BEGA 50215.1 Ceiling and Wall Luminaire
Product Information
- Safety: The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning must be done by a qualified electrician. The manufacturer is not liable for damage caused by improper use or installation.
- Overvoltage Protection: The luminaire’s electronic components are protected against overvoltage according to DIN EN 61547. Additional overvoltage protection components are recommended for extra protection against transients, which can be found on the manufacturer’s website.
- Lamp: The connected wattage for the lamp module is 23.2 W, and for the luminaire is 26.6 W.
- Rated Temperature: The rated temperature for the luminaire is 25°C.
- Ambient Temperature: The ambient temperature for the luminaire is between 30°C and 50°C.
- Module Designation: The module designation is 4x LED-0627/930.
- Colour Temperature: The colour temperature of the luminaire is 3000 K.
- Colour Rendering Index: The colour rendering index is CRI > 90.
- Module Luminous Flux: The module luminous flux is 3860 lm.
- Luminaire Luminous Flux: The luminaire luminous flux is 2650 lm.
- Luminaire Luminous Efficiency: The luminaire luminous efficiency is 99.6 lm/W.
Product Usage Instructions
Please note the following instructions for using the product:
- If the luminaire is to be mounted onto a metallic, electroconductive surface, ensure that the mounting surface is connected conductive to the earth conductor of the luminaire.
- If planning a linear arrangement of several luminaires, maintain a minimum distance of 30 mm between the luminaire caps for installation reasons.
- To prevent dirt accumulation on the LED modules, press the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points. Clip the luminaire cover into the groove of the aluminium profile and push it until it reaches the stop of the luminaire housing. Replace the housing cap and tighten lateral Torx countersunk screw T25.
- When replacing the LED module, refer to the designation noted on a label in the luminaire. The light color and light output of BEGA replacement modules match those of the originally fitted modules. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Follow the installation instructions for the LED module. Replace any defective luminaire cover and close the luminaire.
Dimension
Ceiling and wall luminaire for indoor use
Application
- Ceiling and wall luminaire · indoor luminaire made of impact resistant synthetic diffuser and aluminium housing.
- Luminaire with free-radiating and uniform light distribution for linear illumination in interior.
Product description
- Luminaire made of Aluminium, finish Colour white
- Light-diffusing synthetic luminaire cover 2 elongated fixing holes
- Width 5.5 mm · 500 mm spacing
- Connection terminal 2.5@
- Earth conductor connection
- 2-pole connecting terminal for digital control
- LED power supply unit
- 220-240 V x 0/50-60 Hz
- DC 176-264 V
- DALI-controllable
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect
- temperature-sensitive components without switching off the luminaire
- Safety class I
- Impact strength IK04
- Protection against mechanical
- impacts < 0.5 joule
- – Safety mark
- – Conformity mark
- Weight: 1.7 kg
- This product contains light sources of energy efficiency class(es) D
Safety
- The installation and operation of this luminaire are subject to national safety regulations.
- Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation.
- If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 23.2 W
- Luminaire connected wattage 26.6 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 30 °C
- 50 215.1 K3
- Module designation 4x LED-0627/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 3860 lm
- Luminaire luminous flux 2650 lm
- Luminaire luminous efficiency 99,6 lm / W
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected conductive
to the earth conductor of the luminaire!
Note:
If you a planning a linear arrangement of several luminaires, you must keep a
minimum distance of 30 mm between the luminaire caps for installation reasons.
Installation
- LED are high-quality electronic components!
- Please avoid touching the light output opening of the LED directly during installation or relamping.
- Remove the luminaire from the packaging and put it down so that the open rear side of its housing rests on a soft surface.
- Undo the lateral Torx countersunk screw T25 and remove the luminaire cap.
- Make the earth conductor connection and the electrical connection to the terminals.
- For digital control please use the connecting terminal DA, DA.
- In case this terminal is not used the luminaire will be operated at full light output.
- Drill mounting holes into the mounting surface – spacing 500 mm
- Fix the luminaire housing with enclosed or any other suitable fixing material onto the mounting surface.
- For wall installation note the position of application “arrow down”.
To prevent dirt accumulating on the LED modules, press the supplied plugs into
the housing holes of the luminaire profile above the screw-fitting points.
Clip the luminaire cover into the groove of the aluminium profile and push it
until the stop of the luminaire housing.
Replace the housing cap and tighten lateral Torx countersunk screw T25.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
- Defective luminaire cover must be replaced.
- Close the luminaire.
Spares
Synthetic cover 15 000 481 .4
LED power supply unit DEV-0388/700i
LED module 3000 K LED-0627/930
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com