BEGA 50634 LED Recessed Ceiling and Wall Luminaire Instruction Manual

June 12, 2024
BEGA

**BEGA 50634 LED Recessed Ceiling and Wall Luminaire Instruction Manual

**

DIMENSIONS

Dimensions

Application

Recessed ceiling and wall luminaire · indoor luminaire with hand-blown opal glass, satinmatt and metal housing for connection to external LED power supply unit. They are ideal for places where a soft and uniform lighting distribution is required. For installation into ceilings or walls with a shallow depth in interior areas.

Product description

Luminaire housing made of metal
Opal glass, satin matt, with screw neck
Silicone gasket
Fixing is achieved by using two adjustable
wedge-shaped claws
1 connecting cable with strain relief and plug
connector system for BEGA power supply unit,
on/off or DALI
Safety class III 3

 Conformity mark
Weight: 1.2 kg

This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire  are subject to national safety regulations.Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage inaccordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com

Lamp

  • Module connected wattage 8 W
  • Luminaire connected wattage 10 W
  • Rated temperature ta=25 °C
  • Ambient temperature ta max=35 °C

50 634K3

  • Module designation LED-0329/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1220 lm
  • Luminaire luminous flux 976 lm
  • Luminaire luminous efficiency 97,6 lm/W

Installation

  Luminaire housing and external LED power supply unit must not be covered by any heat insulating materials.

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relampingA separate power supply unit is required to operate the luminaire. For connection to external LED-power supplyunit – accessory 13 206 or 13 207 – the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units.The recessed opening is covered by the frame of the luminaire housing. Fixing of the luminaire in the structure is achieved by using two adjustable wedgeshaped claws.

Installation in solid walls or ceilings
To accommodate the luminaire and the external power supply unit we recommend using the installation housing – accessory 13 024

Installation in suspended ceilings

A recessed opening of ø 118 mm with a minimum installation depth of 45 mm is required. The lateral clearance from the luminaire housing to parts of the building must be at least 50 mm. The claws grip behind the panel. The minimum thickness of the panel must be 3 mm and the maximum thickness 25 mm.

A panel with less than 5 mm thickness must be reinforced on the reverse side. Open luminaire:

Remove glass from luminaire housing by turning it counter-clockwise.

Connect plug part of the luminaire with power supply unit.

Connect to the LED power supply unit. Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling.

Push luminaire housing into the ceiling cut-out. Tighten evenly screws of claw fasteners. Screw glass with gasket into luminaire housing. Make sure that gasket is positioned correctly

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.

The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified

persons using standard tools.

Disconnect the system and open the luminaire.

Please follow the installation instructions for the LED module.

Inspect and, if necessary, replace the luminaire gaskets.

Defective glass must be replaced. Close the luminaire.

Accessories

Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.

13 206 Power supply unit on/off
13 207 Power supply unit DALI

The power supply units are only suitable for the operation of one LED luminaire.

13 024 Installation housing

For the accessories a separate instructions for use can be provided upon request.

Spares

  • Spare glass 11 003 468 .0B1RG
  • LED module 3000 K LED-0329/930
  • LED cover 75 003 495

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals