BEGA 50101 LED Large Area Luminaire Instructions

June 13, 2024
BEGA

BEGA 50101 LED Large Area Luminaire

BEGA-50101-LED-Large-Area-Luminaire-product

Product Information

This product is a luminaire with an LED module. It has a connected wattage of 121.6W for the module and 134W for the luminaire. The rated temperature is 25 degrees Celsius, and the ambient temperature should not exceed 40 degrees Celsius. The module designation is 50 101 K3, and it has a color temperature of 3000K. The color rendering index (CRI) is greater than 90. The module has a luminous flux of 20320 lm, while the luminaire has a luminous flux of 17294 lm. The luminaire has a luminous efficiency of 129.1 lm/W.

Product Usage Instructions

  1. Before installation, make sure to read and understand the safety instructions provided in the user manual.
  2. The installation and commissioning of the luminaire should only be done by a qualified electrician to ensure compliance with national safety regulations.
  3. For additional protection against overvoltage and transients, it is recommended to use separate overvoltage protection components, which can be found on the manufacturer’s website.
  4. The luminaire must be installed by two persons.
  5. To mount the luminaire on a wall, connect the plug-in terminal of the luminaire to the socket of the mounting plate. Align the key holes at the rear of the fitting with the turn-and-lock parts of the outrigger arms and move until they stop. Rotate the luminaire clockwise and tighten it until it stops.
  6. To prevent unintentional loosening of the luminaire cover, use a Torx screwdriver (T10) to turn the torx screw in the edge of the luminaire housing until it stops.
  7. If the LED module needs to be replaced, disconnect the system and open the luminaire. Follow the installation instructions provided for the LED module. Make sure to replace any defective luminaire covers before closing the luminaire.
  8. For spare parts, the following are available: synthetic cover, LED power supply unit, and LED module with a color temperature of 3000K.

Dimension

Large-area luminaire for indoor useBEGA-50101-LED-Large-Area-Luminaire-fig
1

Application

  • Ceiling and wall luminaire · indoor luminaire made of impact resistant synthetic diffuser and metal housing.
  • Large-area luminaire with high light output and high uniform light distribution.

Product description

  • Large-area LED luminaire »MAXIMA«
  • Metal luminaire mounting plate, finish Colour white
  • Light-diffusing synthetic luminaire cover Silicone gasket
  • Mounting plate with 2 key holes, pitch circle ø 220 mm and 3 elongated holes, pitch circle ø 1.090 mm, width 6 mm
  • Connecting terminals 2.5@ · Plug system Earth conductor terminal
  • 2-pole connecting terminal for digital control
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-280 V
  • During DC operation the LED power is reduced to 15 %
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Impact strength IK10
  • Protection against mechanical
  • impacts < 20 joule
  • – Safety mark
  • – Conformity mark
  • Weight: 30.2 kg
  • This product contains light sources of energy efficiency class(es) D

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to  the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 121.6 W

  • Luminaire connected wattage 134 W

  • Rated temperature ta = 25 °C

  • Ambient temperature ta max = 40 °C
    50 101 K3

  • Module designation 8x LED-0690/930

  • Colour temperature 3000 K

  • Colour rendering index CRI > 90

  • Module luminous flux 20320 lm

  • Luminaire luminous flux 17294 lm

  • Luminaire luminous efficiency 129,1 lm / W

Notice prior to installation:

  • The installation of the luminaire must be carried out by 2 persons!
  • For the electrical connection the position of the entry openung of the round mounting plate must be considered.
  • It is essential to make sure that the outrigger arms of the mounting plate do not lose their exact arrangement of 6 x 60° when mounting them on the mounting surface!
  • When mounting the luminaires, it must be ensured that the ceiling surface has sufficient load-bearing capacity.
  • The fixing material included in delivery mustbe checked for suitability with the specific mounting plate used. If necessary, replace with suitable fixing material.
  • Please check the secure mounting of the luminaires after installation.

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Unpack mounting plate.
  • Pass the power connecting cable through the opening in the mounting plate.
  • Fasten the mounting plate with the supplied or other suitable fastening materials to the mounting surface – key holes -.
  • Mark the fastening points of the outrigger arms precisely on the mounting surface.
  • Fasten the outrigger arms of the mounting plate with the supplied or other suitable fastening materials to the mounting surface – elongated holes -.
  • Make sure that all the fastening points of the mounting plate and the outrigger arms are fully screw-fitted – see drawing!
  • Make the earth conductor connection and the electrical connection to the terminals of the mounting plate – plug connection.
  • For digital control please use the connecting terminal DA, DA.
  • In case this terminal is not used the luminaire will be operated at full light output.
  • Unpack luminaire and lift it with enclosed gloves.
  • ATTENTION: In order to avoid deformation under its own weight, do not deposit luminaire on its domed synthetic cover outside the package!

Wall mounting:

  • Pick up the luminaire and connect the plug-in terminal of the luminaire to the socket of the mounting plate.
  • Place the key holes at the rear of the fitting for the locking mechanism over the turn-and-lock parts of the outrigger arms and move as far as the stop.
  • Turn the luminaire clockwise and tighten as far as the stop.

BEGA-50101-LED-Large-Area-Luminaire-fig 4

Ceiling installation:

  • IMPORTANT: When the luminaire is installed on the ceiling, it is essential to use the provided steel retention wires.
  • Pick up the luminaire and hook the steel retention wires by the spherical nipple into the recesses of the outrigger arms.
  • Use a suitable tool to bend the lateral metal lugs towards the ceiling – see drawing.
  • This will ensure that the spherical nipple of the steel retention wire cannot disconnect itself.
  • Connect the plug-in terminal of the luminaire to the socket of the mounting plate.
  • Place the key holes at the rear of the fitting for the locking mechanism over the turn-and-lock parts of the outrigger arms and move as far as the stop.
  • Turn the luminaire clockwise and tighten as far as the stop.

BEGA-50101-LED-Large-Area-Luminaire-fig 5

To prevent unintentional loosening of the luminaire cover, turn the torx screw (T 10) in the edge of the luminaire housing until it stops (lock).

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleaning agents to remove dirt.
  • A defective synthetic cover must be replaced.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Defective luminaire cover must be replaced. Close the luminaire.

Spares

  • Synthetic cover 15 000 476
  • LED power supply unit DEV-0300/1400i
  • LED module 3000 K LED-0690/930

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com