AIRFLOW iCON 15S SELV 12V Fan Range User Guide

June 9, 2024
AIRFLOW

AIRFLOW iCON 15S SELV 12V Fan Range

Product Information

The iCON SELV 12V DC fans are designed for ventilation in domestic premises and are available in two model sizes: iCON 15S and iCON 30S. These fans are powered by Safety Extra Low Voltage and can be fitted to a wall or ceiling. The iCON SELV range can be used as a simple extract SELV fan operated by a remote switch (standard) or can be fitted with an internal control module to give a range of control options (which includes: timer, humidity, motion sensor, pull cord, or combinations of these functions).

The iCON SELV 12V Optional Modules are available separately and can be fitted at the time of installation or retrofitted. The optional modules include PCS Pull cord (Manual on/off), PCTS Pull cord timer (Run on timer 1-30 min), DTS Delayed timer (2 min delay, Run on timer 2-45 min, Pull cord), HTS Humidity timer (40-90% RH, Run on timer 2-45 min, Pull cord), PIR timer (Motion sensor, Run on timer 2-45 min), and PRHTS PIR with humidity timer (Motion sensor, 40-90% RH, Run on timer 2-45 min).

The iCON SELV fan range is IPX4 rated and therefore suitable for mounting in bathrooms (including zones 1 and 2), toilets, kitchens, and utility rooms, as long as it is not exposed to water jets (i.e. can be installed above fixed showerhead). The power supply unit must be fitted outside of wet zones (usually outside of the room). The maximum length of wire between the unit and the fan should not exceed 5 meters using 1.5mm2 wire. Never cover the power supply unit with thermal insulation materials.

Product Usage Instructions

All electrical installation work must be carried out by an approved competent person in compliance with U.K. Building Regulations and to the latest IET standards, or the appropriate regulations in the country of installation. The fan requires a 12V DC supply (included in the box), class
III equipment (marked as stated in BS EN 60417). The power supply unit requires 100-240V 50/60Hz supply (class II). It is self-resetting for overcurrent and short circuit protection. An external 3A fuse and 30mA RCD is required for each unit. The LED indicator shows the unit is switched on.

There are different wiring instructions depending on whether there is a control module fitted or not. Wiring and installation of iCON modules can be found in the instructions included within the module packaging. Please refer to page 5 of 16 for wiring instructions for different control modules.

The iCON 15S has a fan size of 100mm, an air flow of 21 / 77 [l/s / m3/h], a power of 6.1 W, a current of 0.07 A, and a noise level of 32.4 dB(A) @ 3m. The iCON 30S has a fan size of 100mm, an air flow of 37 / 132 [l/s / m3/h], a power of 12.2 W, a current of 0.10 A, and a noise level of 36.2 dB(A) @ 3m.

Fan Dimensions

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-4

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-5

Range Overview

iCON SELV 12V DC fans are designed for ventilation domes-tic premises and available in two model sizes. They are pow-ered Safety Extra Low Voltage fans and can be fitted to a wall or ceiling.
The iCON SELV range can be used as a simple extract SELV fan operated by a remote switch (standard), or can be fitted with an internal control module to give a range of control options (which includes: timer, humidity, motion sensor, pull cord or combinations of these functions).
These optional modules are available separately and can be fitted at the time of installation or retrofitted (see page 6).

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-7

Part no.| Model| Fan Size| Air flow
[l/s / m 3/h]| Power
[W]| Current
[A]| Noise level
[dB(A) @ 3m]
---|---|---|---|---|---|---
72683701| iCON 15S| 100mm      21 / 77| 6.1| 0.07| 32.4
72683801| iCON 30S| 100mm| 37 / 132| 12.2| 0.10| 36.2

Electrical Installation

All electrical installation work to be carried out by an approved competent person in compliance with U.K. Building Regula-tions and to the latest IET standards, or the appropriate regulations in the country of installation.
The fan requires a 12V DC supply (included in the box), class III equipment (marked as stated in BS EN 60417).

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-9

The power supply unit requires 100-240V 50/60Hz supply (class II). It is self resetting for over current and short circuit protection. An external 3A fuse and 30mA RCD is required for each unit. The LED indicator shows the unit is switched on The iCON SELV fan range is IPX4 rated and therefore it is suitable for mounting in bathrooms (incl. zones 1 and 2), toilets, kitchens and utility rooms, as long as it is not exposed to water jets (i.e. can be installed above fixed shower head).
The power supply unit must be fitted outside of wet zones (usually outside of the room). The maximum length of wire between the unit and the fan should not exceed 5 meters using 1.5mm2 wire. Never cover the power supply unit with thermal insulation materials.

Important
Do not place the ventilator near direct heat sources, e.g. rad-ant heaters, or where temperatures can exceed 40°C (104°F).

Electrical Installation

Wiring with no control module fitted:

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-1

Wiring for control modules with no external switching:

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-2

Wiring for control modules with external switching

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-3

Wiring and installation of iCON modules can be found in the Instructions included within the module packaging.

Modules & Covers

iCON Optional Colour Covers

Cover / Fan iCON 15S iCON 30S
Chrome 52634502B
Anthracite 52634503B 52634506B
Sandstone 52634505B 52634508B
Silver 52634504B 52634507B
Ultimate Grey 52634514B 52634517B
Navy Blue 52634516B 52634519B
Turquoise 52634515B 52634518B

iCON SELV 12V Optional Modules

Part no. Model Description
72573603 PCS Pull cord (Manual on/off)
72574204 PCTS Pull cord timer (Run on timer 1-30 min)
72682307 DTS Delayed timer (2 min delay, Run on timer 2-45 min, Pull

cord)
72574202| HTS| Humidity timer (40-90% RH, Run on timer 2-45 min, Pull cord)
72574203| PRTS| PIR timer (Motion sensor, Run on timer 2-45 min)
72574201| PRHTS| PIR with humidity timer (Motion sensor, 40-90% RH, Run on

Front Cover Removal

To remove front cover assembly, first make sure the fan is off, isolated from the power supply and the iris shutter is fully closed.

  1. Undo the locking screw at the bottom edge of the cover using a screwdriver.
  2. Rotate the cover a few degrees anticlockwise until it clicks out from the fittings.
  3. Remove the cover by pulling it out.

To refit the cover, reverse the above procedure. If when refit-ting the front cover the iris stays open, remove the cover and don’t attempt to refit it for approx. two minutes (allowing the actuator to retract back in the closed position). Then try again.

Mechanical Installation

iCON fans can be recessed in a wall or ceiling (iCON 30S is supplied with surface mounting kit). See pages 9 -11 for details.
Always ensure free running of the fan impeller and that duct connections are not over tightened to the fan outlet spigot.
Fix the sealed grommet supplied into the cable entry hole. Pierce the grommet to allow the mains cable to be pulled through while maintaining the integrity of the seal.
Airflow Developments recommends that rigid ducting is used where possible instead of flexible ducting, this will ensure maximum performance.
Before carrying out the installation see pages 12 & 13 for best practice recommendations.

Wall Installation

Recessing fan in the wall
The iCON 15S requires a 110mm diameter hole through the wall lined with a 100mm internal diameter duct.
The iCON 30S requires a 110mm diameter hole through the wall, counter board 160mm to a depth of 80mm. The hole should be lined with a 100mm internal diameter duct.

Surface mounting fan on the wall
When surface mounting the iCON 30S the supplied mounting skirt should be used.
The iCON 30S requires a 110mm diameter hole through the wall lined with a 100 mm internal diameter duct.
Ensure all vapour barriers are properly restored.

Ceiling Installation

Ceiling Recess

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-13

The fan should be fitted in the hole, fixed with the screws provided into the support.
The iCON 15S requires a 110mm diameter hole through the ceiling.
The iCON 30S requires a 160mm diameter hole through the ceiling.
Where flexible duct is used the diameter must be maintained.

Ceiling Surface Mounting

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-14

When surface mounting the iCON 30S, the mounting skirt provided should be used. The mounting skirt should be fixed, with the screws provided, into the support. The fan is then fitted into the skirt.
The iCON 30S requires a 110mm diameter hole through the ceiling.
When recessing or surface mounting in the ceiling, a plywood support (min. 18mm thick) must be mounted between the ceiling joists. Any fixing screws should be fitted through the plaster board into the support.

Best Practice Recommendations

Installation with flexible ducting

AIRFLOW-iCON-15S-SELV-12V-Fan-Range-15

Where flexible ducting is used the diameter must be maintained and it is good ventilation practice that the ducting is extended to a minimum of 90% its possible length in order to maintain the best possible air flow.
Ensure that flexible duct connections are not over tightened to the spigots.
To maximize the air flow rigid ducting should be used where possible. The fan and ducting should be installed in accordance with the requirements of the Domestic Ventilation Compliance Guide, part of the Building Regulations.

To avoid the backflow of condensation into the fan in ceiling installations it is good practice to fit a condensation trap to the vertical outlet duct of the fan.
With through the wall installation fit the duct in an approx. 5° angle down to outside.

Measurements and Commissioning
The Building Regulations 2010, imposes a requirement that testing and reporting of mechanical ventilation performance
(see Approved Document F1) is conducted in accordance with an approved procedure.
Compliance with this requirement by an assessed and registered ‘Competent Person’ should follow a ‘Best Practise’ process and adopt air flow measurement, Method A – The Unconditional Method – using a suitable UKAS certified measuring instrument. Generically referred to as ‘Zero Pressure Air Flow Meter’ or ‘Powered Flow Meter’.
Further information on this method is detailed in NHBC Building Regulations Guidance Note G272a 10/13 and BSRIA Guide document BG 64/2016.

Maintenance

SAFETY FIRST: ALWAYS ISOLATE THE FAN UNIT FROM THE POWER SUPPLY BEFORE DOING ANY WORK ON THE FAN/MODULE.
When installed according to these instructions the iCON range is completely safe. The materials used do not constitute a hazard.

Cleaning

Fan and ducting should be inspected and cleaned on a regular basis to keep fan performance. The external housing of the fan can be wiped with a damp cloth. Do not use household cleaners containing abrasives. Cleaning of the internal parts such as the impeller should be carried out by using a soft brush. Never clean any parts of the fan assembly by immersing in water or using a dishwasher.

Warning
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children should not play with the appliance. Cleaning and user maintenance shall not be carried out by children without adult supervision.

Warranty

Airflow Developments Ltd guarantees the iCON for 3 years from date of purchase against faulty material or workmanship. Applicable to units installed and used in the United Kingdom.
You can register your warranty online (for more information check at www.airflow.com).
Warranty only covers the fan, not the reinstallation if required. In the event of any defective parts being found, Airflow Devel-opments Ltd reserve the right to repair or at our discretion replace without charge provided that the unit:

  1. Has been installed and used in accordance with the fitting and wiring instructions supplied with each unit.
  2. Has not been connected to an unsuitable electrical supply.
  3. Has not been subjected to misuse, neglect or damage.
  4. Has not been modified or repaired by any person not authorised by Airflow Developments Ltd
  5. Has been installed in accordance with latest Building Regulations and IET wiring regulations by a person who is recognised as a competent installer who is part of a competent scheme provider (e.g. NICEIC Ventilation Scheme).

Airflow Developments Ltd shall not be liable for any loss, injury or other consequential damage, in the event of a failure of the equipment or arising from, or in connection with the equipment excepting only that nothing in this condition shall be construed as to exclude or restrict liability for negligence.
This warranty does not in any way affect any statutory or other consumer rights.
For detailed standard warranty terms and conditions see our website or contact Customer Service.

UK Head-Office
AIRFLOW DEVELOPMENTS Ltd
Aidelle House, Lancaster Road
Cressex Business Park
High Wycombe
Buckinghamshire
HP12 3QP
United Kingdom
Tel: +44 (0) 1494 525252
Email: [email protected]
Web: www.airflow.com

Czech Republic
AIRFLOW LUFTTECHNIK GmbH
o.s. Praha
Hostýnská 520
108 00 Praha 10
Malešice
Czech Republic
Tel: +42 (0) 2 7477 2230
Email: [email protected]
Web: www.airflow.cz

Germany
AIRFLOW LUFTTECHNIK GmbH
Wolbersacker 16
53359 Rheinbach
Germany
Tel: +49 (0) 222 69205 0
Email: [email protected]
Web: www.airflow.de

www.airflow.com

© Airflow Developments Ltd.
Airflow Developments Limited reserve the right, in the interests of continuous develop-ment, to alter specifications without prior notice. All orders are accepted subject to our conditions of sale which are available on request.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AIRFLOW User Manuals

Related Manuals