BEGA 50142.1 LED Ceiling and Wall Luminaire Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 50142.1 LED Ceiling and Wall Luminaire
Product Information
Product Description | Luminaire made of Aluminium, finish Colour white |
---|---|
Earth Conductor Connection | 2-pole connecting terminal for digital control |
LED Power Supply Unit | 220-240 V x 0/50-60 Hz DC 176-276 V |
LED Power Limitation | During DC operation the LED power is reduced to 15% |
DALI Control | DALI-controllable |
Basic Insulation | Provided between the mains and control cables |
Thermal Regulation | Temporary thermal regulation to protect temperature- |
sensitive
components without switching off the luminaire
Safety Class| I
Impact Strength| IK05
Weight| 2.3 kg
Energy Efficiency Class| D
Product Usage Instructions
Please note: If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductively to the earth conductor of the luminaire!
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer. The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve additional protection against transients, etc., we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Instructions for use
Application
Ceiling and wall luminaire · indoor luminaire made of the impact-resistant
synthetic diffuser and aluminium housing. Luminaire with free-radiating and
uniform light distribution for linear illumination in the interior.
Product Description
- Luminaire made of Aluminium, finish Colour white
- Light-diffusing synthetic luminaire cover 2 elongated fixing holes
- Width 6.5 mm · 875 mm spacing
- Connection terminal 2.5@
- Earth conductor connection 2-pole connecting terminal for digital control
- LED power supply unit
- 220-240 V x 0/50-60 Hz
- DC 176-276 V
- During DC operation the LED power is reduced to 15 %
- DALI-controllable Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Impact strength IK05
- Protection against mechanical impacts < 0.7 joule
- – Safety mark
- – Conformity mark
- Weight: 2.3 kg
- This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
- Module connected wattage: 34.8 W
- Luminaire connected wattage: 42 W
- Rated temperature: ta = 25 °C
- Ambient temperature: ta max = 45 °C
50 142.1 K3
- Module designation: 4x LED-0694/930
- Colour temperature: 3000 K
- Colour rendering index: CRI > 90
- Module luminous flux: 5540 lm
- Luminaire luminous flux: 4357 lm
- Luminaire luminous efficiency: 103,7 lm / W
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected conductive
to the earth conductor of the luminaire!
Note:
If you a planning a linear arrangement of several luminaires, you must keep a
minimum distance of 30 mm between the luminaire caps for installation reasons.
The synthetic cover of the luminaire body can expand by max. 7 mm when hot.
Installation
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping. Remove the luminaire from the packaging and put it down on a soft surface with the rear of the housing open. Undo the hex socket screw on the side of the luminaire cap. Push the luminaire body on the housing to the side until the luminaire body can be removed freely. Make earth conductor connection. Push silicone sleeves over the lines and make electrical connection to the terminals.For digital control please use the connecting terminal DA, DA. In case this terminal is not used the luminaire will be operated at full light output.
Fix the luminaire housing with enclosed or any other suitable fixing material onto the mounting surface. For wall installation note the position of application “arrow down”.
Pick up the luminaire body and insert the retention bolt into the opening in the housing (keyhole). Before you connect the LED, first swing up the two locking levers of the LED connection terminal. Make the LED connection at the luminaire terminal – use long-nose pliers if necessary. Check that the poles are correct,
black: “Driver -“,
red: “Driver +”.
Close the locking levers of the LED connection terminal. Push the luminaire
body against the housing cap. Make sure not to damage the connection wires
when pushing in. Tighten the hex socket screw on the side of the housing cap.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect the system. Undo the hex socket screw
on the side of the luminaire cap. Push the luminaire body on the housing to
the side and swing up the two locking levers of the LED connection terminal.
Disconnect LED connection at the luminaire terminal. Push the luminaire body
on the housing to the side until the luminaire body can be removed freely.
Unscrew the retention bolts (hexagon socket SW 3). Loosen the Pin-Torx
countersunk screw (T 20). Slide luminaire cover over the LED modules to the
side. Remove the LED module. Install the replacement LED module. Please follow
the installation instructions for the LED module. Defective luminaire cover
must be replaced. Reassemble the luminaire again in reverse order. Make sure
not to damage the connection wires when pushing into the housing cap.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleaning agents to remove dirt. A defective synthetic cover must be replaced.
Spares
- Synthetic cover: 15 000 482
- LED power supply unit: DEV-0159/1050i
- LED module 3000 K: LED-0694/930
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>