GOSSEN METRAWATT Metriso Xtra Resistance Tester Instruction Manual

June 12, 2024
GOSSEN METRAWATT

GOSSEN METRAWATT Metriso Xtra Resistance Tester

GOSSEN METRAWATT Metriso Xtra Resistance Tester

Switching on battery test

Switching on battery test
Switching on battery test

Brightness Contrast

Request help

Brightness Contrast 
Brightness Contrast 

Parameter

select confirm

Parameter

Measurement

  1. select
    Measurement

  2. start
    Measurement

Connection

Connection
Connection

Test Resistance

Test Resistance
Test Resistance
Test Resistance

RINS/RLO k Ω

Interference voltage control

RINS/RLO k Ω

The following measurements are possible on electrically dead devices.
External voltage disables the measurement!

RISO/RINS

Riso/rins

RISO/RINS →  AUTO 1 / AUTO 3

Riso/rins →  Auto 1 / Auto 3

Riso/rins →  Auto 1 / Auto 3

RLO (I > 200 mA !)

RLO \(I > 200 mA !\)

Sockets

Sockets
Sockets

Switching off  Rechargeable batteries Fuses

Switching off  Rechargeable batteries Fuses

Subject to change  without notice

Technical Data

| Measuring Range
---|---
RISO / RINS| U = 50, 100, 250, 500, 1000 V
RISO / RINS| Uvar = 50 … 1000 V
RISO / RINS| Uramp (U ◢ ) = 100 … 1000 V
R| 10 … 10 kW
RLO| 0,01 … 10 Ω (I ³ 200 mA !)
U| 0 … 1000 V
| Limit Values
---|---
Limit RISO / RINS| 50 k Ω @ UISO/UINS = 50 V
 | 100 k Ω @ UISO/UINS = 100 V
 | 500 k Ω @ UISO/UINS = 250 V
 | 1 M Ω @ UISO/UINS = 500 V
 | 1 M Ω @ UISO/UINS = 1000 V & @ Uvar
Limit PI| 1.0 / 1.1 / 1.5 / 2.0 / 3.0 / 4.0
Limit DAR| 1.25 / 1.6
Limit RLO| 2 W

Customers Support

Telefon+49 911 8602-0
Telefax +49 911 8602-669
E-Mail info@gossenmetrawatt.com
www.gossenmetrawatt.com