BEGA 50452.1 LED Recessed Ceiling Downlight Instructions
- June 12, 2024
- BEGA
Table of Contents
Technical amendments reserved
Instructions
50452.1 LED Recessed Ceiling Downlight
Recessed ceiling downlight for indoor use
Instructions for use
Application
Recessed ceiling downlight · Interior luminaire with asymmetrical light
distribution for connection to an external LED power supply unit.
For surface-mounted installation in indoor suspended ceilings of 5-25 mm
thickness.
Product description
Recessed luminaire without power supply unit Luminaire housing made of cast
aluminium Installation housing is made of glass-fibre reinforced polyamide
with 2 fastening springs Reflector surface made of pure aluminium Optical
ilicone lens · BEGA Constant Optics ® Ceiling trim ring made of metal, Colour
white Safety glass Recessed opening ø 142 mm Required installation depth 105
mm 1 connecting cable with strain relief and plug connector system for BEGA
power supply unit, on/off or DALI Safety class III 3 – **** Conformity mark
Weight: 0.8 kg This product contains light sources of energy efficiency
class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
Lighting technology
Half beam angle 65/69°
Lamp
Module connected wattage | 16.8 W |
---|---|
Luminaire connected wattage | 19.5 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 30 °C |
When installed in heat-insulating material | ta max = 25 °C |
50 452.1 K3
Module designation | LED-0800/830 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 2850 lm |
Luminaire luminous flux | 2129 lm |
Luminaire luminous efficiency | 109,2 lm / W |
Installation
A separate power supply unit is required to operate the luminaire.
For connection to external LED-power supply unit – accessory 13 145 or 13 171
– the luminaire is equipped with a 2-pin connector.
Note operating instructions of the LED-power supply units.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
The recessed housing is fixed in the recessed opening by screwing it to the
ceiling from below.
Installation in suspended ceilings:
A recessed opening of 142 mm with a minimum depth of 105 mm is required.
The lateral clearance between the recessed housing and parts of the building
must be at least 50 mm.
Make the appropriate cutout in the suspended ceiling. The ceiling cutout must
have an all-round chamfer of 45°, depending on the thickness of the ceiling
panel.
Remove the ceiling mounting
plate by turning it upwards and out of the thread of the adjusting sleeve,
move it through the ceiling cutout and place it on the suspended ceiling.
Secure the ceiling mounting plate with screws (Ø 3.5 to 4 mm) suitable for
gypsum plasterboard panels from below through the suspended ceiling.
When doing so, hold the ceiling mounting plate through the ceiling
cutout.
Place the enclosed centre-plate made of rigid polystyrene foam on a plain
surface with the chamfer facing upwards.
Position the adjusting sleeve above the centreplate and press it in so that it
is flush with the surface – see drawing.
IMPORTANT: Make sure to use this centre-plate in order to guarantee the
correct installation of the luminaire in the ceiling!
Turn the adjusting sleeve into the thread of the previously fitted ceiling
mounting plate until it is exactly flush with the ceiling.
Fill the 45° chamfer of the ceiling cutout with standard filler and smooth it
so that it is flush.
Allow the filler to set completely! Press the centre-plate about 5 mm upwards
into the adjusting sleeve and then pull it down carefully to remove it from
the adjusting sleeve.
Connect to the LED power supply unit.
Route the LED power supply unit through the installation housing and place it
in the suspended ceiling.
Connect the 2-pin plug connector between luminaire and external LED power
supply unit. Press together the two internal fixing sliders inside the
luminaire housing.
Push the luminaire housing to the end of the installation housing and then
release the fixing sliders.
This mechanism ensures that the luminaire housing sits securely inside the
installation housing.
Ensure correct directionality towards the area to be illuminated.
Installation housing and external LEDpower supply unit must not be installed
in heat-insulating material.Please use the protective gloves
provided for the installation to prevent finger prints on the reflector.
Insert the reflector complete with the silicone lens into the three recessed
rims of the luminaire housing.
Make sure that the positioning bar of the reflector is placed inside the
correct recessed rim. That will ensure that the reflector is positioned
correctly in relation to the LED.
Carefully insert the locking bars of the ceiling trim ring into the 3
remaining openings in the luminaire housing and fix the ceiling trim ring with
a twist to the right.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Close the luminaire.
Accessories
Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain
relief and plug connector system.
13 145 Power supply unit on/off 13 171 Power supply unit DALI
The power supply units are only suitable for the operation of one LED
luminaire.
For the accessories a separate instructions for use can be provided upon
request.
Spares
Centre-plate | 06 000 419 |
---|---|
LED module 3000 K | LED-0800/830 |
Trim ring | 75 002 943 |
Reflector | 76 001 637 M |
50 452.1
BEGA Gantenbrink-Leuchten KG.
Postfach 31 60 ·
58689 Menden ·
info@bega.com ·
www.bega.com
Documents / Resources
| BEGA
50452.1 LED Recessed Ceiling
Downlight
[pdf] Instructions
50452.1, LED-0800-830, 50452.1 LED Recessed Ceiling Downlight, LED Recessed
Ceiling Downlight, Recessed Ceiling Downlight, Ceiling Downlight, Downlight
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>