BEGA 50083.1 Wall Luminaire for Indoor Use Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
50 083.1
Technical amendments reserved
Wall luminaire for indoor use
Instructions for use
50083.1 Wall Luminaire for Indoor Use
Application
Open and free-radiating wall luminaire · indoor luminaire with hand-blown opal
glass and metal housing.
The character of the opal glass creates a smooth and uniform light
distribution in the room.
Product description
Metal luminaire housing, finish Colour white
Hand-blown opal glass
2 mounting holes Ø 6.5 mm
Distance apart 420 mm
Connection terminal 2.5@
Earth conductor connection
2-pole connecting terminal for digital control
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-276 V
During DC operation the LED power is reduced to 15 %
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Impact strength IK02
Protection against mechanical impacts < 0.2 joule
– Safety mark
**– Conformity mark
Weight:** 2.2 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 15.2 W |
---|---|
Luminaire connected wattage | 18.4 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 50 °C |
50 083.1 K3
Module designation | 4x LED-0626/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 2560 lm |
Luminaire luminous flux | 1995 lm |
Luminaire luminous efficiency | 108,4 lm / W |
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected conductive
to the earth conductor of the luminaire!
Installation
Only fix luminaire in position of application as pictured.
For relamping, mounting and dismantling of the glass please keep a distance of
500 mm above the luminaire.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Slide synthetic diffuser out of the LED supporting section.
Establish earth conductor connection and make the electrical connection to the
terminals.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Secure the luminaire housing to the installation surface with the fixing
materials provided or other suitable materials.
Make sure to use the gaskets supplied.
Note position of application “arrow down”.
Insert the synthetic diffuser by sliding into the LED supporting section until
the stop.
Loosen the knurled knob.
Position glass into luminaire housing and fix it with the knurled knob.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass | 11 003 227 .1R G |
---|---|
LED power supply unit | DEV-0158/700i |
LED module 3000 K | LED-0626/930 |