BEGA 12064.2 LED Recessed Ceiling Downlight Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
**BEGA 12064.2 LED Recessed Ceiling Downlight Instruction Manual
**
Instructions for use
Application
Recessed ceiling luminaire · indoor luminaire with hand-blown crystal glass
and metal housing for connection to external LED power supply unit. A focusing
/ dispersing lens bundles the powerful LED light in the centre of the
reflector for a direct proportion of downlight. At the same time, a proportion
of the dispersed light is used to illuminate the luminaire glass and to
generate the vertical illuminance. For installation into ceilings with a
shallow depth in interior areas.
Product description
- Luminaire housing made of metal
- Ceiling frame ring made of stainless steel
- Crystal glass with screw neck
- Additional focusing / diffusing lens made of partially frosted crystal glass
- Reflector made of pure, high-gloss anodized aluminium
- Silicone gasket
- Fixing is achieved by using two adjustable wedge-shaped claws
- Connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI.
- Safety class III 3
- Conformity mark
- Weight: 1.2 kg
- This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e.g. transients, etc. we recommend separate overvoltage
protection components. You can find them on our website at
www.bega.com.
Lamp
Module connected wattage 13.5 W
Luminaire connected wattage 16.5 W
Rated temperature ta=25 °C
Ambient temperature ta max=40 °C
12 064.2K3
Module designation LED-0328/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 2135 lm
Luminaire luminous flux 1637 lm
Luminaire luminous efficiency 99,2 lm/W
Lighting technology
Half beam angle 40
Installation
Luminaire housing must not be installed in heat-insulating material. LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
A separate power supply unit is required to operate the luminaire. For connection to external LED-power supply unit – accessory 13 201 or 13 204 – the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units.
Please note:
The black marked connector is not used to connect to the power supply unit 13
201 on/off. The recessed opening is covered by the frame of the luminaire
housing.Fixing of the luminaire in the structure is achieved by using two
adjustable wedgeshaped claws.
Installation into concrete ceilings:
For this purpose installation housing 13 026 is available.
Installation into inserted ceilings:
A recessed opening of ø 161 mm is necessary to accept the luminaire housing.
Recessed depth min. 45 mm. The lateral distance between recessed luminaire and
other building parts must be at least 50 mm. The claws catch the ceiling
facing from the back side. Minimum thickness of the ceiling facing is 3 mm. If
the ceiling facing has a thickness of less than 10 mm or in case of
aninstallation into plasterboard ceilings, the facing thickness in the region
of the claws must be increased from the back side. Open luminaire: Remove
glass from luminaire housing by turning it counter-clockwise. Connect plug
part of the luminaire with power supply unit. Push external LED power supply
unit and luminaire housing into the ceiling cut-out.
Luminaire housing and external LED power supply unit must not be installed
in heat-insulating material.
Tighten evenly screws of claw fasteners. Impress the enclosed cover ring about
the sealing ring onto the glass. Make sure that the sealing ring is seated
correctly! Slide enclosed – separately packed – dispersing lens into the
reflector. Screw glass with cover ring and dispersing lens into the luminaire
housing.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module. Inspect and,
if necessary, replace the luminaire gaskets. Defective glass must be replaced.
Close the luminaire.
Accessories
Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain
relief and plug connector system.
13 201 Power supply unit on/off
13 204 Power supply unit DALI
The power supply units are only suitable for the operation of one LED
luminaire.
13 026 Installation housing
For the accessories a separate instructions for use can be provided upon request.
Spares
Dispersing lens 11 003 042 10RG
Spare glass 11 003 048 42M1RG
LED module 3000 K LED-0328/930
Trim ring 72 000 160 L
Gasket glas 83 001 446
BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden ·
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>