GOSSEN METRAWATT EM2281 ENERGYMID Electronic Energy Meters Instruction Manual

June 12, 2024
GOSSEN METRAWATT

GOSSEN METRAWATT EM2281 ENERGYMID Electronic Energy Meters

Product Information

Product Name: ENERGYMID Electronic Energy Meters
Model: EM2281/EM2289 (Direct Connection), EM2381/EM2387/EM2389 (Via Transformer)

Manufacturer: Gossen Metrawatt GmbH

Safety Precautions:

  • Danger of electric shock due to live components
  • Danger of life-threatening electric arcs
  • Risk of injury due to incorrect installation and use
  • Read and comply with all product documentation and operating instructions

Application:

  • Intended use for energy measurements as described in the documentation
  • Using the instrument for purposes other than described is contrary to the intended purpose
  • Gossen Metrawatt GmbH assumes no liability for damage or injury resulting from improper use

Scope of Delivery:

  • 1 Energy meter
  • 1 Condensed operating instructions
  • 1 Calibration certificate (only with feature P9)

Ambient Conditions:

  • Operating temperature range: Not specified
  • Storage temperature range: Not specified
  • Relative humidity: Max. 95%, no condensation allowed; Max. 75% annual average and noncondensing
  • Elevation: Max. 2000 m
  • Place of use: Indoors
  • Mechanical classification: M1
  • Electromagnetic classification: Not specified

Product Usage Instructions

  1. Ensure safety precautions are followed to prevent electric shock and injury.
  2. Read and understand all product documentation and operating instructions.
  3. Use the energy meter only for the intended purpose of energy measurements.
  4. Do not use the instrument for any other purposes not described in the documentation.
  5. Ensure proper installation and connection of the energy meter and all connecting lines and cables.
  6. If the instrument does not function flawlessly, permanently remove it from operation and secure it against inadvertent use.
  7. Dispose of the device properly according to section 15 of the documentation.

Safety Precautions

Condensed Operating Instructions

3-349-868-03 8/8.22

ENERGYMID
Electronic Energy Meters Direct Connection EM2281/EM2289 Via Transformer EM2381/EM2387/EM2389

DANGER
Electric shock due to live components! Life endangering due to electric arcs!
Touching voltage conducting components is life endangering! ­ Installation may only be performed by a qualified
electrician. ­ Observe and comply with all safety regulations
which are applicable for your work environment. ­ Wear suitable and appropriate personal protective
equipment (PPE) whenever working with the instrument. ­ During installation, the installation environment must be voltage-free. Observe the five safety rules in accordance with DIN VDE 0105-100.

DANGER
Life endangering! Danger of injury! Incorrect installation and use.
Read and comply with all further product documentation, in particular the operating instructions. Available at www.gossenmetrawatt.com > Products > Industrial Measuring Technology > Energy Management > Energy Meters > EM2281 … EM2389 or QR code shown above.

CAUTION
Incorrect Installation
Incorrect installation may result in property damage to the product and/or the respective system. Risk of operational malfunctions. ­ Observe the specified technical data, characteristic
values and ambient conditions. ­ The instrument may only be installed and operated if
it and all connecting lines and cables are undamaged and in perfect working order. If the instrument doesn’t function flawlessly, permanently remove it from operation and secure it against inadvertent use.

Application

Intended Use / Use for Intended Purpose
ENERGYMID EM2281, EM2289, EM2381, EM2387 and EM2389 instruments are multifunctional energy meters (certified in accordance with MID). They’re used for the acquisition and billing of active energy. Technical properties and other functions are defined by selecting the desired device type and via configurable features (when ordering). Refer to the data sheet and your order for your instrument variant. All instruments include measures for protection against tampering (tamper-proof cover and configuration disabling). Values are also forwarded to superordinate management systems via feature-dependent communication interfaces. Safety of the operator, as well as that of the instrument, is only assured when it’s used for its intended purpose.
Use for Other than Intended Purpose
The instrument may only be used for the measurements described in the documentation for the instrument. Using the instrument for any purposes other than those described in these condensed operating instructions, or in the instrument’s operating instructions, is contrary to use for intended purpose.
Liability and Guarantee
Gossen Metrawatt GmbH assumes no liability for property damage, personal injury or consequential damage resulting from improper or incorrect use of the product, in particular due to failure to observe the product documentation. Furthermore, all guarantee claims are rendered null and void in such cases. Nor does Gossen Metrawatt GmbH assume any liability for data loss.

3 Scope of Delivery

1

Energy meter

1

Condensed operating instructions

1

Calibration certificate (only with feature P9)

M22

1948 1948

DE-M 22

4 Symbols on the Instrument
EBY Marking with stamp of the federally approved 8 test laboratory 22 (for verification only / with feature P9)
CE and metrology mark with indication of year (M22) and registration number of the notified body for module D, country-specific calibration validity period
Metrological symbol for national approval in Germany (DE = Germany, M = Metrology) with indication of year (22) and registration number of the notified body.
DE MTP 17 B 002 MI-003 (EM228x) DE MTP 16 B 004 MI-003 (EM238x) DE MTP 20 B 004 (EM228x Z2) DE MTP 20 B 005 (EM238x Z2) Prototype test certificate
Meter type: bidirectional meter Energy import Energy export
Anti-reversing
Mains type: 2 or 3-wire energy meter

Double insulation (protection category II)

!

Warning concerning a point of danger (attention, observe documentation!)

European conformity marking

The device may not be disposed of with household trash. See section 15.

5 Rating Plate Entries
Nominal voltage Imin – In (Imax) / nominal frequency Accuracy class / operating temperature Serial number energy export / ® energy import LED constant
UP key
Type designation (article no.)
ENTER key
Current/voltage transformer ratio
Pulse output Prototype test certificate
2D code or calibration mark (feature P9)

6 Ambient Conditions

Operating temperature range

-25 … +55 °C

Storage temperature range

-25 … +70 °C

Relative humidity

Max. 95%, no condensation allowed Max. 75% annual average and noncondensing

Elevation

Max. 2000 m

Place of use

Indoors

Mechanical classification

M1

Electromagnetic classification

E2

Protection

Front (panel-mount instrument): IP 51 Terminals: IP 20

CAUTION
Incorrect Installation
The instrument may only be installed inside an external housing, e.g. switch or meter cabinet. The housing must provide at least IP 51 protection and must be located indoors. Only in this case is protection against dust and water ingress guaranteed in accordance with the EN50470-1.

7 Tamper-Proof Sealing

  1. The manufacturer’s seal on the side of the instrument serves as a calibration and guarantee seal.
  2. Four tamper-proof seals for the terminal cover: can be mounted to the left and right of each terminal cover.

8 Connector Pin Assignments and Wire Gauge
Note: Observe the wiring diagrams in the top and bottom terminal covers.

Connections Current input
Voltage input

Direct Meter (EM228X) Trans. Meter (EM238X)

Fine wire: 6 to 16 mm² Solid wire: 6 to 25 mm² With wire end ferrule: 6 to 16 mm² Torque: 3 Nm

Fine wire: 0.5 to 4 mm² Solid wire: 0.5 to 6 mm² With wire end ferrule: 0.5 to 2.5 mm² Torque: 0.5 Nm

­

Fine wire:

0.5 to 4 mm²

Solid wire:

0.5 to 6 mm²

With wire end ferrule:

0.5 to 2.5 mm²

Torque: 0.5 Nm

S0 pulse output Bus output Tariff input (power utility pulse) LON (W1) a
M-Bus (W2) a TCP/IP (W4) a Modbus (W7) a

Fine wire: Solid wire: With wire end ferrules: Torque:

0.2 to 2.5 mm² 0.2 to 2.5 mm² 0.25 to 1.5 mm² 0.4 Nm

Twisted pair copper cable, recommended: JY (ST) Y 2 × 2 × 0.8 mm with twisted wire pairs (where 0.8 mm = wire diameter, wire cross-section = 0.5 mm²), maximum cable length of 900 m with bus topology (bus terminator at both ends), 500 m with free topology (bus terminator at one end) or 320 m from device to device

2-wire twisted-pair

RJ-45 (8P8C)

2-wire twisted-pair, shielded if possible, maximum length of 1000 m (depending on cable thickness and transmission speed), cross-section of at least 0.22 mm², wave impedance approx. 100 to 150 , terminating resistors at both ends (the following applies: resistance value = line impedance)

a. For detailed information, refer to the interface description for your instrument which can be accessed via the link on the title page.

Contact, Support and Service

Gossen Metrawatt GmbH can be reached directly and without hassle ­ we have a single number for all of your needs!

+49-911-8602-0

Monday to Thursday
Friday:

8 a.m. to 4 p.m.
8 a.m. to 2 p.m.

support.industrie@gossenmetrawatt.com

Please contact GMC-I Service GmbH for repairs and verification:

+49-911-817718-0

Beuthener Str. 41

service@gossenmetrawatt.com 90471 Nürnberg

www.gmci-service.com

Germany

© Gossen Metrawatt GmbH Prepared in Germany · Subject to change, errors excepted · PDF version available on the Internet
All trademarks, registered trademarks, logos, product names and company names are the property of their respective owners.

Terminal Assignments, Direct Connection (EM228X)) Top and bottom terminals
N

Current Current Voltage L1

Current Current Voltage
L2

Current Current Voltage
L3

Terminal Assignments, Transformer Connection (EM238X) Top terminals:

W1: LON W2: M-Bus W4: TCP/IP W7: Modbus RTU V1 … 9: SØ pulse output

Tariff connections
Tb Tn Ta

TCP/IP

Bottom terminals:

Gossen Metrawatt GmbH Südwestpark 15 90449 Nürnberg · Germany Phone: +49 911 8602-0 Fax: +49-911-8602-669 e-mail info@gossenmetrawatt.com www.gossenmetrawatt.com

Current Current Current CurrentCurrent Current

Voltage

Voltage

Voltage

L1

L2

L3

N

9 Bus Interfaces
LON-Bus (feature W1), M-Bus (feature W2), TCP/IP (feature W4), Modbus RTU (feature W7)

Complete information concerning the interfaces can be found in the interface descriptions, which can be accessed via the link on the title page.

10 Pulse Output

External Voltage Source 24 V DC

  • 24

V3 / V4 External Voltage Source AC/DC
~
24

RL
U 23/25

RL
U 23/25

I = max. 27 mA

I = max. 100 mA

U Max. 40 V

Energy type*

t

U Max. 375 V

Energy type*

t

Standard pulse duration: 30 ms + 5%, interpulse period: > 30 ms

V7/V8 pulse duration: 130 ms + 5%, interpulse period: > 130 ms

Default setting: active energy Terminal 23 (S01): import, terminal 25 (S02): export

  • Type of energy can be selected with feature V2, V4.

Pulse Rates

V1/V3, fixed V7 V8 V9, fixed V2/V4, programmable [pulses per kWh]

Direct

U228x 1000 100 — — 1 1000 pls/kWh

Transformer

U2381 / U238x

f (secondary) 100 …

CT x VT = 1 (Q0) 1000 100 1000 50000 1100010,000 pls/kWh CTxVT=1(Q0)U6/7 1000 100 1000 20000 1100010,000 pls/kWh CTxVT=1(Q0) U3 1000 100 1000 50000 1100010,000 pls/kWh CT, VT, progr. (Q1) 1000 100 1000 50000 1100050,000 pls/kWh CT, VT, progr. (Q1)U6/7 1000 100 1000 20000 1100050,000 pls/kWh CT, VT, progr. (Q1)U3 1000 100 1000 50000 1100050,000 pls/kWh

CTxVT; CT, VT, fixed f (primary) (Q9)

2 10

1000 100 — —

11 100

100 10 — —

101 1000

10 1 — —

1001 10,000 1 100 — —

10,001 100,000 0.1 10 — —

100,0011,000,000 0.01 1 — —

f (primary)
1 1000 pls/kWh 0.1 100 pls/kWh 0.01 10 pls/kWh 1 1000 pls/MWh 0.1 100 pls/MWh 0.01 10 pls/MWh

Underlined values are default values.

11 Display and Control Panel

11.1 Test LEDs The test LEDs are located above the control keys. The left LED indicates energy export and the right LED indicates energy import. Blinking frequency accelerates as the measured power value increases. If all current values are smaller than starting current, both LEDs light up continuously.
LED Constant
Direct meter (EM228x): 10,000 pulses per kWh Trans. meter (EM238x): 100,000 pulses per kWh

11.2 Resolution, Main Display (large characters), Energy Import
Internally, metering is executed with increased resolution. As a result, the last place in the overall register may be a few digits higher than the sum of the individual registers if multiple tariffs are used.

Meter Feature U2281, U2289
Q0
Q9
Q1 **

CT × VT CT × VT Standard Calibration Unit

min. max.

Display Display *

— 123456.78 23456.789 kWh

1

1 12345.678 2345.6789 kWh

2

4 12345.678 2345.6789 kWh

5

40 123456.78 3456.7890 kWh

41

400 1234567.8 34567.890 kWh

401

4000 12345678 345678.90 kWh

4001 40000 123456.78 3456.7890 MWh

40001 400000 1234567.8 34567.890 MWh

400001 1000000 12345678 345678.90 MWh

1

4 u12345.67

**

kWh

5

40 u123456.7

**

kWh

41

400 u1234567

**

kWh

401

4000 u12345.67

**

MWh

4001 40000 u123456.7

**

MWh

40001 100000 u1234567

**

MWh

U238x

  • An additional place to the right of the decimal point is included for the calibration display in the case of a main display which can be calibrated (Q0 or Q9). The leading digit is thus eliminated in the case of an 8-place display.

* In the case of Q1, the secondary display can be calibrated Q0, for which reason display overflow is based on the secondary display. The standard display is shifted one place to the left if necessary.
11.3 Display The instrument shows measured variables (e.g. active energy) and information (e.g. active tariff) at the display.
Main display: active energy
in kWh or MWh (M2/M3: reactive energy* in kVArh or MVArh)

Auxiliary display 1: active power in kW or MW (M2/M3: reactive energy or power in kVAr(h) or MVAr(h))

Auxiliary display 2: e.g. IN, OUT for import or export Error: error code alternates with momentary display

  • Transformer meter EM238x: CT and VT are taken into consideration. Power: negative sign for export

u

Main display, not calibrated (feature Q1,

programmable CT/VT , see section 11.2).

T1 … T8: active tariff

Display of instantaneous power in 4 quadrants: positive or negative active power P, positive or negative reactive power Q.

Correct connection: Continuous illumination of the phase symbols where P 0
Phase failure: Symbol for affected phase is cleared from the display.
Incorrect phase sequence: Phase symbols blink in following order: 3 – 2 – 1, background illumination blinks red.

Negative power: Respective phase symbol blinks.
For bus connection: appears when the meter transmits a data packet.

Key symbols for parameters configuration with features Q1 and V2, V4:
CT, VT and S0 parameters can be changed depending on features.
CT, VT and S0 parameters disabled.

All other feature combinations: CT, VT or S0 parameters (which are or can be calibrated) are preset at the factory and can be queried in the display mode, other values can be changed.

Parameters which are or can be calibrated are preset at the factory, other parameters are disabled with the enable key.

Values which are preset at the factory are printed additionally on the rating plate.

Background Illumination

Background illumination is switched on each time a key

is activated. It goes back off after about 2 minutes.

Background illumination colors indicate various display

menus:

­ White:

query menus

­ Pink:

Parameter display and setting menus

­ Red:

firmware version display

­ Blinking red: in case of error

11.4 Operation The standard display appears by default. The UP and ENTER keys can be used to switch to other displays or menus from the standard display. If no keys are pressed for a period of 1 minute, the meter is returned automatically to its standard display.
Settings can be changed if certain features are included: ­ CT and VT parameters for U238x with feature Q1, ­ S0 parameter for U228x/U238x with feature V2/V4
Other parameters in accordance with the interface description.

11.5 Viewing Values and Changing Parameters Beginning from the standard display, it may be necessary to navigate through several displays/menus until you reach the value to be viewed or the parameter to be changed. Parameter changes are only possible after activating the enable key, which makes it possible to enable or disable parameter changes. It’s located underneath the top terminal cover between terminals 21 and 22 and is activated with a pointed object (e.g. an ESD safe screwdriver).
Enable Key

Pressing the enable key activates the “change parame-

ters” operating mode (key off):

Pressing the enable key again disables the “change

parameters” operating mode (key on):

If no keys are pressed for a period of about 2 minutes, the “change parameters” operating mode is exited automatically and disabled (key on).
Briefly press the enable key. The “change parameters” mode is active.

Navigate through the various displays/menus until you reach the desired parameter. See “Configuration and Operation”.
You can now view the desired value or adjust a parameter. See “Configuration and Operation”. If no keys are pressed for a period of about one minute, the setting menu is exited.
Press and hold the ENTER key or wait for one minute in order to change to the standard display.
Press the enable key in order to disable the “change parameters” mode. Alternatively, disabling takes place automatically after 2 minutes.

11.6 Switching Amongst Tariffs

Hardware Controlled

Tariff inputs Ta and Tb are each connected with refer-

ence to Tn. The tariffs are controlled by applying a

defined voltage level.

Tariff Inputs Tb

Ta

Tariff 1

0

0

Tariff 2

0

1 Level 0 = < 12 VAC

Tariff 3

1

0 Level 1 = 45 … 265 VAC

Tariff 4

1

1

Depending on the combination of levels 0 and 1, the values measured at the instrument are recorded in the corresponding tariff. Recording is thus possible in a daytime and a nighttime tariff, for example. Software Controlled (not included in scope of MID approval)
In the case of meters with bus (features W1 … W7), 4 further tariffs can be selected (software controlled).

12 Error Messages
If an error occurs, the respective error code and active energy or instantaneous power are displayed alternately.

Error Code Meaning

! 0L0volt All phase voltages < 75%

! 0VHi1

Maximum value for U1 exceeded

! 0VHi 2

Maximum ceeded

value

for

U2

ex-

! 0VHi3

Maximum value for U3 exceeded

! 1Hi1

Maximum value for I1 exceeded

! 1Hi2

Maximum exceeded

value

for

I2

! 1Hi3

Maximum value for I3 exceeded

! 0SYnc Frequency measuring error

! 0C0m Interface error

! EnErgY Meter defective

! 0cALib

Balancing (calibration) required

! 0AnALog DC offset too high

! 0MemErr Memory error
! 0CERT Calibration logbook

Cause/Remedy Check connection* Check connection Check connection Check connection Check connection Check connection Check connection Meter connected to direct voltage Check connection
Send meter in for repair
Replace meter

  • In the case of meters with feature U3 (100…110V L-L) including TCP/IP or Modbus RTU bus connections (W4 und W7), background illumination and the bus connection are deactivated. The meter reading profile Z1 cannot be viewed as long as the error is pending. Meter functioning is otherwise unimpaired.

Repairs

Manufacturer’s Guarantee
If your meter requires repair, please contact our service department (see reverse side of this folder).
i Note

Loss of Warranty and Guarantee Claims
Unauthorized modification of the meter is prohibited. This also includes opening the meter. If it can be ascertained that the instrument has been opened by unauthorized personnel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any consequential damages. If the manufacturer’s seal is damaged or removed, all guarantee claims are rendered null and void.
The instruments are guaranteed for a period of 3 years after shipment. The manufacturer’s guarantee covers materials and workmanship. Damages resulting from use for any other than the intended purpose or operating errors, as well as any and all consequential damages, are excluded.
14 Verification
The calibration period in Germany is 8 years. Verification by our state- approved test laboratory (EB-8) is possible at any time (see reverse side of this folder).

15 Disposal and Environmental Protection
The following comments refer specifically to the legal situation in the Federal Republic of Germany. Owners or end users who are subject to other national requirements are required to comply with the respectively applicable national requirements and to implement them correctly on site.
The symbol on the left depicting a crossed-out garbage can on wheels refers to the legal obligation of the owner or end user (German electrical and electronic equipment act ElektroG and German battery act BattG) not to dispose of used electrical equipment and batteries with unsorted municipal waste (“household trash”).
Old devices, electrical or electronic accessories and depleted batteries used in Germany can be returned free of charge to Gossen Metrawatt GmbH or the service provider responsible for their disposal in compliance with applicable regulations, in particular packaging and hazardous goods laws. Further information can be found on our website.
16 CE Declaration
The instrument fulfills all requirements of applicable EU directives and national regulations. We confirm this with the CE mark. The CE declaration of conformity is available upon request (see link on title page).

Operating Overview Key

Keys

ENTER key (press briefly)

Long ENTER key (press and hold)

UP key (press briefly)

Abbreviations

CT

Transformation ratio, current

IN

N conductor current (calculated)

S0

S0 pulse output

THD

Distortion component

(for voltage and current)

VT

Transformation ratio, voltage

Features

M1

Multifunctional variant:

Measurement of U, I, P, Q, S, PF, f, THD, IN

M2

Measurement of reactive energy

M3

Multifunctional variant:

Measurement of U, I, P, Q, S, PF, f, THD,

IN, reactive energy

Q1

Programmable transformation ratios

Q9

Fixed transformation ratios

V2/V4

Programmable S0

V9

Customer-specific S0 rate

W1 … W7 Bus connections

Z1

Meter reading profile (only possible with

bus)

Z2

Certified meter reading profile

Configuration and Operation

STANDARD DISPLAY Active energy import Active power import

12345. 678

T1
kWh

4567 W

Long

1n a

Firmware

Long

Version
1. 00

View Active and Reactive Energy / Display Test / Calibration Display / Set Transformation Ratio / Set S0 Interface Parameters

Active tariff (here T1)

All tariffs *

Reactive energy, inductive (M2/M3 only) Active energy export Reactive power, inductive (M2/M3 only) Active power export

12345. 678

T1
kVArh

12345. 678

T1
kWh

678 VAr

4567 W

1n R

0 u t a-

Reactive energy, capacitive (M2/M3only) Active energy import, total

Active energy export, total

Reactive power, capacitive (M2/M3 only) Reactive energy import, tot. (M2/M3 only) Reactive energy ex. tot. (M2/M3)

12345. 678

T1
kVArh

678 VAr

12345. 678

T1T3
kWh

. T2T4
12345 678 kVArh

12345. 678

T1T3
kWh

. T2T4
12345 678 kVArh

0 u t R-

1 n

0 u t

Display test
8888:88:88 kWh 8888:88:88 kWh 88:88:88

2 further test images

  • Max. 4 tariffs with S0 (V1 … V9) or 8 tariffs with bus (W1 … W7)

Transformation ratios (Em238x only)

Calibration display
2345. 6789 kWh 1234.5678 kWh
1234 W

Fixed display and illumination ­ live values
2345. 6789 kWh Active energy import . 1234 5678 kWh Active energy export
Hold

CT

10000
c t

VT

1000

u t

Pulse frequency

50 1000

per kWh

10000
c t set
1000
u t set

Setting CT or VT (U238x with feature Q1)
Q0: CT = VT = 1 Q1: adjustable (CT × VT 100,000) Q9: Fixed individually (default: QCT = 1 … 10,000,
QVT = 1 … 1000, CT × VT 1,000,000)
Blinking cursor / entry
Identifies the current entry position. Next cur-
sor position via ENTER.
The value at the cursor position can be
changed with the UP key.
When the least significant digit (rightmost) is
acknowledged by pressing the ENTER key, the entry is saved and SAVinG appears briefly as
confirmation at auxiliary display 2.

50 1000
per kWh set

Adjusting Pulse Frequency ­ feature V2/V4 only Number of pulses read out per kWh.

Different values can be displayed. Which values are displayed depends on the feature (see table below).
Feature-dependent displays appear in gray in the graphic overview.

Measuring Function Measured Quantity

Accuracy

(Display) Feature M0 M1 M2 2 M3 2

Active energy (kWh) 1 EP1…EP8, EPtot

1%

Reactive energy (kVArh)

EQ1…EQ8, EQtot

2%

·· · · —- · ·

Star voltage (V) Delta voltage (V) Current per phase (A) Neutral conductor current (A)

U1N, U2N, U3N U12, U23, U13 I1, I2, I3 IN

0.5% 1 d — · — · 0.5% 1 d — · — · 0.5% 1 d — · — · 1% 1 d, typ. — · — ·

Active power (kW) P1, P2, P3, Ptot

1% 1 d

–· — ·

Reactive power (kVAr) Q1, Q2, Q3, Qtot

1% 1 d

–· — ·

Apparent power (kVA) S1, S2, S3, Stot

1% 1 d

–· — ·

Power factor (cos) PF1, PF2, PF3, PFtot 1% 1 d

–· — ·

Frequency (Hz)

f

0.05% 1 d — · — ·

RMS distortion value THD U1, U2, U3

–· — ·

THD I1, I2, I3

–· — ·

1 Total active power (kW) appears at auxiliary display 2 2 Not approved for billing purposes in Switzerland

S0 pulse output (only with feature W0)**

Pulse duration
50 0.100
sec
Pulse source

50 0.100

sec

set

Adjusting Pulse Duration ­ feature V2/V4 only
Duration of the pulse for the on state or the high value.
Default: 30 ms Recommendation in case of processing problems: 70 ms
When selecting the value to be adjusted, consider the mutual dependence of pulse frequency and pulse duration.

50 srC1/2

50 srC1/2

Select 4 pulse sources for pulse outputs S01 and S02 ­
feature V2/V4 only

+ / ­ kWh

+ / ­ kWh ­ Active energy import kWh or export ­ kWh

set

­ Reactive energy import kVAr or export ­ kVAr
2 states: S0 switch is “Closed” or “0pen”

** Refer to the corresponding interface description (link on title page) for further menus in the case of bus connections (feature W1 … W7) ­ the meter reading profile setting can be found

Switching Tariffs / View Active and Reactive Energy / Power Displays / Mains Monitor / Retrieving and Setting the Meter Reading Profile

Tariff (T1)

active energy Reactive energy (M2/M3)

1.8.1

12345. 678

T1
kWh

. 3.8.1 12345 678 kVArh

t1 : 1 n

Active tariff (here T1)

Q1: secondary calibrated

Power displays M1/M3 only

Mains monitor M1/M3 only

Active energy import, total

3/4-wire

Reactive energy import, total (M2/M3) Active power per phase

Phase voltages

4-wire only

4-wire only

1.8.0

12345. 678

T1T3
kWh

. T2T4
3.8.0 12345 678 kVArh

1 1234

T1
W

2 1234

1

230.0

T1
V

2 230.4

1 n

3 1234

3 230.4

Tariff (T1)

2.8.1

12345. 678

T1
kWh

. 4.8.1 12345 678 kVArh

t1 : 0 u t

Export, total

Reactive power per phase

2.8.0

12345. 678

T1T3
kWh

. T2T4
4.8.0 12345 678 kVArh

T1
11234 VAr 2 1234

0 u t

3 1234

4-wire only

Delta voltage

12

400.4

T1
V

23 400.4

31: 400.4

Tariff (T2)

1.8.2

12345. 678

T1
kWh

. 3.8.2 12345 678 kVArh

t2: 1n

Tariff (T1)

Apparent power per phase

1.8.1

12345. 678

T1
kWh

. 3.8.1 12345 678 kVArh

1 1 234

T1
VA

2 1234

t1 : 1 n

3 1234

4-wire only

Phase currents

1 1 . 234

T1
A

2 1. 234

3 1. 234

Tariff (T2)

2.8.2

12345. 678

T1
kWh

. 4.8.2 12345 678 kVArh

t2: 0ut

Tariff (T1)

2.8.1

12345. 678

T1
kWh

. 4.8.1 12345 678 kVArh

t1 : 0 u t

Total power T1
1234 VA 1234 VAr
1234 W

1n1.234

T1
A

N conductor current

(4-wire only)

. Line frequency
50 00 hz kW

4-wire only

Tariff (T3)

1.8.3

12345. 678

T1
kWh

. 3.8.3 12345 678 kVArh

t3: 1n

Tariff (T2)

Power factor per conductor

1.8.2

12345. 678

T1
kWh

. 3.8.2 12345 678 kVArh

pf1 : 1. 00 T1 2 : 1. 00

t2: 1n

3 : 1. 00

4-wire only

THD U1, U2, U3
dv1 : 0.120 T1 2 : 0. 042 3 : 0. 050

Tariff (T3)

2.8.3

12345. 678

T1
kWh

. 4.8.3 12345 678 kVArh

t3: 0ut

Tariff (T2)

2.8.2

12345. 678

T1
kWh

. 4.8.2 12345 678 kVArh

t2: 0ut

Power factor
pf : 1. 00 T1
50.00 Hz

THD I1, I2, I3
d11 : 0. 476 T1 2 : 0. 120 3 : 0. 092

Tariff (T4)

1.8.4

12345. 678

T1
kWh

. 3.8.4 12345 678 kVArh

t4: 1n

Tariff (T4)

2.8.4

12345. 678

T1
kWh

. 4.8.4 12345 678 kVArh

t4: 0ut

Tariff (T3)

1.8.3

12345. 678

T1
kWh

. 3.8.3 12345 678 kVArh

t3: 1n

Tariff (T3)

2.8.3

12345. 678

T1
kWh

. 4.8.3 12345 678 kVArh

t3: 0ut

OBIS Feature W1 … W7: T5 … T8

T4, feature W1 … W7: T5 … T8

2-wire

Apparent/reactive/active power

Voltage/current/frequency

T1
1234 VA

123.4

T1
V

1234 VAr

1. 234 A

1234 W

50.00 Hz

Power factor
pf : 1. 00 T1
50.00 Hz

THD U, I
dv : 0. 028 T1 d1 : 0. 082

Meter reading profile Z1 (only with feature Z1 and with bus W1 … W7)

2/3/4-wire

Retrieve meter reading profile

23456.78

T1
kWh

d 15 13 : 30

16.10.16

Return to main menu
Duration (dt) / time (hh:mm) Date (DD.MM.YY)

Retrieve meter reading profile Z1 :
Each time the UP key is pressed, the next older meter reading profile is displayed along with its date and time.

Setting Meter Reading Profile Z1

Standard display

12345. 678

T1
kWh

1234567 W

1 n a

Firmware

Long

Version T1
1. 00

2 ×

Blinking cursor /
entry
Identifies the current entry position. Next cur-
sor position via ENTER.
The value at the cursor position can be
changed with the UP
key. When the least significant digit (rightmost) is acknowledged by
pressing the ENTER key,
the entry is saved and
SAVinG appears briefly
as confirmation at auxiliary display 2.

Duration

15 T1

dt

Long

1 5 T1 dt set

Setting Duration

Long Duration dt can be set with UP: 1, 2, 3, 4, 5, 10, 15, 30 or 60 min.
Default = 15. Integration takes place synchronous to clock time.

Retrieve meter reading profile Z1 (see above)
Certified meter reading profile (only with feature Z2) (Only with feature W4 and without U3) Please refer to the TCP/IP interface description for a description of the certified meter reading (Z2) (available on the Internet, see link on title page).

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GOSSEN METRAWATT User Manuals

Related Manuals