GOSSEN METRAWATT PROFITEST MF Series Tester Instruction Manual

June 12, 2024
GOSSEN METRAWATT

PROFITEST MF Series Tester
Instruction Manual

Read the detailed operating instructions, available at www.gossenmetrawatt.com.
The short-form instructions are no substitute for the detailed instructions!

Download Centerhttps://www.gmc-instruments.de/services/download- center/?q=&doctype=product_manual&lang=de-DE

Safety Instructions

Observe this documentation, in particular all included safety information, in order to protect yourself and others from injury, and to prevent damage to the instrument.
These condensed operating instructions and the detailed operating instructions should be made available to all users.
General

  • Tests/measurements may only be performed by a qualified electrician, or under the supervision and direction of a qualified electrician. The user must be instructed by a qualified electrician concerning performance and evaluation of the tests/measurements.
  • Observe the five safety rules in accordance with DIN VDE 0105-100:2015-10, VDE 0105-100:2015-10, Operation of electrical installations – Part 100: General requirements (1. Shut down entirely. 2. Secure against restart. 3. Assure absence of voltage at all poles. 4. Ground and short circuit. 5. Cover neighbouring live components, or cordon them off.)
  • Observe and comply with all safety regulations which are applicable for your work environment.
  • Wear suitable and appropriate personal protective equipment (PPE) whenever working with the instrument.
  • The functioning of active medical devices (e.g. pacemakers, defibrillators) and passive medical devices may be affected by voltages, currents and electromagnetic fields generated by theinstrument and the health of their users may be impaired. Implement corresponding protective measures in consultation with the manufacturer of the medical device and your physician.If any potential risk cannot be ruled out, do not use the instrument.

Accessories

  • Use only the specified accessories (included in the scope of delivery or listed as options) with the instrument.
  • Carefully and completely read and adhere to the product documentation for optional accessories. Retain these documents for future reference.

Handling

  • Use the instrument in undamaged condition only. Inspect the instrument before use. Pay particular attention to damage, interrupted insulation or kinked cables. Damaged components must be replaced immediately.
  • Accessories and cables may only be used as long as they’re fully intact. Inspect accessories and all cables before use. Pay particular attention to damage, interrupted insulation or kinked cables.
  • If the instrument or its accessories don’t function flawlessly, permanently remove the instrument/accessories from operation and secure them against inadvertent use.
  • If the instrument or accessories are damaged during use, for example if they’re dropped, permanently remove the instrument/accessories from operation and secure them against inadvertent use.
  • The instrument and the accessories may only be used for the tests/measurements described in the documentation for the instrument.
  • The integrated voltage measuring function and mains check may not be used to test systems or system components for the absence of voltage. Testing for the absence of voltage is only permissible with a suitable voltage tester or voltage measuring system which fulfills the requirements specified in DIN EN 61243.

Operating conditions

  • Do not use the instrument and its accessories after long periods of storage under unfavorable conditions (e.g. humidity, dust or extreme temperature).
  • Do not use the instrument and its accessories after extraordinary stressing due to transport.
  • The instrument must not be exposed to direct sunlight.
  • Only use the instrument and its accessories within the limits of the specified technical data and conditions (ambient conditions, IP protection code, measuring category etc.).
  • Do not use the instrument in potentially explosive atmospheres.

Rechargeable batteries

  • If the charger is used, only the rechargeable battery pack (Z502H/Z502O) may be fitted in the instrument.

  • Do not use the instrument while the rechargeable battery pack (Z502H/Z502O) is being charged.

  • Do not use the instrument if the battery compartment cover has been removed.
    Touch contact with dangerous voltages is otherwise possible.

  • The rechargeable battery pack (Z502H/Z502O) may only be charged in undamaged condition.
    Inspect the rechargeable battery pack (Z502H/Z502O) before use. Pay particular attention to leaky and damaged batteries.

Fuses

  • The instrument is equipped with fuses. The instrument may only be used as long as the fuses are in flawless condition. Defective fuses must be replaced. See detailed operating instructions

Measurement cables and establishing contacts

  • Plugging in the measurement cables must not necessitate any undue force.
  • Never touch conductive ends (e.g. of test probes).
  • Fully unroll all measurement cables before starting a test/measurement. Never perform a test/measurement with the measurement cable rolled up.
  • Avoid short-circuits due to incorrectly connected measurement cables.
  • Ensure that alligator clips, test probes or Kelvin probes make good contact.

Data security

  • Always create a backup copy of your measurement data.
  • Observe and comply with the applicable national data protection regulations. Use the corresponding functions provided by the instrument such as access protection, as well as other appropriate measures.

Applications

Please read this important information!
Intended Use / Use for Intended Purpose
The measuring and test instruments in the PROFITEST MF series include

  • PROFITEST MF XTRA (M534H)*

  • PROFITEST MF TECH (M534K)*

  • Article number on the rating plate (test instrument only); order numbers (instrument with standard scope of delivery or extended accessories) see data sheet.
    The test instruments are used to test the effectiveness of protective measures at stationary electrical installations per DIN VDE 0100-600, DIN VDE 0105-100, OVE E 8101, NIN / NIV and other country-specific standards. They also allow for testing of electric charging stations in accordance with EN 61851-1 (DIN VDE 0122-1), and earth measurements. The test instruments includes pre-defined test sequences for easy use; optionally, user-defined test sequences can be programmed.
    The test instruments are especially suited for tests during installation, initial start-up, and for recurrent tests and troubleshooting in electrical installations.
    The range of application of the test instruments covers all alternating and 3-phase current systems with nominal voltages of 230 V / 400 V (300 V / 500 V) with nominal frequencies of 16⅔ Hz / 50 Hz / 60 Hz / 200 Hz / 400 Hz.
    A system structure is created in the test instrument and the measured values are assigned to the objects. Completed tests and measured values can be saved and documented in a measure- ment and test report.
    Safety of the operator, as well as that of the test instrument, is only assured when it’s used for its intended purpose.
    Use for Other than Intended Purpose
    Using the test instrument for any purposes other than those described in these condensed operating instructions, or in the test instrument’s operating instructions, is contrary to use for intended purpose.
    Liability and Guarantee
    Gossen Metrawatt GmbH assumes no liability for property damage, personal injury or consequential damage resulting from improper or incorrect use of the product, in particular due to failure to observe the product documentation. Furthermore, all guarantee claims are rendered null and void in such cases. Nor does Gossen Metrawatt GmbH assume any liability for data loss.
    Opening the Instrument/Repairs
    The test instrument may only be opened by authorized, trained personnel in order to ensure flawless, safe operation and to assure that the guarantee isn’t rendered null and void. Even original replacement parts may only be installed by authorized, trained personnel.
    Unauthorized modification of the test instrument is prohibited. If it can be ascertained that the test instrument has been opened by unauthorized personnel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any consequential damages.
    If the guarantee seal is damaged or removed, all guarantee claims are rendered null and void.

Scope of Delivery

Standard equipment of the PROFITEST MF series:

1 Test instrument 1 Compact rechargeable battery pack (Z502H)

1 Earthing contact plug insert, country-specific
(PRO-SCHUKO/GTZ3228000R0001)| 1Charger (Z502R)
1 2-pole measuring adapter and 1 cable for expansion into
3-pole adapter (PRO-A3-II/Z501O)| 1 DAkkS calibration certificate
2 Alligator clips| 1 Condensed operating instructions* (this document)
1 USB cable| Information on Open Source Software Lizenzen
1 Shoulder strap| 1 Software IZYTRONIQ BUSINESS Starter
(12 months IZYTRONIQ CLOUD
)

  • Detailed operating instructions available on the Internet for download from www.gossenmetrawatt.com
    ** Download from the Internet; registration certificate in the scope of delivery

Symbols on the Instrument

| Warning concerning a point of danger (attention, observe documentation!)
---|---
| Protection category II device
| Charging socket for extra-low direct voltage (for charger Z502R)
GOSSEN METRAWATT PROFITEST MF Series Tester - Icon 3| Battery loading level indicator
| Warning symbol according to EN 61557-10 for limiting external overvoltage
2× FF3,15/500G| Fuses
| The instrument and its batteries may not be disposed of with household trash. Further information is included in the operating instructions.
****| EU conformity marking
| If the guarantee seal is damaged or removed, all guarantee claims are rendered null and void.
| Special technical knowledge of qualified personnel is required for electrical installation or repair.

GOSSEN METRAWATT PROFITEST MF Series Tester - Icon 8Measuring category
CAT III 600 V
CAT IV 300 V

Technical Data (excerpt)

The complete technical data and characteristic values (display ranges, resolution, uncertainties etc.) can be found in the complete operating instructions.

Ambient Conditions

Accuracy| 0 … + 40 ºC
Operation| –5 … + 50 ºC
Storage| –20 … + 60 ºC (without rechargeable batteries)
Relative humidity| Max. 75%, no condensation allowed
Elevation| Max. 2000 m
Nominal Ranges of Use

Voltage UN| 120 V| (108 … 132 V)
230 V| (196 … 253 V)
400 V| (340 … 440 V)
Frequency fN| 16 ⅔ Hz| (15.4 … 18 Hz)
50 Hz| (49.5 … 50.5 Hz)
60 Hz| (59.4 … 60.6 Hz)
200 Hz| (190 … 210 Hz)
400 Hz| (380 … 420 Hz)
Overall voltage range| 65 … 550 V
Overall frequency range| 15.4…420Hz
Waveform| Sinusoidal
Temperature range| 0 °C … + 40 °C
Supply voltage| 8 … 12 V
Line impedance angle| Corresponds to cos j =1 … 0,95
Probe resistance| < 50 kW
Overload Capacity

RISO| 1200 V continuous
UL-PE, UL-N| 600 V continuous
RCD RE RF| 440 V continuous
ZL-PE, ZL-N| 550 V (Limits the number of measurements and pause duration. If overload occurs, the instrument is switched off by means of a thermostatic switch.)
RLO| Electronic protection prevents switching on if interference voltage is present
Protection with Fine-Wire Fuse| FF 3.15 A 10 s,
Fuses blow at > 5 A
Electrical Safety

Protection class| II per EN 61010-1
Nominal Voltage| 230/400 V (300/500 V)
Test voltage| 3.7 kV, 50 Hz
Measuring category Pollution degree| CAT III 600 V and CAT IV 300 V
Fuses| 2
L and N terminals| 1 fuse link ea.
FF 3.15 A/500G 6.3 x 32 mm
Mechanical Design

Dimensions| W × L × D = 260 × 330 × 90 mm
Weight| approx. 2.7 kg with rechargeable batteries
Type of protection| Housing: IP40; test probes: IP40 per EN 60529
Data Interfaces

Type| USB type B for PC connection
Typ| USB type A for connecting a USB keyboard, barcode reader or RFID scanner

Scope of Functions

PROFITEST MF … (article number) TECH (M534K) XTRA (MM534H)

Testing of residual current devices (RCDs)
UB measurement without tripping the RCCB| ✓| ✓
Tripping time measurement| ✓| ✓
Measurement of tripping current IF| ✓| ✓
Selective, SRCDs, PRCDs, type G/R| ✓| ✓
AC/DC sensitive RCDs, types B and B+| ✓| ✓
DC sensitive RDC-DDs and RCMBs| ✓| ✓
Testing of insulation monitoring devices (IMDs)| —| ✓
Testing Residual Current Monitoring Devices (RCMs)| —| ✓
Testing for N-PE reversal| ✓| ✓
Measurements of loop impedance ZL-PE / ZL-N
Fuse table for systems without RCDs| ✓| ✓
Without tripping the RCD, fuse table| ✓| ✓
15 mA measurement 1)| ✓| ✓
Earth resistance RE (mains operation)
I/U measuring method (2/3-wire measuring method via measuring adapter: 2-wire/2-wire + probe)| ✓| ✓
Earthing resistance RE (battery operation)
3 or 4-wire measuring method via PRO-RE adapter| —| ✓
Soil resistivity rE (battery operation)
(4-wire measuring method via PRO-RE adapter)| —| ✓
Selective earthing resistance RE (mains operation) with 2-pole adapter, probe, earth electrode and current clamp sensor (3-wire measuring method)| ✓| ✓
Selective earthing resistance RE (battery operation)
with probe, earth electrode and current clamp sensor
(4-wire measuring method via PRO-RE adapter and current clamp sensor)| —| ✓
Earth loop resistance RESCHL (battery operation)
with 2 clamps (clip-on current transformer direct and clip- on current transformer via PRO-RE/2 adapter)| —| ✓
Measurement of equipotential bonding RLO automatic polarity reversal| ✓| ✓
Insulation resistance RISO
Variable or rising test voltage (ramp)| ✓| ✓
Voltage UL-N / UL-PE / UN-PE / f| ✓| ✓
Special measurements
Current measurement with clamp IL, IAMP| ✓| ✓
Rotating Field Direction| ✓| ✓
Earth leakage resistance RE(ISO)| ✓| ✓
Voltage drop (DU)| ✓| ✓
Standing-surface insulation ZST| ✓| ✓
Meter start-up (kWh test)| ✓| ✓
Leakage current with PRO-AB adapter (IL)| —| ✓
Residual voltage test (Ures)| —| ✓
Intelligent ramp (ta + DI)| —| ✓
Electric vehicles at charging stations (IEC 61851-1)| ✓| ✓
Documentation of fault simulations at PRCDs with the PROFITEST PRCD adapter| —| ✓
Features
Selectable user interface language 2)| ✓| ✓
Memory (database for up to 50,000 objects)| ✓| ✓
Automatic test sequences function| ✓| ✓
USB port type A (connection of USB keyboard/barcode reader/RFID scanner)| ✓| ✓
USB port type B (data transmission)| ✓| ✓
PC database and report generating software IZYTRO- NIQ 3)| ✓| ✓
Measuring category: CAT III 600V / CAT IV 300 V| ✓| ✓
DAkkS calibration certificate| ✓| ✓

  1. The so-called live measurement is only advisable if there is no bias current within the system. Only suitable for motor protection switches with small nominal current values.
    As of firmware 3.4.4: 15 mA test current, only applies if RCD is set with IΔN = 30 mA; otherwise test current = ½ · IΔN of the pre-set RCDs

  2. currently available languages D, GB, I, F, E, P, NL, S, N, FIN, CZ, PL

  3. IZYTRONIQ BUSINESS Starter (IZYTRONIQ CLOUD)

Sockets

GOSSEN METRAWATT PROFITEST MF Series Tester - Sockets

Initial Start-Up

Attention!
Remove the protective films from both sensor surfaces (finger contacts) of the testplug.
This is the only way to safely detect contact voltages.
Insert the enclosed, pre-charged compact rechargeable battery pack (Z502H):
➭ Loosen the screw on the battery com- partment cover (back of instrument).
➭ Remove the battery compartment cover.
➭ Insert the compact rechargeable battery pack.
➭ Replace the battery compartment cover.
➭ Screw the battery compartment cover into place.
Further information on the power supply can be found in the operating instructions.

  1. Switching on,
  2. Connection &
  3. rech. battery testGOSSEN METRAWATT PROFITEST MF Series Tester - Sockets 1

Settings

  1. Brightness
  2. Request helpGOSSEN METRAWATT PROFITEST MF Series Tester - Settings

Parameter:
1-3a select
3b confirm
4c take over

GOSSEN METRAWATT PROFITEST MF Series Tester -
Parameter

Measurement

Measurement

  1. select
  2. start
  3. trip RCD

= see operating instructions

GOSSEN METRAWATT PROFITEST MF Series Tester -
Measurement

GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
1| GOSSEN METRAWATT PROFITEST MF Series
Tester - Measurement 2*for fN < 45 Hz => UN < 500 V
15 mA test current, only applies if RCD is set with IΔN = 30 mA; otherwise test current = ½ · IΔN of the pre-set RCDs
---|---
GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
3| GOSSEN METRAWATT PROFITEST MF Series
Tester - Measurement 4
GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
5| GOSSEN METRAWATT PROFITEST MF Series
Tester - Measurement 6
GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
7|
RLO/RISO**
The following measurements are only possible on voltage-free devices.
Interference voltage disables the measurement!

GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
8

GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
9| Phase sequence GOSSEN METRAWATT
PROFITEST MF Series Tester - Measurement 10
GOSSEN METRAWATT PROFITEST MF Series Tester - Measurement
11| GOSSEN METRAWATT PROFITEST
MF Series Tester - Measurement 12

Switching off

Contact & Support

+49 911 8602-0
info@gossenmetrawatt.com
support@gossenmetrawatt.com
Monday to Thursday: 8 a.m. to 4 p.m.
Friday: 8 a.m. to 2 p.m.
Service, repairs, spare parts and calibrations
+49 911 817718-0
service@gossenmetrawatt.com
www.gmci-service.com

GOSSEN METRAWATT PROFITEST MF Series Tester - Qr Code
1https://www.gmci-service.com/

CE Declaration

The instrument fulfils all requirements of applicable EU directives and national regulations. We confirm this with the CE mark. The CE declaration is available upon request.
A calibration certificate is included with the instrument.
© Gossen Metrawatt GmbH
Prepared in Germany · Subject to change without notice / Errors excepted · A PDF version is available on the Internet
All trademarks, registered trademarks, logos, product names, and company names are the property of their respective owners.

Gossen Metrawatt GmbH
Südwestpark 15
90449 Nürnberg • Germany
Phone: +49 911 8602-0
Fax: +49 911 8602-669
E-Mail: info@gossenmetrawatt.com
www.gossenmetrawatt.com
3-447-155-27
2/1.23

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GOSSEN METRAWATT User Manuals

Related Manuals