BEGA 66519 Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 66519 Wall Luminaire Instruction Manual

BEGA

Wandleuchte
Wall luminaire
Applique

Instructions for use

Application

Wall luminaire with two-sided light output. For illumination and design tasks in architecture.
The light directed downwards is intended to illuminate the wall and the horizontal surface in front of it.
The light directed upwards is intended to illuminate the wall and ceiling surfaces.


Product description

Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure® coating technology Clear safety glass
Silicone gasket
Reflector made of pure anodised aluminium Mounting plate with 2 fixing
holes ø 4.3 mm · 160 x 14 mm spacing
2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G 1.5@ Connecting terminal 2.5@ with plug connection
Earth conductor connection BEGA Ultimate Driver®
LED power supply unit 220-240 V x 0/50-60 Hz DC 176-264 V
DALI-controllable
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I Protection class IP 65
Dust-tight and protection against water jets Impact strength IK10
Protection against mechanical impacts < 20 joule
r – Safety mark c – Conformity mark Weight: 5.2 kg
This product contains light sources of energy efficiency classes D

Safety

The installation and operation of this luminaire are subject to national safety regulations.

Installation and commissioning may only be

carried out by a qualified electrician.

The manufacturer accepts no liability for damage caused by improper use or installation.

If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.


Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.

To achieve an additional protection against

e. g. transients, etc. we recommend separate overvoltage protection components.

You can find them on our website at

www.bega.com.

Lamp

Module connected wattage                            24.6 W
Luminaire connected wattage                       26.6 W
Rated temperature                                          ta = 25 °C
Ambient temperature                                      ta max = 50 °C 66 519 K3
Module designation                                        2x LED-0724/830
Colour temperature                                        3000 K
Colour rendering index                                 CRI > 80
Module luminous flux                                    3830 lm
Luminaire luminous flux                             2446 lm Luminaire luminous efficiency            92 lm / W 66 519 K4
Module designation                                       2x LED-0724/840
Colour temperature                                      4000 K
Colour rendering index                                 CRI > 80
Module luminous flux                                   3930 lmLuminaire luminous flux                         2523 lm Luminaire luminous efficiency 94,8 lm / W

Lighting technology

Half beam angle 17°

Installation

The luminaire must only be operated with the complete protective cover.

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

Undo screw at wall box and remove mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
Note position of application of the mounting plate “arrow down”.
Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
Make earth conductor connection and electrical connection to the connecting terminal (plug connection).
Push plug into coupler as far as it will go. Make earth conductor connection between luminaire and mounting plate.
Note position of application of the luminaire “arrow down”.
Place luminaire housing onto the mounting plate and fix it.
Make sure that gasket is positioned correctly.
Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.


Please note:

Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified
persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced. Close the luminaire.

Spares __

Spare glass                                                   14 000 212
LED power supply unit                              DEV-0270/700
LED module 3000 K                                 LED-0724/830
LED module 4000 K                                 LED-0724/840
Reflector                                                     76 001 134
Gasket glass                                                83 000 563
Gasket wall box                                          83 001 081
Sealing ring                                                 83 001 757