Wall luminaire
24488 Wall Luminaire
Instructions for use
Application
Wall luminaire with asymmetrical light distribution.
For lighting wall and ground surfaces.
**Product description
**
Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Safety glass, antireflection-coated Silicone gasket
Reflector surface made of pure aluminium
Mounting plate with 3 elongated holes, Width 6.5 mm · 80 x 145 mm spacing 2
screw cable glands with strain relief for through-wiring power connecting
cable ø 7–12 mm
1 screw cable gland closed at the factory with a dummy plug
Connecting terminal 2.5□ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
LED power supply unit 220-240 V x≂ 0/50-60 Hz
DC 176-276 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 66
Dust-tight and protection against strong water jets
Impact strength IK07
Protection against mechanical impacts < 2 joule
– Safety mark
– Conformity mark
Weight: 4.8 kg
This product contains light sources of energy efficiency class(es) C
Dark Sky
The light from this luminaire is directed evenly and highly efficiently onto
the surface to be illuminated and emits less than 1 % of the luminaire
luminous flux into the upper halfspace of the luminaire.
Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
Module connected wattage| 15.8 W
Luminaire connected wattage| 18.2 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 50 °C
24 488 K3
Module designation| LED-1081/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 3010 lm
Luminaire luminous flux | 2334 lm
Luminaire luminous efficiency | 128,2 lm / W
24 488 K4
Module designation| LED-1081/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 3095 lm
Luminaire luminous flux | 2400 lm
Luminaire luminous efficiency | 131,9 lm / W
- preliminary data
Installation
Undo hexagon socket head screws (wrench size 3 mm) up to the stop and
disassemble the mounting plate.
Pass the power connecting cable through the cable entry in the mounting plate.
The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the
enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket
insert and thrust screw (wrench size 22 mm) (see sketch).
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface.
Tighten screw cable gland.
Make earth conductor connection and electrical connection to the connecting
terminal (plug connection).
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Make sure that gasket is positioned correctly.
Push plug into coupler as far as it will go.
Place the luminaire onto the mounting plate and fix it.
Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass with frame graphite | 25 000 087 |
---|---|
LED power supply unit | DEV-0312/700 |
LED module 3000 K | LED-1081/830 |
LED module 4000 K | LED-1081/840 |
Reflector | 76 001 960 |
Gasket wall box | 83 001 097 |
Gasket glass frame | 83 002 042 |
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
Documents / Resources
| BEGA
24488 Wall
Luminaire
[pdf] Instruction Manual
24488, 24488K3, 24488K4, 24488 Wall Luminaire, Wall Luminaire, Luminaire
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>