GOSSEN METRAWATT R2500 Compact Controllers and Temperature Limiters Instruction Manual

June 12, 2024
GOSSEN METRAWATT

R2500 Compact Controllers and Temperature Limiters

Product Information

Product Name: R2500 Compact Controllers and
Temperature Limiters

Manufacturer: Gossen Metrawatt GmbH

Model Number: R2500

Controller Type: Compact controller, 48 x 48
mm, IP 67, with self-tuning, 2nd setpoint and 2 alarms, hot-runner
functions, data logger, alarm history, program controller, infrared
interface

Outputs:

  • Two-step, three-step, step-action controller with 2 transistors
    and 2 relays

  • Two-step, three-step, step-action controller with 2 transistors
    and 3 relays

  • Continuous, split range controller, discontinuous action
    controller with 1 continuous output, 1 transistor output, and 3
    relay outputs

Measuring Ranges:

  • Thermocouple Type J, L: 0 … 900 °C / 32 … 1652 °F
  • Thermocouple Type K, N: 0 … 1300 °C / 32 … 2372 °F
  • Thermocouple Type R, S: 0 … 1750 °C / 32 … 3182 °F
  • Thermocouple Type B: 0 … 1800 °C / 32 … 3272 °F
  • Thermocouple Type C: 0 … 2300 °C / 32 … 4172 °F
  • Thermocouple Type E: 0 … 700 °C / 32 … 1292 °F
  • Thermocouple Type T: 0 … 400 °C / 32 … 752 °F
  • Thermocouple Type U: 0 … 600 °C / 32 … 1112 °F
  • Resistance thermometer Pt100: 0 … 340 Ohm
  • Resistance thermometer Ni100: 0 … 50 mV

Feature: Measurement input: configurable
standard signal (0 / 2 … 10 V or 0 / 4 … 20 mA)

Auxiliary Voltage: 85 … 265 V AC, 48 … 62
Hz or 20 … 30 V DC

Extras: Heating current monitoring, RS 485 data
interface

Configuration: Default settings or configured
per customer requirements

Languages: German, English, Italian, French

Product Usage Instructions

  1. Read the operating instructions completely and carefully before
    using the device.

  2. Make sure that the operating instructions are available to all
    users of the instrument.

  3. If the device is exposed to extreme conditions (e.g. humidity,
    dust, or extreme temperature), remove it from operation and secure
    it against unintentional use.

  4. No special maintenance is required for the housing. Keep
    outside surfaces clean using a slightly dampened cloth. Avoid the
    use of solvents, cleansers, and abrasives.

  5. Repair and replacement of parts should only be carried out by
    trained personnel who are familiar with the associated
    dangers.

  6. If repair or parts replacement service is required, please
    contact Gossen Metrawatt GmbH or their
    representatives/subsidiaries.

Operating Instructions
R2500
Compact Controllers and Temperature Limiters

3-349-374-03 20/7.22

Contents

Page Contents

Page

Safety Features and Precautions …………………………………………………4 Maintenance ………………………………………………………………………….5 Repair and Replacement Parts Service …………………………………………5 Product Support Industrial Division ………………………………………………5 Device Identification ………………………………………………………………..6 Mechanical Installation / Preparation …………………………………………..8 Electrical Connection ………………………………………………………………8 Operation ……………………………………………………………………………10 Disabling Modifications …………………………………………………………..11 Performance After Activating Auxiliary Voltage …………………………….11 Operating Flow Chart …………………………………………………………….12 Automatic Operation / Off ……………………………………………………….13 Manual / Automatic Selection ………………………………………………….13 Controller Types ……………………………………………………………………19 Conversion of Parameter Sets ………………………………………………….20 Backup Functions ………………………………………………………………….20 PI Performance ……………………………………………………………………..20 Extra derivative action for cooling ………………………………………………20 Configuring the Switching Outputs and the Continuous Output ………..21 Relay Outputs for Actuating Signals …………………………………………..21 Actuator Output for Contactor …………………………………………………..22 Water Cooling ………………………………………………………………………22 Configuration of the Controller with Continuous Output ………………….22 Setpoint Ramps …………………………………………………………………….23

Suppression of Periodic Disturbances ………………………………………. 23 Adaptive Measured Value Correction ………………………………………… 24 Hot-Runner Control ………………………………………………………………. 25 Feed-Forward Control …………………………………………………………… 26 Parameters Configuration ………………………………………………………. 27 Program Controller ……………………………………………………………….. 29 Program Entry …………………………………………………………………….. 31 Manual Optimization …………………………………………………………….. 33 Self-Tuning ……………………………………………………………………….. 37 Balancing …………………………………………………………………………… 38 Limit Value Monitoring …………………………………………………………. 39 Limiter ………………………………………………………………………………. 39 Heating Current Monitoring …………………………………………………….. 40 Heating Circuit Monitoring ……………………………………………………… 41 Alarm History ………………………………………………………………………. 42 Data Logger ……………………………………………………………………….. 42 Error Messages …………………………………………………………………… 43 Error Acknowledgement ………………………………………………………… 44 Error mask …………………………………………………………………………. 45 Replacing an R2400 Controller with an R2500 Controller ……………… 47 Technical Data …………………………………………………………………….. 49 ……………………………………………………………………………………….. 50

Gossen Metrawatt GmbH

R2500 ­3

Gossen Metrawatt GmbH
Meanings of Symbols on the Instrument
Indicates EC conformity
Continuous doubled or reinforced insulation
Warning concerning a point of danger Attention: observe documentation!
Functional earth terminal, earthing for functional purposes only (no safety function)
The device may not be disposed of with the trash. Further information regarding the WEEE mark can be accessed on the Internet at www.gossenmetrawatt.com by entering the search term WEEE.

R2500 ­4
Safety Features and Precautions
The R2500 controller is manufactured and tested in accordance with safety regulations IEC 61010-1 / DIN EN 61010-1 / VDE 0411-1. If used for its intended purpose, the safety of the user and the device is assured. Read the operating instructions completely and carefully before using the device, Follow all instructions contained therein. Make sure that the operating instructions are available to all users of the instrument.
Observe the following safety precautions: ­ The device may only be connected to an electrical system which
complies with the specified nominal range of use (see circuit diagram and serial plate), and which is protected with a fuse or circuit breaker with a maximum nominal current rating of 16 A. ­ The installation must include a switch or a circuit breaker which serves as a disconnecting device.

The controller may not be used: ­ If it demonstrates visible damage ­ If it no longer functions flawlessly ­ After long periods of storage under unfavorable conditions (e.g.
humidity, dust or extreme temperature) In such cases, the instrument must be removed from operation and secured against unintentional use.

Maintenance
Housing No special maintenance is required for the housing. Keep outside surfaces clean. Use a slightly dampened cloth for cleaning. Avoid the use of solvents, cleansers and abrasives.
Repair and Parts Replacement Repair and replacement of parts conducted at a live open instrument may only be carried out by trained personnel who are familiar with the dangers involved.

Repair and Replacement Parts Service
If required please contact:
GMC-I Service GmbH Service Center Beuthener Straße 41 90471 Nürnberg, Germany Phone +49 911 817718-0 Fax +49 911 817718-253 E-Mail service@gossenmetrawatt.com www.gmci-service.com

Return and Environmentally Sound Disposal The R2500 is a category 9 product (monitoring and control instrument) in accordance with ElektroG (German electrical and electronic device law). This device is subject to the WEEE directive. Furthermore, we make reference to the fact that the current status in this regard can be accessed on the Internet at www.gossenmetrawatt.com by entering the search term WEEE. We identify our electrical and electronic devices in accordance with WEEE 2012/19/EU and ElektroG with the symbol shown at the right per DIN EN 50419. These devices may not be disposed of with the trash. Please contact our repair and replacement parts service department regarding the return of old devices.

This address is only valid in Germany. Please contact our representatives or subsidiaries for service in other countries.
Product Support Industrial Division
If required please contact:
Gossen Metrawatt GmbH Product Support Hotline ­ Industrial Division Phone: +49 911 8602-500 Fax: +49 911 8602-340 E-Mail: support.industrie@gossenmetrawatt.com

Gossen Metrawatt GmbH

R2500 ­5

Gossen Metrawatt GmbH

Device Identification

Feature

Compact controller, 48 x 48 mm, IP 67, with self-tuning, 2nd setpoint and 2 alarms, hot-runner functions, data logger, alarm history, program controller, infrared interface

Controller Type

Outputs

Two-step, three-step, step-action controller

2 transistor, 2 relay

Two-step, three-step, step-action controller

2 transistor, 3 relay

Continuous, split range controller, discontinuous action controller

1 continuous, 1 transistor, 3 relay

Measuring Ranges

Configurable measurement input

Thermocouple

Type J, L

0 … 900 C /

32 … 1652 F

Type K, N

0 … 1300 C /

32 … 2372 F

Type R, S

0 … 1750 C /

32 … 3182 F

Type B

0 … 1800 C /

32 … 3272 F

Type C

0 … 2300 C /

32 … 4172 F

Type E

0 … 700 C /

32 … 1292 F

Type T

0 … 400 C /

32 … 752 F

Type U

0 … 600 C /

32 … 1112 F

Resistance thermometer Pt100

­ 200 … 600 C / ­328 … 1112 F

Ni100

­ 50 … 250 C / ­58 … 482 F

Ohm

0 … 340

Linear

0 … 50 mV

R2500 ­6 Designation
R2500 A1 A2 A5
B1

Feature Measurement input: configurable standard signal
0 / 2 … 10 V or 0 / 4 … 20 mA Auxiliary Voltage 85 … 265 V AC, 48 … 62 Hz 20 … 30 V DC Extras Heating current monitoring RS 485 data interface Configuration Default settings Configured per customer requirements Operating Instructions German English Italian French None
Gossen Metrawatt GmbH

Designation B2
C1 C2 E0 E1 K0 K9 L0 L1 L2 L3 L4
R2500 ­7

Gossen Metrawatt GmbH
Mechanical Installation / Preparation

48 48

104 119
5

R2500 ­8
behind at the top and bottom with the two included snap retainers. Several devices can be mounted next to each other without separators at the side.
In general, unobstructed air circulation must be assured when one or several devices are installed. The ambient temperature underneath the devices may not exceed 50 C. In order to assure IP 67 protection, an appropriate seal must be installed between the device and the panel.

45+0.6
45+0.6
Figure 1: Housing Dimensions and Panel Cutout
The R2500 controller is intended for installation to a control panel. The installation location should be vibration-free to the greatest possible extent. Aggressive vapors shorten the service life of the controller. Requirements set forth in VDE 0100 must be observed during the performance of all work. Work on the device may only be carried out by trained personnel who are familiar with the dangers involved. Set the housing into the panel cutout from the front, and secure it from

Electrical Connection
Connectors: screw terminals for wire with 1.5 square mm cross-section or two- core wire-end ferrules for 2 0.75 square mm

1

12

2

12

3

14

4

15

5

15

6

16

7

17

8

18

9

19

10

20

Figure 2: Connector Terminal Positions

Attention: to ensure radio interference suppression, the protective conductor and/or control cabinet grounding must be connected to terminal 13.

Binary Input

Transistor Output

Cont. Output

Auxiliary Voltage

A1, A2, A5

A5

C1

C2

1

1

11 L

110 / 230 V AC 24 V DC

2

­

­

20 mA / 10 V

12 N

­

3

+ out1

3+

13

4

+ out2 + out2 4

14

5
20 mA
6
10 V
7

5

15

out 1

6

16

7

17

8

A

9

B

10

C

8

18

A2

9

19

A1

10

20

B1

B2

Sensor

E0
Heating Current Transformer

E1 RS 485

Relay Outputs

A2, A5
Relay Output

Gossen Metrawatt GmbH

R2500 ­9

Gossen Metrawatt GmbH
Operation
Figure 3: Controls
Actual value Setpoint / heating current / manipulating factor (operating level)
Setpoint 2 active Manual operation
Switch displays, levels and values (see operating flow chart) Reduce value / increase value

R2500 ­10
Switching output for heating active Switching output for cooling active Alarm 1 active Alarm 2 active Infrared interface Select: Off/manual automatic operation

Setting Values with the Up and Down Scroll Keys ­ At the operating level, the setpoint can be adjusted within a range extending from the minimum to the maximum setpoint. ­ Configuration and parameter settings can be changed if password protection has not been activated, or if the correct password has been entered. ­ In order to avoid erroneous settings, changes must be acknowledged within 5 seconds with the key. ­ The change can be discarded by pressing the key.

Disabling Modifications
The default setting (PSEt = dEF) allows for modification of all parameters and configurations. The following settings can be used in order to disable the entry of changes: Disabling Setpoint Changes The setpoint can only be adjusted between its minimum and maximum values. The SPL and SPH parameters must be set accordingly. Disabling Changes to Parameters and Configurations After password protection for device operation has been activated (PASS not equal to diS), changes can only be made after the correct password has been entered. However, changes are always possible via infrared or bus interface! Disabling Self- Tuning Starting self-tuning by pressing the corresponding keys can be separately disabled with the configuration tunE = diS. However, self-tuning can always be started via infrared or bus interface!
Performance After Activating Auxiliary Voltage

LED Segment Test

U/M

Designations

Actual Value

Approx. 1.5 s

Approx. 1.5 s

Approx. 1.5 s

Firmware Version

Setpoint or oFF

Gossen Metrawatt GmbH

R2500 ­11

Gossen Metrawatt GmbH

R2500 ­12

Operating Flow Chart
Operating Level

Automatic Operation

Actual

Actual Setpoint

Actual Ht. Current

Actual Man. Factor

Actual

Setpoint can only be set here
Parameter Level (page 27)

With heat current monitoring only
Configure (page 14)

With program controller only
Program Controller

Param. Value *

Configuration *

Program

Param. Value

Configuration

Program

Press key briefly.

Press and hold key until display switches.

Press and hold both keys until display switches.

*) If password protection for device operation is activated (configuration: PASS = EnA ), the correct password must be entered in order to change values. Otherwise -no- appears at the display if an attempt is made to change a value.

Automatic Operation / Off

Operating Level

­ No alarm function ­ No indication of errors

Off Actual

The controller can be deactivated by pressing and holding the is configured to on/off.

key, if it

Manual / Automatic Selection

­ Alarm function and error indication identical to automatic operating mode.

­ The actuator outputs are controlled with the scroll keys and not by the controller function.

­ Switching between manual and automatic modes is bumpless in both directions.

­ PDPI controller: The manipulating factor is displayed as a percentage. Value

changes are forwarded immediately to the control outputs.

­ Step-action

controller:

The switching outputs can be adjusted directly with “more” or

“less” by pressing the up and down scroll keys.

Operating Level Manual Operation
Actual Man. Factor
If the key is configured to manual / automatic

Gossen Metrawatt GmbH

R2500 ­13

Gossen Metrawatt GmbH

Configuration

+ press and hold simultaneously

Configuration

Display

Sensor type

SEnS

U/M Input quantity
Controller type

SEnS SEnS
COut

R2500 ­14

Selection

tYP.j tYP.L tYP.K tYP.b tYP.S tYP.r tYP.n tYP.E tYP.t tYP.v tYP.C tYP.Pt 1 ni 1 ni12 rES 0HM Lin

Types J L K B S R N E T U C ­ Pt100 Ni100 Ni120 ­ Resistor in Voltage in mV

1°C, 1°F, 01. °C, 01. °F

0 – 20 / 4 – 20 dead / live zero

MEAS P0W 0n0F PdP1 ProP

Measure only Actuator Limit transducer 2/3 step, step-action, split range Proportional actuator

Standard
Type J
1°C 0 – 20 PdPI

Comment
Not with standard signal
With standard signal only See page 19

Configuration Derivative action
Binary input
Binary input

Display tu 11
1n 1
1n

Selection
dis / ena
phlt prun oFF SP 2 LooP HAnd tunE Quit FEF0 StvP booS LoGG Dark set2 baCk
stat dyn

Standard

­/ Extra derivative action for cooling diS

Pause program controller

Start/stop program controller

No function

Setpoint 2 active

Controller on

Manual operation

Start self-tuning

Clear limit value error

SP 2

Feed-forward control

Start-up active

Start boosting

Data logger recording

Display darkl

Parameter set conversion

Backup function

Binary input dynamic, switching by key

StAt

Comment only with 3-step controllers
The function of the binary input has precedence over operation and configuration.

Gossen Metrawatt GmbH

R2500 ­15

Gossen Metrawatt GmbH Configuration

Display

out1 switching output

0ut1

out2 switching output Switching output selection
Continuous Output
Continuous output Alarm 1 Alarm 2

0ut 2 0ut
Cont
Cont A 1 A 2

Selection

Standard

tr2 tr1 phlt prun oFF HEAt
CooL
H20 Hclo Cclo Hotr 1ndu al1l

Controller 2

Controller 1

Program pause

Program running

No function

Heater, more heat

with step-action controller

Cooling, more cooling

HEAt

with step-action controller

Water cooling

Less heat w. step-action controller

Less cooling w. step-action controller

Hot-runner heat

Induction heating

1st lower limit value

Same as out1 switching output

oFF

nor

As configured

xCh

Outputs out1 and out2

nor

exchanged with A1 and A2

oFF HEAt
CooL Proc SP

No function

Heater,

Cooling,

oFF

Current controlled variable

Current setpoint

0 – 20 / 4 – 20 Dead / live zero 20-0 / 20-4 dead / live zero invers

0 – 20

noc / ncc Operating current / idle current noc

noc / ncc Operating current / idle current noc

R2500 ­16 Comment
See page 21
See page 21 See pages 21 and 22, only if a continuous output is present (designation A5) See page 39

Configuration Channel error mask A1 Device error mask A1 Channel error mask A2 Device error mask A2 Alarm 1 Alarm 1 Alarm 1 Alarm 2 Alarm 2 Alarm 2 Limiter Heating circuit monitoring Adaptive measured value correction Actuator output for contactor PI performance Manual key function Start self-tuning

Display
A1M1 A1M2 A2M1 A2M2 AL 1 AL 1 AL 1 AL 2 AL 2 AL 2 L1M LbA AMC rELA p1 HKEY tune

Setpoint staircase

sp

Actuation inactive

Stvp

Selection

def / 1 … 3FFF

0 … 03FF

0 … 3FFF

0 … 03FF

rEL / AbS Relative / absolute

nSvP / SvP Start-up inhibiting off / on

nSto / Stor Alarm memory off / on

rEL / AbS Relative / absolute

nSvP / SvP Start-up inhibiting off / on

nSto / Stor Alarm memory off / on

no / yes

no / yes

no / yes

no / yes

no / yes

oFF / HAnd

EnA / diS Enable / disable

ramp step

Setpoint ramp Setpoint staircases, configurable with SPuP, SPdn and t SP

no / yes

Standard def 0 0 0 rEL nSUP nSto rEL nSUP nSto no no no no no oFF EnA
rAMP
no

Comment
see page 45
See page 39
See page 39 See page 41 See page 24 See page 22 See page 20 See page 13 See page 37 only for program controller See page 25

Gossen Metrawatt GmbH

R2500 ­17

Gossen Metrawatt GmbH Configuration

Display

Bus protocol

Prot

Baud rate Interface address Data logger recording Alarm History Program controller Password for operation 1)

bAUd Addr logg h1st prog PASS

Device settings, parameter set

pset

  1. Universal key = 42

Selection
r260 Mod r217 hbth
9.6 / 19.2
0 … 255
no / yes
no / yes
EnA / diS
EnA / diS
Act dEF GEt1 GEt2 GEt3 GEt4 Put1
Put2 Put3 Put4

DIN 19244 E same as R2600 Modbus DIN 19244 E same as R0217 HB-Therm
Enable / disable Enable / disable Retain active configuration Load default settings Load user configuration 1 … … Load user configuration 4 Save active configuration as user configuration 1 … … Save active configuration as user configuration 4

Standard r260
9.6 250 no no diS diS
Act

R2500 ­18 Comment With bus interface only
Not with DIN protocoll With bus interface only
See pages 11 and 12
Configuration per customer specification (K9) is saved to the user settings. All settings are overwritten during loading!

Controller Types

Controller Type Measure (Cout = MEAS) Actuator (Cout = POW) Limit transducer (Cout = OnOF)
PDPI controller and PDPI step-action controller (Cout = PdPI )
Proportional actuator (Cout = ProP)

Applications This configuration is intended for temperature monitoring. Limit value monitoring can be configured. System deviation is not used for any other purposes. Same as controller type 1 (measure) In addition, the actuator manipulating factor is read out with the actuating cycle. The maximum manipulating factor is read out if the actual value is less than the momentary setpoint. The minimum manipulating factor is read out if the actual value is greater than the momentary setpoint plus the dead zone. Switching hysteresis is adjustable, and status changes are possible after each actuating cycle. Actuating cycle time is used as a time constant for an additional input filter. The PDPI control algorithm assure short settling time without overshooting. The actuating cycle is at least as long as the selected value. The dead band inhibits switching back and forth between “heating” and “cooling” if no lasting deviation occurs. Selection of these two controller types, namely PDPI and PDPI step-action controller, defines the controller itself on the basis of the output configuration. The control variable is proportional to system deviation, and a statistical dead zone can be adjusted at the cooling side. Actuating cycle time is used as a time constant for an additional input filter. This controller type is not intended for temperature regulation, because it does not demonstrate the dynamics required for control without overshooting.

Gossen Metrawatt GmbH

R2500 ­19

Gossen Metrawatt GmbH

R2500 ­20

Conversion of Parameter Sets

If the binary input is configured to parameter set conversion (SEt2 ), parameter set 2 is loaded when the contact is closed, and paramter set 1 is loaded when the contact is open. The active configuration is overwritten in each case. The W2 LED lights up when parameter set 2 and/or 3 is active.

Backup Functions
If the binary input is configured to backup function (bACK), the momentary actual value is adopted as setpoint value when the contact is closed. Control is inactive and the manual operation LED lights up. When the contact is open, control is effected with the adopted setpoint value according to configuration.

PI Performance
The differential component of the PDPI controller type can be attenuated to such an extent by activating PI performance (configuration: PI = YES) that practically no more derivative action occurs. As opposed to a pure PI controller, response to setpoint changes can be configured without overshooting. This setting is advisable for control systems which include true delay time.

Extra derivative action for cooling
In controlled systems in which cooling has much better or worse thermal contact than heating, control performance for a cooling work point can be improved by setting the tu II configuration to EnA. This makes it possible to set the delay time for cooling (parameter tu II ) independently. In the case of water cooling, half the derivative action is automatically used for cooling when configuration tu II = diS has been selected.

Configuring the Switching Outputs and the Continuous Output
Switching output out1 is configured with a 2-step heating controller as a standard feature (relay or transistor output, depending upon variant). Control performance (2-step heating or cooling, 3-point discontinuous, step-action controller, continuous-action controller, split range controller) is determined by the configuration selected for the actuating outputs. See also the “Configuration” table on page 16. ­ Actuators for heating and cooling are selected independent of each other. ­ If 2-step control is required, heating and cooling outputs may not be configured simultaneously for the respective controller. ­ Both switching outputs can be assigned to the same controller output for separate control of several actuators with a single controller output. ­ If a continuous and a discontinuous output are both configured for heating (or cooling) at the same time, the channel performs like a
continuous-action controller and the discontinuous output is inactive. ­ If, inadvertently, only one “Less” output is configured for heating (or cooling), it remains inactive. ­ Settings can be freely combined regardless of controller type.
Relay Outputs for Actuating Signals
If two relay outputs are required for the actuating signals, for example in the case of three-step or step-action control, the alarm outputs can be exchanged with the actuator outputs. The Out = XCh configuration (see page 16) exchanges the functions of out1 with A1 and out2 with A2.

Gossen Metrawatt GmbH

R2500 ­21

Gossen Metrawatt GmbH

R2500 ­22

Actuator Output for Contactor

If, during ascertainment of control parameters (manual optimization or self- tuning), a cycle time results which is significantly shorter than advisable for the service life of the contactor, cycle time can be increased to the limit of system controllability by configuring the actuating outputs for contactor control (rELA = YES). If the bit is set before self-tuning is started, cycle time is set to the highest possible value by the self-tuning function.

Water Cooling
In order to account for the disproportionately powerful cooling effect which prevails when water is evaporated, the cooling control variable can be read out in a modified fashion by configuring the switching output for water cooling (Outx = H2O).

Configuration of the Controller with Continuous Output
Switching back and forth between current output and voltage output is automatic based upon load impedance.

Continuous output = heating or cooling

Cont = HEAt or CooL

The manipulated variable is read out within a range of 0 to 100% depending upon controller type.

Continuous output = controlled variable or setpoint Cont = Proc or SP The momentary controlled variable of the currently valid setpoint is read out. The read-out is scaled with the rnL and rnH parameters.

Setpoint Ramps

Function
Setpoint display Limit values

The parameters SPuP / SPdn cause a gradual temperature change (rising / falling) in degrees per minute. Activated by: ­ Switching auxiliary power on ­ Changing the momentary setpoint, activating setpoint 2 ­ Switching from manual to automatic operation The targeted setpoint is displayed (not the currently valid setpoint) with a blinking r at the left-hand digit. Relative limit values make reference to the ramp, not the targeted setpoint. As a rule, no alarm is triggered for this reason.

Suppression of Periodic Disturbances
If the measured value is superimposed with highly periodic oscillation which, for example, occurs due to cyclical withdrawal of energy from the control loop, the manipulated value may fluctuate between its extreme values resulting in unsatisfactory control results.

If the period is constant, this oscillation can be filtered out by setting the period in the oscillation suppression tSUP parameter. This is accomplished by means of narrow-band filtering in order to remove the signal component with the selected period, which is then disregarded for measuring signal control. The actual values for the display are not influenced. As opposed to adaptive measured value correction (see also page 24), oscillation can also be suppressed with this function whose periods are greater than half of the system’s delay time.

Periods can be selected within a range of 0.3 to 25 seconds, and the filter remains inactive for other setting values.

Due to the fact that this suppression filter influences control dynamics, ascertainment of control parameters by means of self-tuning or manual optimization has to be performed while oscillation suppression is active.

Gossen Metrawatt GmbH

R2500 ­23

Gossen Metrawatt GmbH

R2500 ­24

Adaptive Measured Value Correction

If a control loop is interfered with by periodic disturbance of the actual value, control can be improved by activating adaptive measured value correction. Periodic disturbance is thus suppressed, without impairing the controller’s ability to react to system deviations. Correction is adapted to the oscillation amplitude of the disturbance to this end, and only the mean value is forwarded to the controller.

Adaptation of correction to the disturbance is matched to prevailing control dynamics and requires no further parameters.

Prerequisites for improved control: ­ The oscillation amplitude of the disturbance must be constant, or may only change slowly. ­ The oscillation period must be less that half of the system’s delay time (parameter tu).

Due to the fact that correction greatly influences actual value ascertainment, control may also be worsened, for example if: ­ Measured value deviations are irregular ­ Individual measured value outliers occur ­ Fluctuation is not periodic ­ The disturbance is noise-like

Hot-Runner Control
By configuring the switching output for heating as a hot runner (Outx = Hotr), the manipulated variable is read out as a rapidly pulsating signal, i.e. actuation cycle time is 0.1 seconds regardless of the actuation cycle time parameter setting. With the help of this configuration, the start-up circuit and boost functions are also enabled.

Start-Up Circuit

The start-up circuit is enabled with the StUP = YES configuration, or by means of the binary input when it has been configured as follows: In1 = StUP.

The start-up circuit is only enabled for controller type PDPI. No start-up occurs for other controller types.

The start-up procedure is initiated if the actual value is more than 2 °C less than the start-up setpoint after auxiliary voltage is turned on (reset)

or after the off state has been ended,

or if the actual value drops to more than 40 °C less than the start-up setpoint after a start-up procedure has

been completed or during dwell time.

Start-up continues

until the actual value exceeds the start-up value minus 2 °C.

The control variable is limited to the start-up manipulating factor.

Dwell time then begins,

which is selected with the dwell time parameter.

The controller regulates temperature to the actuation setpoint.

The actuation procedure is ended as soon as dwell time has expired.

The controller then regulates temperature to the valid setpoint.

If the currently valid setpoint is still so far beneath the start-up setpoint that the condition for ending actuation cannot be fulfilled, the start-up procedure

continues indefinitely. In this case, control variable limiting by means of maximum manipulating factor would be advisable.

Gossen Metrawatt GmbH

R2500 ­25

Gossen Metrawatt GmbH

R2500 ­26

Temporary Setpoint Increase (boosting)

Temporarily increasing the setpoint in the hot-runner control mode can be used to free clogged mold nozzles of “frozen” material remnants.

This procedure is triggered by bit 3 of the controller function, which is set via the interface, keyboard or the binary input. The binary input must be con-

figured as follows to this end: In1 = booS. If the binary input is not used to this end, setpoint increase is activated or stopped by simultaneosly pressing

and holding the keys

. Boosting is ended by clearing this bit, or is stopped automatically after maximum boosting time has elapsed.

The relative increase is saved to the setpoint increase parameter, and the maximum duration of the increase is saved to the boost time parameter.

The increase effects the setpoint or setpoint 2 only, and has no influence on the start-up setpoint or the ramp function. The setpoint value, and not the

increase, is indicated with a b in the left digit.

Feed-Forward Control
When configured as a discontinuous or continuous-action controller (not as a step-action controller) control quality can be significantly improved by means of feed-forward control where abrupt load fluctuations prevail, if the binary input is configured for feed-forward control (In 1 = FEFO).
­ When the contact at the binary input is closed, the controller’s manipulating factor is increased by an amount of Y FF, ­ and is reduced by the same value when the contact is opened. ­ No function during self-tuning.
Example: If a machine requires an average of 70% heating power during production operation, but only 10% during idle time, the difference of Y FF is set to 60%, and the binary input is only activated during production.

Parameters Configuration

Press and hold

Parameters

Display

Upper limit value for relay A1

al1h

Lower limit value for relay A1 al1l

Upper limit value for relay A2

al2h

Lower limit value for relay A2 al2l

Setpoint 2

sp 2

Ramp for rising setpoints

spup

Ramp for falling setpoints

spdn

Heating current setpoint (see balancing)

amps

Proportional band heating

pb 1

Proportional band cooling

pb11

Dead band H/C

dbnd

Path delay time

tu

Cooling path delay time

tu11

Read-out cycle time Motor run-time Switching hysteresis

tc ty hyst

Gossen Metrawatt GmbH

X1 = lower range limit, X2 = upper rang limit, MRS = X2 ­ X1

Range

Standard Comments

oFF, 1 … MRS/2 oFF, X1 … X2

oFF

Relative (= default config.)

oFF

Absolute

SP L … SP H

X1

oFF, 1 … MRS/2 per min. oFF

oFF, 1 … MRS/2 per min. oFF

Auto, oFF, 0.1 … A H

oFF

0 … MRS/2

50

0 … MRS/2

50

0 … MRS/2

0

0 … 900 s

50 s

0 … 900 s

50 s

0.1 … 300 s

1 s

1 … 600 s

60 s

0 … MRS/2

4

See page 23
Not with step-action controller or bus interface
Only with 3-step controllers Not with 2-step controllers
Only with 3-step controllers if extra derivative action has been configured
Only with step-action controllers For limit value monitoring and limit transducers

R2500 ­27

Gossen Metrawatt GmbH

Parameters

Display

Maximum setpoint

sp H

Minimum setpoint

SP L

Maximum manipulating factor y H

Minimum manipulating factor y l

Actual value correction

Cal

Actual gain value

gain

Decimal point position

dpnt

Upper range limit, standard signal rn h

Lower range limit, standard signal rn l

Manip. factor for actuation mode y st

Manip. factor for feed-forward control y ff

Sensor error manipulating factor y se

Actuation setpoint

spsv

Start-up manipulating factor

y sv

Dwell time

t sv

Boosting (setpoint increase)

spbo

Boosting time

t bo

Oscillation inhibiting

tsvp

Range SP L … X2 X1 … SP H ­100 … 100% ­100 … 100% ­MRS/2 … +MRS/2 0 … 500% 0, 0.1, 0.02, 0.003 r n L … 9999 ­1999 … r n H ­100 … 100% ­100 … 100% ­100 … 100% SP L … SP H ­100 … 100% 0 … 300 s 0 … MRS/2 0 … 600 s oFF, 0.3 … 25 s

R2500 ­28

Standard X2 X1 100% ­100% 0 100% 0 100 0 0 0 0 0 10 0 0 0 oFF

Comments Limiting the setpoint entry
Not with standard signal With standard signal only
See page 26 See page 43
For hot-runner controllers only, see pages 25 and 26
See page 23

Program Controller

Activation

At the configuration level with ProG = EnA

Function

The current setpoint is determined exclusively by the program. Eight programs with twelve segments each are saved to the controller and can be selected. The functions which otherwise influence the setpoint, such as setpoint swapping and setpoint ramps, as well as the start-up circuit and boosting for hot- runner control, are without function.

Program

Each of the twelve program segments is defined by means of segment duration, targeted setpoint and the control tracks, and the program can be set to end upon completion of the first through the eleventh segment as well.

Sequence

StoP The program has been completed or stopped, or hasn’t yet been started (after a reset). The controller and the actuator outputs are inactive, relative limit value errors are suppressed. The momentary setpoint is set to the actual value. The program is started over again after it has been stopped.

run.X

The program has been started, possibly automatically after a reset (X stands for the current segment). The controller and the actuator outputs are active, relative limit value errors are enabled. Segment 1 is always executed when the program is started, and the initial setpoint is the actual value. The program can be started and stopped with a binary input: In1 = Prun.

Wt.X Same as for run.X. If “wait until setpoint is reached” has been selected (with WAit = YES), the program waits until system deviation amounts to only 2° C before activating the next segment.

Gossen Metrawatt GmbH

R2500 ­29

Gossen Metrawatt GmbH

R2500 ­30

hLt.X The running program has been halted, the momentary setpoint has been frozen (X stands for the current segment). The program can be halted with a binary input: In1 = PhLt.

Control tracks

Two control tracks can be activated for the duration of the segments. They can be assigned to available switching outputs with the setting: Out… = tr… The states run and hLt can also be assigned to available switching outputs with the settings: Out… = Prun and Out… = PhLt.

Control parameters

When the program controller is active, the control parameters should not (cannot) be set manually or by means of self-tuning, because a constant setpoint is required for usable optimization results. Select ProG = diS to this end.

Display

The displays are supplemented as follows at the operating level: The momentary setpoint appears at the setpoint display when a program is running, and only dashes appear after the program has been ended because there is no longer an active setpoint. The setpoint cannot be changed. A status display also appears. Current status, namely StoP, run.X, Wt.X or hLt.X (X stands for the current segment), appears at the bottom display.

Operation

The sequence can be controlled in the status display with the help of the up and down scroll keys, if it has not been configured to binary inputs. In order to avoid erroneous settings, changes must be acknowledged within 5 seconds with the key. The change can be discarded by pressing the key.

Program Entry

+ Press and hold simultaneously

Configuration

Display Selection

Program selection

ProG

no.1 Load program 1 … no.8 Load program 8 Put1 Save current program
to program 1
…Put8 Save current program to program 8
cLr Delete current program

Performance after reset Auto StoP / run

Wait Until Setpoint is reached wait no / yes

Type of segments

segs ramp / step Ramps/increments

Unit of time for segments tIME M-S / H-M Seconds / minutes

Duration of segment 1

MS 1

0:00 … 99:59

Target setpoint, segment 1 SP 1

SP L … SPH

Control tracks, segment 1 tr 1

—- … 21

Duration of segment 2

MS 2

End End of program 0:00 … 99:59

Target setpoint, segment 2 SP 2

SP L … SP H

Control tracks, segment 2 tr 2

—- … 21

Standard no. 1
StoP no rAMP M-S 0:00 0°C —End 0°C —-

Comment
Valid for all 8 programs Valid for all 8 programs Valid for all 8 programs Valid for all 8 programs
Specified numbers designate active control tracks. If End is selected, no further entries are displayed.

Gossen Metrawatt GmbH

R2500 ­31

Gossen Metrawatt GmbH

Configuration Duration of segment 12 Target setpoint, segment 12 Control tracks, segment 12

Display
MS12 SP12 tr12

Selection End, 0:00 … 99:59 SP L … SP H —- … 21

Example: Desired temperature-time profile:

setpoint

Standard End 0°C —-

Comment

R2500 ­32 Actual value

Control track 1 Control track 2

The pertinent program:

Segment

1

2

3

4

5

6

7

Duration MS 1…7 (HM 1…7 ) 0:40

0:30

0:20

0:50

0.00

0:50

End

Setpoint SP 1…6

100

100

180

180

120

120

Tracks tr 1…6

—1

—1

—-

–2-

–2-

–2-

Manual Optimization
Parameters Pb I, Pb II, tu and tc are determined by means of manual optimization in order to maintain optimized controller dynamics. A start-up test or an oscillation test is performed to this end. Preparation ­ Complete configuration (page 14) and parameter settings (page 27) must first be performed for use of the controller. ­ Deactivate the program controller, because a constant setpoint is required for the optimization procedure. ­ The actuators should be deactivated with the Off or Manual Operation function (page 13). ­ A recorder must be connected to the sensor and adjusted appropriately to prevailing circuit dynamics and the setpoint. ­ For 3-step or split range controllers, on and off time of the switching output for heating or the continuous output must be recorded (e.g. with an
additional recorder channel or a stopwatch). ­ Configure limit transducer (Cout = OnOF). ­ Set read-out cycle time to the minimum value: tc = 0.1. ­ If possible, deactivate manipulating factor limiting: Y H = 100. ­ Reduce (or increase) the setpoint so that overshooting and undershooting do not cause any impermissible values.

Performing the Start-Up Test ­ dbnd = MRS Setting for 3-step and split range controllers (switching output for cooling may not be triggered)
dbnd = 0 Setting for step-action controllers (switching output for cooling must be triggered) ­ Start the recorder. ­ Activate the actuators with Automatic Operation. ­ Record two overshoots and two undershoots. Actuation test is now complete for 2-step, continuous-action and step-action
controllers. Continue as follows for 3-step and split range controllers: ­ Set dbnd to 0 in order to cause further overshooting with active switching output for cooling. Record two overshoots and two undershoots. ­ Record on-time TI and off-time TII for the last oscillation at the switching output for cooling or the continuous output.

Gossen Metrawatt GmbH

R2500 ­33

Gossen Metrawatt GmbH
t
x P

dbnd = MRS xss

dbnd = 0 (3-step and split range controllers only)

R2500 ­34

TI

TII

Evaluating the Start-Up Test

­ Apply a tangent to the curve at the intersection of the actual value and the setpoint, or the cut-off point of the output.

­ Measure time t.

­ Measure oscillation amplitude xss, or for step-action controllers overshooting x. Parameter Value

tu

1.5 t

tc

tu / 12

Pb I Pb II Parameter

xss

­

Pb I (TI / TII)

2-step controller 3-step controller

2 xss

­

Pb I (TI / TII)

Cont.-action controller Split range controller

t ­ (tY / 4) tY / 100 x / 2 ­
Step-action controller

If manipulating factor limiting was active, the proportional band must be corrected: Y H positive: Pb I multiply by 100% / Y H Y H negative: Pb II multiply by -100% / Y H

Performing the Oscillation Test If a start-up test is not possible, for example if neighboring control loops influence the actual value too greatly, if the switching output for cooling must be active in order to maintain the actual value (cooling operating point), or if optimization is required directly to the setpoint for any given reason, control parameters can be determined by means of sustained oscillation. However, calculated values for tu may be very inaccurate in this case under certain circumstances. ­ Preparation as above. Test can be performed without a recorder if actual value is observed at the display, and if times are measured with a stopwatch. ­ dbnd = 0 Setting for 3-step, split range and step-action controllers ­ Activate the actuators with Automatic Operation, and if applicable start the recorder. Record several oscillations until they become uniform in size. ­ Measure oscillation amplitude xss. ­ Record on-time TI and off-time TII for the oscillations at the switching output for heating or the continuous output.

xss

TI

TII

Evaluating the Oscillation Test

tu 1 tc Pb I
Pb II Parameters

xss
­ 2-step controller

Parameter Value

0.3 (TI + TII) tu / 12

xss TII (TI + TII)
Pb I (TI / TII) 3-step controller

2 xss
­ Cont.-action controller

1 If either TI or TII is significantly greater than the other, value tu is too large.

2 xss TII (TI + TII) Pb I (TI / TII) Split range controller

0.2 (TI + TII ­ 2tY) tY / 100
xss / 2
­ Step-action controller

Gossen Metrawatt GmbH

R2500 ­35

Gossen Metrawatt GmbH
Correction with manipulating factor limiting Y H positive:Pb I multiplied by 100 % / Y H Y H negative:Pb II multiplied by -100% / Y H

R2500 ­36

Correction for step-action controllers in the event that TI or TII is smaller than tY:

Pb I multiplied by

tYtY TI TI

, if TI is smaller, or by

tYtY TII TII

, if TII is smaller.

The value for tu is very inaccurate in this case. It should be optimized in the closed loop control mode.

Closed Loop Control Mode The closed loop control mode is started after self- tuning has been completed: ­ Configure the desired control algorithm with controller type (Cout). ­ Adjust the setpoint to the required value. ­ For 3-step, split range and step-action controllers, the dead band can be increased from dbnd = 0, if control of the switching outputs (or continuous
output) changes too rapidly, for example due to an unsteady actual value.

Self-Tuning

Self-tuning is used to optimize controller dynamics, i.e. the Pb I, Pb II, tu and tc parameters are set.

Preparation

Start

Current

­ Complete configuration must be performed before self-tuning is started.

­ The setpoint value is adjusted to the value which is required after self- tuning.

­ Deactivate the program controller.

Slow Blinking

Start

­ Self-tuning can only be started if it has been enabled (configuration: tunE = EnA).

Abort

Current

­ Briefly pressing

both keys simultaneously at the operating level triggers self-tuning. Self- tuning cannot be

Current

started in the “actuator” or “limit transducer” mode.

or

­ tun1…tun9 blinks at the display at all levels during self-tuning.

­ The controller is switched to the automatic operating mode after self-tuning has been successfully completed.

­ In the case of 3-step controllers, cooling is activated if the upper limit value is exceeded in order to prevent overheating. Self-tuning then performs an oscillation

test around the setpoint.

Sequence

­ The setpoint which is active when tuning is started remains valid and can no longer be changed. ­ Activation or deactivation of setpoint 2 does not become effective. ­ Selected setpoint ramps are not taken into consideration. ­ If started at the operating point (actual value approximates the setpoint value), overshooting cannot be avoided. ­ There are no time limitations for the sequence. Self-tuning may take quite a long time, depending upon the control system. Abort

­ Self-tuning can be aborted at any time with the

key ( automatic operating mode), or by switching off with the

key.

­ If an error occurs during self-tuning, the controller no longer reads out an actuating signal. In this case, self-tuning must be aborted with the

key. Additional information regarding error messages upon request.

Self-tuning is enabled upon shipment from the factory (default setting). Starting the self-tuning function can be disabled in the configuration.

Gossen Metrawatt GmbH

R2500 ­37

Gossen Metrawatt GmbH
Balancing
Thermocouple Correction (parameter: CAL) The correction value is selected in C / F. The displayed correction value is added to the measured temperature.

R2500 ­38

Cable Compensation for Pt 100 with 2-Wire Connection (parameter: CAL) Balancing is performed manually if the sensor temperature is known: CAL = known sensor temperature ­ displayed temperature value

Correction of a Temperature Gradient (parameter: GAin) If the measured temperature value is not to be displayed, but rather a value which deviates from it, the GAin parameter is set to a value other than 100%:

GAin =

temperature to be displayed in C measured temperature in C

100%

Ascertaining the Nominal Heating Current Value (parameter: AMPS) By setting AMPS = Auto, control is interrupted for about 1 second, heating is activated and heating current is measured and saved as the nominal value. If the value is not equal to zero, heating current monitoring is automatically activated.

Limit Value Monitoring

Alarm Relay, NO Contact Alarm Relay, NC Contact

Hysteresis adjustable with HYSt parameter

Setpoint

Actual V

AL L AL L

AL H AL H

Relative Limit Values Absolute Limit Values

Start-up inhibiting: Alarm suppression is active during start-up (configuration: ALx = SUP) until temperature has exceeded the lower limit level for the first time. During cooling, suppression is active until temperature has fallen below the upper limit value for the first time. It is active when auxiliary power is activated, if the current setpoint is changed or setpoint 2 is activated, or if switching takes place from Off toAutomatic Operation.

Limiter
If a controller needs to be deactivated in the event of a limit value violation within the control loop, the controller must be configured as a limiter (LIM = YES). The limiter can be combined with all controller types. ­ The limiter responds to the second limit value, which must be set and configured accordingly. ­ The controller is deactivated as soon as a second limit value is violated. The controller becomes active again when there are no more limit value errors. ­ If the controller is to remain continuously deactivated after limit value monitoring has been triggered, the alarm memory must be activated
(configuration: AL2 = Stor). ­ The limit value errors must then be cleared in order to reactivate the controller. This is accomplished by pressing the key and acknowledging
the Quit AL display within 5 seconds with the key. ­ These errors can also be cleared with the binary input, if it has been configured to clear limit value errors (In 1 = quit).

Gossen Metrawatt GmbH

R2500 ­39

Gossen Metrawatt GmbH

R2500 ­40

Heating Current Monitoring

Current Measurement Function
Threshold AMPS current setpoint Activation

Heating current is acquired with an external transformer. Compatible with R2400 with GTZ 4121 for alternating and 3-phase current. An alarm is triggered if the current setpoint is fallen short of by more than 20% with activated heat (control output active), or if current is not “off” when the heat is switched off. The alarm is not triggered until heating current is high enough when the switching output for heating is active, and when current drops to zero when the switching output for heating is inactive. Monitoring is only active if discontinuous heating has been selected in the configuration, and not in the case of continuous and step-action controllers. The default monitoring threshold is 20%. Heater phase current is entered for this parameter. AMPS can be set to Auto for automatic adjustment with the heater switched on. The measured current value is saved to memory. Parameter AMPS not set to oFF.

Heating Circuit Monitoring

­ Function

­ Can be set to active or inactive with the LbA configuration

­ Without external transformer, without additional parameters

­ Assumes correct optimization of tu and Pb I control parameters!

Due to the fact that self-tuning generates other results in certain cases when heating circuit monitoring is activated,

heating circuit monitoring must be activated before self-tuning is started.

­ In the event of manual optimization or subsequent adaptation of control parameters, the lower limit for the tu parameter

must be observed:

Minimum tu =

2·Pb I t

t = maximum temperature rise during start-up

­ Error message LE appears after approximately 2 times tu, if heat remains on at 100% and measured temperature rise is too small.
­ Monitoring is not active: Where controller type = limit transducer, actuator or step-action controller During self-tuning With standard signal input (designation B2) Where manipulating factor limiting Y H < 20%

Gossen Metrawatt GmbH

R2500 ­41

Gossen Metrawatt GmbH

R2500 ­42

Alarm History

· The alarm history includes 100 error status entries with the respective time stamps. Whenever at least one entire bit of the overall error status changes, the complete error status is saved with the current time stamp.
· Recording is started over each time the device is reset, and data are lost if auxiliary power fails. Recording can be activated with the setting HISt = YES in the configuration, or via interfaces.
· After the ring buffer has been filled to capacity with 100 entries, the oldest entry is deleted each time a new one is recorded.
· Entries can only be read out via the bus interface or the infrared interface. See the interface description for detailed information.

Data Logger
· The data logger has enough capacity for 3600 sampled value pairs including actual values and manipulated variables. The logger sampling cycle can be configured within a range of 0.1 to 300.0 seconds. This results in recording times of 0.1 to 300 hours (6 minutes to 12 days).
· Recording must be started over again each time the device is reset, and data are lost if auxiliary power fails. · Recording can be started via a binary input, with the setting LoGG = YES in the configuration or via interface. · After the ring buffer has been filled to capacity with 3600 entries, the oldest values are deleted as new ones are recorded. · Entries can only be read out via the bus interface or the infrared interface. See the interface description for detailed information.

Error Messages

Responses in the event of an error:

1. Alarm output A1 is activated; its performance is determined by the configuration (see page 17).

2. LED A1 blinks at all levels, but the error message only appears at the operating level (upper display blinks).

3. Exceptions and additional information are included in the following table:

Display

Error Message Source

Response

sensor error high Broken sensor or actual value > upper range limit
sensor error low Sensor polarity reversed or actual value < lower range limit

Controller Sort
2 or 3-step
Step On/Off ctrl. Actuator

Manipulating Factor Read-Out

YSE = ­100/0/100%

YSE ­100/0/100%

­100/0/100%

If the controller has settled in: last “plausible” manip. factor,
If not: YSE

Control outputs inactive

YSE

No response to error

Remedy 1

current error Heating current

Current transformer has reversed polarity, is unsuitable or defective

Same as heating current monitoring alarm, continues to control temperature

2

display

no tune

Self-tuning cannot be started (controller No response to error, error display remains until sort: “actuator” or “limit transducer”). acknowledged (see below).

­

tune error 2

Disturbance in self-tuning sequence in Control outputs inactive, self-tuning must be aborted with

step 1 … 9 (in this case step 2)

the and keys.

3

Gossen Metrawatt GmbH

R2500 ­43

Gossen Metrawatt GmbH

R2500 ­44

Display

loop error

Error Message Source

Response

Measured temperature rise is too small Control outputs inactive, error message remains until

with heat on at 100%

acknowledged (see below).

Remedy 4

parameter error Parameter not within permissible limits Control outputs inactive, the parameter level is disabled.

5

digital error

Error detected by digital component monitoring

Control outputs inactive

6

analog error

Hardware error detected by analog component monitoring

Control outputs inactive

6

Remedies

1. Eliminate sensor error. 2. Inspect current transformer. 3. Avoid disturbances which impair the self-tuning sequence, e.g. sensor
errors. 4. Close the control loop: Check the sensor, the actuators and the heater for
correct functioning. Check sensor-heater assignments (wiring). Correctly optimize control parameters tu and Pb I.

5. Restore default configuration and default parameters, and then reconfigure or load user-defined default settings.
6. Arrange for repair at authorized service center.

Error Acknowledgement
Errors are acknowledged by pressing the key and acknowledging the Quit AL display within 5 seconds with the key.

Error mask
With the default setting (configuration A1M1 = def), relay output A1 reads out alarms from limit value monitor 1, as well as all other errors (sensor errors, heating current errors etc.), and relay output A2 only reads out alarms from limit value monitor 2. The individual error messages can be assigned to outputs A1 and A2 in a targeted fashion with the error masks. The values must be added and entered hexadecimally to this end. (Configuration is more user friendly with the Compact Config PC tool.)

Device error mask (A1M2 and A2M2)

Value

Meaning

0002

Heating current overrange

0004

Cold junction error

0010

Heating current not off

0020

Heating current too low

0040

Heating current too high

0100

Memory error

0200

Parameter error

Display CE CJE
Blinks Blinks Blinks
FE PE

default A1 A1 A1 A1 A1 A1 A1

Gossen Metrawatt GmbH

R2500 ­45

Gossen Metrawatt GmbH

Channel error mask (A1M1 and A2M1)

Wert

Meaning

0001

Broken sensor, 2nd input

0002

Reversed polarity, 2nd input

0004

Analog error

0008

Broken sensor

0010

Reversed polarity

0020

1st Lower limit value fallen short of

0040

2nd lower limit value fallen short of

0080

1st upper limit value exceeded

0100

2nd upper limit value exceeded

0200

Parameter impermissible for entry via interface

0800

Heating circuit error

1000

Self-tuning start-up error

2000

Self-tuning error or abort

Display SE H SE L AE SE H SE L Blinks
Blinks
LE no t tE X

default A1 A1 A1 A1 A1 A1 A2 A1 A2 ­ A1 ­ A1

R2500 ­46

Replacing an R2400 Controller with an R2500 Controller

Replacement with regard to feature A

R2400

Feature

Heating output Cooling output

A1

Transistor

A1

Relay

A1

Transistor

A1

Relay

A2, A4

Transistor

Transistor

A2, A4

Relay

Transistor

A2, A4

Transistor

Relay

A2, A4

Relay

Relay

Feature A1 A2 A1 A2 A1 A2 A2
A2

A3

Continuous

A5

A3

Continuous

A5

A3

Continuous

Relay

A5

A3

Relay

A5

A3

Relay

A5

A3

Relay

Relay

A5

Configuration Out1 = HEAt
Out1 = HEAt Out1 = CooL Out1 = CooL
Out1 = HEAt Out1 = HEAt Out1 = CooL Rewiring: Out1 = HEAt Rewiring: 17 to 18 Out1 = oFF Out1 = oFF
Out1 = CooL Rewiring: Out1 = HEAt
Out1 = CooL Out1 = HEAt Rewiring: 17 to 18

R2500

Out2 = oFF

Out2 = oFF

Out2 = oFF

Out2 = oFF

Out2 = CooL

Out2 = CooL

Out2 = HEAt

3 to 4 and 17 to 15

Out2 = CooL Out = XCh

15 to 20

16 to 19

19 to 16

20 to 15

Cont = HEAt

Cont = CooL

Cont = HEAt

17 to 15

Cont = Proc

Cont = Proc

Out2 = CooL Out = XCh

15 to 20

16 to 19

19 to 16

20 to 15

· When configured as a step-action controller (R2400, features A2, A4), the configuration of the corresponding output is not Outx = CooL in the case of the R2500, but rather Outx = HcLo.

Gossen Metrawatt GmbH

R2500 ­47

Gossen Metrawatt GmbH
Replacement with regard to features B and C: · Features B1 and B2 are identical for both devices. · Features C1 and C2 for the R2400 are feature C1 for the R2500. · Feature C3 cannot be replaced with the R2400. · Feature C4 for the R2400 is feature C2 for the R2500.
The following functions cannot be replaced: · Position acknowledgement display for step-action controller (R2400,
feature A4). Step-action controller function is available. · 24 V AC auxiliary power (R2400, feature C3)

R2500 ­48
measuring range span as is the case with the R2400. Conversion is accomplished as follows: Pb (R2500) = Pb (R2400) x mrs (R2400) / 100%.
! Attention!
To ensure radio interference suppression, the protective conductor and/or control cabinet grounding must be connected to terminal 13.

The following rewiring is required:
· The connector terminals on the R2400 can still be used, because the pin assignments are identical except for a few exceptions. The two plug connectors can be pulled out after loosening the lacquered screws.
· In the case of 230 V AC auxiliary power (R2400, feature C1), the conductor connected to terminal 13 is moved to terminal 12.
· If the actuating signal for cooling is read out via the relay, the corresponding connection must be changed (see table on page 47).
· If both actuating signals are read out via relay, the relay connections must be changed (see table on page 47).
Converting Parameters In the case of the R2500, the proportional bands are specified in the unit of measure of the controlled variable, instead of as a percentage of the

Technical Data

Ambient Conditions

Annual mean relative humidity, no condensation

75%

Ambient temperature

Nominal range of use Operating range Storage range

0 C … + 50 C 0 C … + 50 C ­25 C … + 70 C

Auxiliary Voltage Nominal Value 110 V AC 230 V AC 24 V DC

Nominal Range of Use

Voltage

Frequency

85 to 265 V AC

48 to 62 Hz

20 to 30 V DC

­

Power Consumption Typically 1.5 W

Electrical Safety Safety class Fouling factor Measuring category Operating voltage EMC interference emission EMC interference immunity

II, panel-mount device per DIN EN 61010-1, section 6.5.4 2, per DIN EN 61010-1, section 3.7.3.1 and IEC 664 II, per DIN EN 61010 appendix J and IEC 664 300 V per DIN EN 61010 EN 61326 EN 61326

Refer to the data sheet for complete technical data (3-349-377-03).

Relay output
Switching capacity Service life Interference suppression

Floating NO contact, common phase for switching outputs A1 and A2
250 V AC/DC, 2 A, 500 VA / 50 W

5 105 switching cycles at nominal load
Utilize external RC element (100 – 47 nF) at contactor

Gossen Metrawatt GmbH

R2500 ­49

Gossen Metrawatt GmbH

R2500 ­50

Gossen Metrawatt GmbH

R2500 ­51

© Gossen Metrawatt GmbH Prepared in Germany · Subject to change, errors excepted · PDF version available on the Internet
All trademarks, registered trademarks, logos, product names, and company names are the property of their respective owners.

Gossen Metrawatt GmbH Südwestpark 15 90449 Nürnberg · Germany

Phone +49 911 8602-0 Fax +49 911 8602-669 E-Mail info@gossenmetrawatt.com www.gossenmetrawatt.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GOSSEN METRAWATT User Manuals

Related Manuals