BEGA 50 603.5 LED Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 50 603.5 LED Wall Luminaire

BEGA-50-603-5-LED-Wall-Luminaire-PRODUCT

Dimensions

BEGA-50-603-5-LED-Wall-Luminaire-FIG-1

Application

  • Wall luminaire · indoor luminaire with integrated power supply unit for many lighting tasks in interior applications.
  • The light emits upwards and downwards.

Product Description

  • Luminaire made of aluminium alloy
  • Finish Colour velvet black
  • Safety glass
  • Reflectors made of anodised pure aluminium 2 elongated fixing holes
  • Width 5 mm · 76,5 mm spacing
  • 1 cable entry for mains supply cable up to ø 10.5 mm max. 5 x 1.5@
  • Connecting terminal 2.5@ with plug connection
  • Earth conductor connection: 2-pole connection terminals for digital control
  • BEGA Ultimate Driver®
  • LED power supply unit: 220-240 V x 0/50-60 Hz
  • DC 176-276 V
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Impact strength IK07
  • Protection against mechanical impacts < 2 joule
  • BEGA-50-603-5-LED-Wall-Luminaire-FIG-2: Safety mark
  • CE: Conformity mark
  • Weight: 2.1 kg
  • This product contains light sources of energy efficiency class(es) E

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Specifications

Lamp

  • Module connected wattage: 16.2 W
  • Luminaire connected wattage: 19.3 W
  • Rated temperature: ta = 25 °C
  • Ambient temperature: ta max = 50 °C

50 603.5 K3

  • Module designation: 2x LED-0800/930
  • Colour temperature: 3000 K
  • Colour rendering index: CRI > 90
  • Module luminous flux: 2510 lm
  • Luminaire luminous flux: 1806 lm
  • Luminaire luminous efficiency: 93,6 lm / W

50 603.5 K4

  • Module designation: 2x LED-0800/940
  • Colour temperature: 4000 K
  • Colour rendering index: CRI > 90
  • Module luminous flux: 2550 lm
  • Luminaire luminous flux: 1834 lm
  • Luminaire luminous efficiency: 95 lm / W

Light technique

  • Wide beam rotationally symmetrical light distribution
  • Half beam angle 39°

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Undo set screw and lift off luminaire housing.
  • Loosen push plug connection and earth connection (plug connection).
  • Pass the power connecting cable through the cable entry in the mounting plate.
  • Note position of application of the mounting plate “arrow down”.
  • Fasten the mounting plate with the supplied fastening material or other suitable fastening material to the installation surface.
  • Make earth conductor connection.
  • Push silicone sleeves over the lines and make electrical connection to terminal (plug connection).
  • The two connecting terminals marked DA, DA are provided for digital control purposes.
  • If these terminals are not assigned, the luminaire will work with full light output.
  • Make earth conductor connection between luminaire housing and mounting plate.
  • Push plug into coupler as far as it will go.
  • Install luminaire housing over mounting plate and tighten set screw.
  • Note position of application of the luminaire “arrow down”.

Maintenance

Cleaning /Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares

  • Glass/Trim ring: 20 000 086 M
  • LED power supply unit: DEV-0312/500
  • LED module 3000 K: LED-0800/930
  • LED module 4000 K: LED-0800/940
  • Reflector: 76 001 798 M

BEGA Gantenbrink-Leuchten KG