BEGA 50338.1 Recessed Ceiling Downlight Instruction Manual

June 12, 2024
BEGA

BEGA 50338.1 Recessed Ceiling Downlight

Product Information

  • Product Name: 50 338.1
  • Module Designation: K3
  • Colour Temperature: 3000 K
  • Colour Rendering Index: CRI > 90
  • Module Luminous Flux: 1355 lm
  • Luminaire Luminous Flux: 1041 lm
  • Luminaire Luminous Efficiency: 86.8 lm/W

Product Usage Instructions:

  1. The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning should only be carried out by a qualified electrician. The manufacturer is not liable for any damage caused by improper use or installation.
  2. To achieve additional protection against overvoltage and transients, it is recommended to use separate overvoltage protection components, which can be found on the manufacturer’swebsite.
  3.  Clean the luminaire regularly with solvent-free cleansers to remove dirt.
  4. To replace the LED module, follow these steps:
  5. Make sure the system is disconnected and the luminaire is opened.
  6. Refer to the installation instructions for the LED module and follow them carefully.
  7. Close the luminaire after replacing the module.

Note: The product also includes spares such as LED power supply unit, LED modules with different colour temperatures (3000 K  and 4000 K), and a reflector. These spares can be identified usingthe provided part numbers.

Recessed ceiling downlight for indoor use

BEGA-50338.1-Recessed-Ceiling-Downlight-01

Instructions for use

Application
Recessed ceiling luminaire · indoor luminaire with asymmetrical wide beam light distribution. For installation in suspended ceilings of 5-25 mm in interior applications.

Product description

  • Recessed LED ceiling luminaire  with a remote power supply unit
  • Luminaire housing made of cast aluminum Fixing is achieved by using  2 adjustable fastening springs
  • Reflector surface made of pure aluminium Light-diffusing disc
  • Recessed opening ø 170 mm
  • Required installation depth 90 mm Connecting cable 2 x 1,0@
  • External LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • Safety class II
  • Safety mark
  • CE   – Conformity mark
  • Weight: 0.45 kg

This product contains light sources of energy efficiency classes D, E

Lamp

  • Module connected wattage 10 W
  • Luminaire connected wattage 12 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 45 °C
  • When installed in heat-insulating
  • material ta max = 25 °C

50 338.1 K3

  • Module designation LED-0859/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1355 lm
  • Luminaire luminous flux 1041 lm
  • Luminaire luminous efficiency 86,8 lm / W

50 338.1 K4

  • Module designation LED-0859/940
  • Colour temperature 4000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1475 lm
  • Luminaire luminous flux 1133 lm
  • Luminaire luminous efficiency 94,4 lm / W

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to
the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.

You can find them on our website at www.bega.com.

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Cover the recessed opening with the stop ring of the luminaire housing.
The luminaire housing is then fixed in the recessed opening via two springs. Installation in suspended ceilings:
A recessed opening of 170 mm with a minimum depth of 90 mm is required.
The lateral clearance from the installation housing to parts of the building must be at least 50 mm.
The minimal thickness of the ceiling panel must be 5 mm and must not be greater than 25 mm. A ceiling panel with less than 5 mm thickness must be reinforced on the reverse.
The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires. Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling.
Place the LED unit on top of the luminaire housing over the reflector and lock it in place by turning it to the right.
Compress the fastening springs of the luminaire housing on both sides and slide the luminaire housing into the recessed opening.
The fastening springs lock into place behind the ceiling panel.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Close the luminaire.

Spares

  • LED power supply unit DEV-0375/350
  • LED module 3000 K LED-0859/930
  • LED module 4000 K LED-0859/940
  • Reflector 76 001 621

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals