BEGA 50565.1 Ceiling Luminaire for Indoor Use Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
- BEGA 50565.1 Ceiling Luminaire for Indoor Use
- Product Information
- Safety
- Overvoltage Protection
- Lamp Module Information
- Product Usage Instructions
- Application
- Product description
- Safety
- Overvoltage protection
- PRODUCT SPECIFICATION
- Installation
- Cleaning · Maintenance
- Spares
- ABOUT COMPANY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEGA 50565.1 Ceiling Luminaire for Indoor Use
Product Information
The product is a luminaire that requires installation and operation according to national safety regulations. The luminaire contains electronic components that are protected against overvoltage. It is recommended to use separate overvoltage protection components for additional protection. The luminaire has different module designations with corresponding color temperature, color rendering index, module luminous flux, luminaire luminous flux, and luminaire luminous efficiency.
Safety
The installation and operation of this luminaire should be carried out by a qualified electrician. The manufacturer is not liable for damage caused by improper use or installation. Any modifications to the luminaire should be done by the responsible person and will be considered as the manufacturer’s responsibility.
Overvoltage Protection
The electronic components in the luminaire are protected against overvoltage according to DIN EN 61547. Additional protection against transients can be achieved by using separate overvoltage protection components, which can be found on the manufacturer’s website at www.bega.com.
Lamp Module Information
- Module 50 565.1 K27: LED-0800/927, 2700 K, CRI > 90, 1200 lm, 943 lm (luminaire), 97.2 lm/W (luminaire)
- Module 50 565.1 K3: LED-0800/930, 3000 K, CRI > 90, 1255 lm, 986 lm (luminaire), 101.6 lm/W (luminaire)
Product Usage Instructions
- Installation:
- A qualified electrician should perform the installation.
- Ensure the luminaire housing is positioned precisely in relation to the mounting plate.
- Align the vertical bar inside the luminaire housing with the mounting hole on the long bar of the mounting plate.
- Press the luminaire housing firmly against the mounting plate and turn it clockwise until it stops.
- Opening Luminaire:
- To open the luminaire, unscrew the glass from the luminaire housing by turning it counter-clockwise.
- Hold the luminaire housing in place with one hand to prevent it from turning on the mounting plate.
- Replacement of LED Module:
- The LED module designation can be found on a label in the luminaire.
- To replace the module, disconnect the system and open the luminaire following the installation instructions for the LED module.
- Defective glass must be replaced before closing the luminaire.
Application
Ceiling luminaire · Indoor luminaire with wide beam light distribution.
Product description
- Aluminium alloy housing,
- finish Colour velvet white
- Crystal glass, partially satin matt, with screw neck
- Reflector made of pure anodised aluminium
- 2 mounting holes ø 4.5 mm
- Distance apart 96 mm
- The luminaire is suitable for through-wiring. Connecting terminals 2.5@
- Earth conductor connection
- LED power supply unit
- 220-240 V x 0/50-60 Hz
- DC 170-280 V
- BEGA Thermal Switch®
- Temporary thermal shutdown to protect temperature-sensitive components
- Safety class I
- r – Safety mark
- c – Conformity mark
- Weight: 0.95 kg
- This product contains light sources of energy efficiency classes E
Safety
- The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
PRODUCT SPECIFICATION
- Lamp
- Module connected wattage 8.1 W
- Luminaire connected wattage 9.7 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 45 °C
- 50 565.1 K27
- Module designation LED-0800/927
- Colour temperature 2700 K
- Colour rendering index CRI > 90
- Module luminous flux 1200 lm
- Luminaire luminous flux 943 lm
- Luminaire luminous efficiency 97,2 lm / W
- 50 565.1 K3
- Module designation LED-0800/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 1255 lm
- Luminaire luminous flux 986 lm
- Luminaire luminous efficiency 101,6 lm / W
Installation
- LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
- Remove mounting plate from the luminaire housing.
- Unplug the earth conductor connection (plug contact).
Please note:
- If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductive to the earth conductor of the luminaire!
- Lead the power connecting cable through the mounting plate.
- Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
- Establish the earth conductor connection to the luminaire housing (plug contact).
- Make earth conductor connection.
- Push silicone sleeves over the lines and make electrical connection.
IMPORTANT:
- To ensure secure connection, the luminaire housing must be positioned precisely in relation to the mounting plate.
- Make sure that the vertical bar inside the luminaire housing is positioned precisely in the area of the mounting hole on the long bar of the mounting plate.
- Press the luminaire housing firmly against the mounting plate and turn it clockwise firmly against the stop.
Open luminaire:
- Unscrew glass from luminaire housing by turning it counter-clockwise.
- To prevent the luminaire from turning on the mounting plate, hold the luminaire housing in place with one hand.
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
- Replacement of the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
- The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
- Defective glass must be replaced.
- Close the luminaire.
Spares
- Spare glass 11 003 417 10M RG
- LED power supply unit DEV-0141/250
- LED module 2700 K LED-0800/927
- LED module 3000 K LED-0800/930
- Reflector 76 000 980 .2
ABOUT COMPANY
- BEGA Gantenbrink-Leuchten KG
- Postfach 31 60
- 58689 Menden
- info@bega.com
- www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>