocol makes the general convenience on PLC, HMI and PC connection. For Modbus protocol information please download the file from website. Besides the PLC, HMI application, the user software provide the device setting and data logging function, it also can free download from website.

Technical Data :

  1. Max. network size : 32 transmitters
  2. Communication : with COM-Port (serial interface) of PC
  3. Max. network expansion : 1200m (3937ft) total length at 9600 baud
  4. Transmission rate : 9600, 19200, 38400, 57600, 115200 Baud
  5. Parity : None, Even, Odd
  6. Data length : 8bit
  7. Stopbit : 1or2 bit
  8. Factory default Station address 1, Data format 9600, N81

Configuration

Download the software from eyc-tech official website, decompress it and execute it. Planning software operating system requirements: Windows XP SP2 or above.

  1. Hardware connection: Connect the THG03 / THR23 / GS23 to PC through USB to RS-485 or RS 232 to RS-485 cenverter

  2. Check the COM port number from Device Manager in Computer Management. e.g. COM1in illustration
    Configuration

  3. Open the Ul, go to function ” Interface” , clickitem ” Config” and then setting COM port, BAUD rate, data format and Station ID, pressed ” Apply” for connection
    Configuration

  4. Scan RS-485 connection
    Open the U, go to function ” Interface” , clickitem ” Config” and then setting COM port, pressed ” Scan” bottom for scan devices and pressed ” Close and Export ” when the interested devices found.
    Pick up the device that you want to connect to and then press “Apply” to go.
    Configuration

  5. Setting on Analog Output
    In the group of OUT1(OUT2), Output tab. Both outputl and output2 related setting could be found

  6. Quantity : Temperature, Relative Humidity, Carbon Dioxide (CO3)

  7. Analog type : Voltage or Current

  8. Analog Range : 0…20 mA /4 … 20 mA (if output current) / 0 … 10 V (if output voltage)

  9. Range for Upper and Lower

  10. Alarm Mode: Check the box if analog output pretends an alarm switch output

  11. Alarm Trigger Point: Upper and Lower

  12. Alarm Output Level: Upper and Lower
    Configuration

  13. Display Panel
    In the Monitor tab. There is a large display of available measurements.
    Configuration

  14. Setting on RS-485, Data Transmission Test and environment parameters There are 3 groups in setting tab. The description of each item as below.
    % Environment Parameters :

  15. Air Pressure Modbus Protocol :

  16. station ID

  17. Baud Rate

  18. Date Frame

  19. Modbus Echo Test Enable/Disable

  20. Modbus Echo Test Result Reset

  21. CO;Auto Calibration Wl CO2Auto Calibration : Function is enabled if the bar color green, otherwise function is disabled. In the general environment, the CO, concentration usually measured as 400ppm. The environments as From Room/ Office with the condition as midnight period & nobody status, the CO, concentration usually measured as 400ppm. Thus, eyc-tech use the average statistics values for 7 days to implement Self-Correcting feature. This feature is not adaptive to use in special environment as Factory/ Plant Greenroom where the CO, concentration may keep on high value & keep for long period. Others

  22. Write Setting

  23. Read Setting
    Configuration

  24. Data display and logging

  25. The measurement of OUT1 and OUT2 will be display here

  26. Clear plot chart

  27. Toggle the selection channel of color function, refer to item (8)

  28. Snap the current plot chart

  29. Display title of vertical axis (ON or OFF toggle in turn once click)

  30. Enable secondary axis (right axis)

  31. Change chart linestyle in turn

  32. Select the color of plot channel

  33. Export the records in plot buffer

  34. Enable horizontal axis

  35. Enable the legend of plot channel

  36. Enable the log function, the data in cvs format with comma delimiter

  37. The scale of horizontal scale

  38. Select the scale method of vertical axis

  39. Select the range of vertical axis

  40. The vertical axis, label of OUT1

  41. The vertical axis, label of OUT2
    Configuration

  42. Device Information

  43. Serial Number

  44. Model Name

  45. Firmware Version

  46. Firmware Checksum

  47. The activation of RS-485 function

  48. Programming range of measurements and offset values

  49. Analog Output Calibration Data

  50. Calibration Date
    Configuration

Inspection and maintenance

  1. Maintenance
    Since this product is inspected and calibrated for high accuracy at the factory before shipment, no calibration on the installation site is necessary when this product is installed. For inspection and maintenance follow the instructions below :
    (a) Periodicinspection
    Periodically inspect this product for its sensing accuracy and clean the cover. Set the period between inspections based on atmospheric dust and other contaminants in the CO., Temperature and Humidity Transmitter (Indoor) installation environment.
    (b) Sensor maintenance
    Do not damage sensor surface during maintenance process
    (c) Troubleshooting
    If any problem occurs during operation, refer to the table below for appropriate solutions.

  2. Troubleshooting :
    Problem| Cleck items| Soluations
    ---|---|---
    No output
    ®Unstable output| isconnected wiring
    @ Loose wiring
    ®power supply voltage
    ®Sensor damages| Re-perform wiring
    @ Crew on terminal tightly or
    replace wires
    ®Replace the sensor
    Slow response to
    output
    ®Error in output| Moisture / Condensation
    on the product
    ® Check installed location
    ® Check installed angle
    ® Check dust and
    contamination on the
    sensor| Remove the sensor and filter dry
    power-off state sensor in clean
    air seasoning
    ® Refer to the section
    ® Cleaning the filter of THGO3
    ® Calibrate
    ® Replace the sensor