BEGA 51 211.2 Ceiling Luminaire Downlight Instruction Manual

June 13, 2024
BEGA

BEGA logo 51 211.2 Ceiling Luminaire Downlight
Instruction Manual

51 211.2 Ceiling Luminaire Downlight

Technical amendments reserved
Ceiling luminaire · downlight for indoor use

BEGA 51 211.2 Ceiling Luminaire Downlight - indoor

Instructions for use

Application

Ceiling luminaire downlight · indoor luminaire with symmetrical wide beam light distribution.

Product description

Aluminium alloy housing, finish Stainless steel
Crystal glass, partially satin matt, with screw neck
Light-diffusing silicone lens
Reflector made of pure an doused aluminium 2 mounting holes ø 4.5 mm
Distance apart 96 mm Connecting terminals 2.5@
Earth conductor connection
LED power supply unit
220-240 V 0/50-60 Hz
DC 176-275 V
DALI-controllable
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire Safety class I Impact strength IK06 Protection against mechanical impacts < 1 joule
– Conformity mark Weight: 1.3 kg This product contains light sources of energy efficiency classes E

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lighting technology Half beam angle 55°
Lamp

Module connected wattage 16.4 W
Luminaire connected wattage 19 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 40 °C

51 211.2 K27

Module designation LED-0800/927
Colour temperature 2700 K
Colour rendering index CRI > 90
Module luminous flux 2295 lm
Luminaire luminous flux 1432 lm
Luminaire luminous efficiency 75,4 lm / W

51 211.2 K3

Module designation LED-0800/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 2395 lm
Luminaire luminous flux 1495 lm
Luminaire luminous efficiency 78,7 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or revamping.

Remove mounting plate from the luminaire housing.
Unplug the earth conductor connection (plug contact).
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductive to the earth conductor of the luminaire!
Lead the power connecting cable through the mounting plate.
Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
Establish the earth conductor connection on the earthing screw ( ) of the mounting plate.
Establish the earth conductor connection to the luminaire housing (plug contact).
Push silicone sleeves over the lines and establish the electrical connection to the terminals marked (L) and (N).
The two connecting terminals marked DA, DA are provided for digital control purposes.
If these terminals are not assigned, the luminaire will work with full light output.BEGA 51 211.2 Ceiling Luminaire Downlight -
purposes

IMPORTANT:
To ensure secure connection, the luminaire housing must be positioned precisely in relation to the mounting plate.
Make sure that the vertical bar inside the luminaire housing is positioned precisely in the area of the mounting hole on the long bar of the mounting plate.
Press the luminaire housing firmly against the mounting plate and turn it clockwise firmly against the stop.
Open luminaire: Unscrew glass from luminaire housing by turning it counter- clockwise.
To prevent the luminaire from turning on the mounting plate, hold the luminaire housing in place with one hand.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.
Spares

Spare glass 11 003 417 10M RG
LED power supply unit DEV-0402/490i
LED module 2700 K LED-0800/927
LED module 3000 K LED-0800/930
Reflector 76 001 658 M

BEGA logoBEGA Gantenbrink-Leuchten KG ·
Postfach 31 60 ·
58689 Menden ·
info@bega.com ·