DIMENSIONS
Application
Wall luminaire · indoor luminaire for brilliant light with crystal glasses and aluminium luminaire housing.
The luminaire directs the light of the lamps upwards and downwards.
Product description
- Luminaire made of Aluminium, finish Colour white
- Crystal glasses, partially satin matt, with screw neck
- Reflectors made of anodised pure aluminium 2 elongated fixing holes
- Width 5mm · 76,5mm spacing
- 1 cable entry for mains supply cable up to ø 10.5 mm max. 5 x 1.5@
- Connecting terminal 2.5@ with plug connection
- Earth conductor connection
- 2-pole connection terminals for digital control
- LED power supply unit
- 220-240 V x 0/50-60 Hz
- DC 176-280 V
- DALI-controllable
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Switch®
- Temporary thermal shutdown to protect
- temperature-sensitive components
- Safety class I
- – Safety mark
- – Conformity mark
- Weight: 2.2 kg
- This product contains light sources of energy
- efficiency class(es) E
Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only becarried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 16.2 W
- Luminaire connected wattage 19 W
- Rated temperature ta=25 °C
- Ambient temperature ta max=25 °C
50 601.1K3
- Module designation 2x LED-0800/930
- Colour temperature 3000 K
- Colour rendering index CRI >90
- Module luminous flux 2510 lm
- Luminaire luminous flux 1774 lm
- Luminaire luminous efficiency 93,4 lm/W
50 601.1K4
- Module designation 2x LED-0800/940
- Colour temperature 4000 K
- Colour rendering index CRI >90
- Module luminous flux 2550 lm
- Luminaire luminous flux 1802 lm
- Luminaire luminous efficiency 94,8 lm
Installation
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Undo set screw and lift off luminaire housing. Loosen push plug connection and earth connection (plug connection).
Pass the power connecting cable through the cable entry in the mounting plate.
Note position of application of the mounting plate “arrow down”.
Fasten the mounting plate with the supplied fastening material or other suitable fastening material to the installation surface.
Make earth conductor connection. Push silicone sleeves over the lines and make electrical connection to terminal (plug connection).
The two connecting terminals marked DA, DA are provided for digital control purposes. If these terminals are not assigned, the luminaire will work with full light output. Make earth conductor connection between luminaire housing and mounting plate. Push plug into coupler as far as it will go. Install luminaire housing over mounting plateand tighten set screw. Note position of application of the luminaire “arrow down”.
Cleaning · Maintenance
Disconnect the electrical installation.
Unscrew glasses with reflectors from luminaire housing. Remove reflector
retaining springs.
Clean luminaire and glasses.
Defective glass must be replaced.
Use only solvent-free cleansers.
Attach reflectors with retaining springs to glasses.
Screw glasses with reflectors into luminaire housing.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Defective glass must be replaced. Close the luminaire.
Spares
- Spare glass 11 003 417 10MRG
- LED power supply unit DEV-0409/500
- LED module 3000 K LED-0800/930
- LED module 4000 K LED-0800/940
- Reflector 76 000 980 .2