BEGA 50003.1 LED Recessed Ceiling Downlight for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 50003.1 LED Recessed Ceiling Downlight for Indoor Use
Product Information
This product is a recessed ceiling luminaire with crystal glass designed to provide wide beam light. It is suitable for installation in suspended ceilings with a height of 1045 mm in interior applications. Please note that a remote power supply unit is required to operate this luminaire. If you wish to integrate this luminaire into a LCN or Zigbee controlled building management system, we recommend using our BEGA Control light control system.
For safety purposes, it is important to follow national safety regulations during the installation and operation of this luminaire. Only a qualified electrician should perform the installation and commissioning. The manufacturer will not be liable for any damage caused by improper use or installation. Any modifications made to the luminaire should be carried out by a person responsible for these modifications, who will be considered the manufacturer.The electronic components installed in the luminaire are protected against overvoltage according to DIN EN 61547. However, for additional protection against transients and other factors, we recommend using separate overvoltage protection components available on our website at www.bega.com.
The product specifications are as follows:
- Lamp Module connected wattage: 16.8 W
- Luminaire connected wattage: 21 W
- Colour temperature: 3000 K
- Colour rendering index (CRI): > 90
- Module luminous flux: 2440 lm
- Luminaire luminous flux: 1002 lm
- Luminaire luminous efficiency: 47.7 lm/W
Replacement parts available for this product include:
- Spare glass
- LED module 3000 K
- Trim ring
- Reflector
Please refer to the part numbers provided in the user manual for ordering these spare parts.
Product Usage Instructions
- Ensure that the suspended ceiling has a height of 1045 mm to accommodate the installation of this luminaire.
- Contact a qualified electrician to perform the installation and commissioning of the luminaire.
- Obtain a remote power supply unit to operate the luminaire.
- If you wish to integrate the luminaire into an LCN or Zigbee-controlled building management system, consider using our BEGAControl light control system.
- Follow national safety regulations during the installation and operation of the luminaire.
- Protect the luminaire against overvoltage by using separate overvoltage protection components, which can be found on our website at www.bega.com.
- Refer to the provided product specifications for details on wattage, colour temperature, CRI, luminous flux, and luminous efficiency.
- If any modifications need to be made to the luminaire, ensure that they are carried out by a person responsible for these modifications.
- When ordering replacement parts, refer to the part numbers provided in the user manual.
Dimension
Instructions for use
Application
Recessed ceiling luminaire with crystal glass for wide beam light. For
installation in suspended ceilings of 10- 45 mm in interior applications. A
remote power supply unit is required to operate this luminaire. If this
luminaire should be integrated into a LCN or Zigbee-controlled building
management system we recommend our BEGA Control light control system.
Product Description
LED recessed luminaire without power supply unit Luminaire made of cast
aluminum, aluminum and stainless steel Crystal glass with thread, partially
frosted Silicone gasket Reflector made of pure anodized aluminium Metal
ceiling frame ring, Colour white Luminaire housing with 2 fixing claws and
guide screws Ceiling aperture ø 128 mm Free space installation depth required
90 mm 1 connecting cable with strain relief and plug connector system for the
BEGA power supply unit, on/off or DALI Safety Class III 3 Protection class IP
65 Dust-tight and protection against water jets Impact strength IK06
Protection against mechanical impacts < 1 joule c – Conformity mark Weight:
1.2 kg This product contains light sources of energy efficiency class(es) E
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e. g. transients, etc. we recommend separate overvoltage
protection components. You can find them on our website at
www.bega.com.
- Lamp
- Module connected wattage 16.8 W
- Luminaire connected wattage 21 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 35 °C
- When installed in heat-insulating
- material ta max = 25 °C
- 50 003.1 K3
- Module designation LED-0800/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 2440 lm
- Luminaire luminous flux 1002 lm
- Luminaire luminous efficiency 47,7 lm / W
Light technique
Symmetrical wide beam light distribution Half beam angle 49°
Installation
A separate power supply unit is required to operate the luminaire.
For connection to external LED-power supply unit – accessory 13 192 or 10 528
– the luminaire is equipped with a connector. Note the operating instructions
of the LED power supply units. LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Installation into concrete ceilings:
For the installation of luminaire and external power supply unit we recommend
to use installation housing 10 441.
Installation into inserted ceilings:
A recessed opening of ø 128 mm is necessary to accept the luminaire housing.
Free space depth min. 90 mm. The lateral distance between the recessed
luminaire and other building parts must be at least 50 mm. The claws catch the
ceiling facing from the back side. The minimum thickness of the ceiling facing
is 10 mm. If the ceiling facing has a thickness of less than 10 mm or in case
of an installation into plasterboard ceilings, the facing thickness in the
region of the claws must be increased from the back side. Remove glass with
reflector from luminaire housing by turning counter-clockwise. Connect plug
part of the luminaire with power supply unit.
Push external LED power supply unit and luminaire housing into the ceiling cut-out. Tighten guide screws. When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed. When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed. Lead enclosed trim ring with gasket over the screw-neck of the glass. Make sure that gasket is positioned correctly. Insert glass with mounted reflector and frame ring by turning it clockwise into luminaire housing.
Maintainance
Cleaning · Maintenance
Clean the luminaire regularly with solvent-free cleansers from dirt. Defective
glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect from main supply. Unscrew glass with
ceiling frame ring from the luminaire housing by turning it counterclockwise.
Please follow the installation instructions for the LED module. Check gasket.
Screw in glass with ceiling frame ring by turning it clockwise beyond the
stop. The defective glass must be replaced.
Spares
- Spare glass 11 003 091 10R G
- LED module 3000 K LED-0800/930
- Trim ring 71 001 572 M2
- Reflector 76 001 335
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com