iskydance DT AC Triac DALI Dimmer Owner’s Manual

June 12, 2024
iskydance

iskydance DT AC Triac DALI Dimmer

Product Information

  • Product Name: AC Triac DALI Dimmer
  • Model No.: DT

Features:

  • AC phase-cut mosfet DALI dimmer
  • One DALI address, one channel output
  • Compliant with DALI standard protocol IEC 62386-102, IEC 62386-207
  • DALI address can be manually assigned or automatically assigned by DALI master
  • Reverse-phase dimming or forward-phase dimming selectable
  • Connect with external push switch for on/off and dimming function
  • Suitable for dimming single color dimmable LED lamps, traditional incandescent, and halogen lights
  • Over-heat protection with automatic recovery

Technical Parameters:

  • Input voltage: AC100-240V
  • Output voltage: AC100-240V
  • Output current: Max 1.5A
  • Output power: 150-360W
  • Dimming level: 256 levels
  • Dimming range: 0 – 100%
  • Operation temperature: -30°C to +55°C
  • Case temperature (Max.): +70°C
  • IP rating: IP20

Warranty and Protection:

  • Warranty: 5 years
  • Protection: Over-heat, LVD

Safety and EMC:

  • EMC standard (EMC): ETSI EN 301 489-1 V2.2.3, ETSI EN 301 489-17 V3.2.4
  • Safety standard (LVD): EN 62368-1:2020+A11:2020
  • Certification: CE, EMC, LVD
  • Package Size: L190 x W48 x H25mm
  • Gross weight: 0.140kg

Product Usage Instructions

  1. Make sure all wire connections and polarities are correct and secure before applying power to avoid damage.
  2. Connect the AC L input and AC N input to the corresponding power supply.
  3. Connect the dimmable LED light or dimmable LED driver to the AC100-240V OUTPUT and AC100-240V INPUT respectively.
  4. If using a push switch for on/off and dimming function, connect it to the PUSH-DIM terminals.
  5. Set the DALI address either manually or automatically assigned by the DALI master. The assigned address will be shown in the digital display.
  6. Select the desired dimming mode by long-pressing the two buttons simultaneously for 2 seconds. Switch between reverse-phase dimming (CR) or forward-phase dimming (CF).
  7. Ensure that the compatible load types and maximum load limits are not exceeded.
  8. Observe the recommended operation temperature range of -30°C to +55°C.

Note: For calculating the maximum number of load lamps or drivers, use the input power or input current parameters of a single lamp or driver, not the output power parameters. The sum of surge current of multiple dimmable LED drivers should not exceed 2 times 65A to prevent overload and damage to the product.

AC Triac DALI Dimmer

Model No.: DT

1DALI address/1 Channel output/Leading edge or trailing edge/Numeric display

Features

  • AC phase-cut mosfet DALI dimmer, one DALI address, one channel output.
  • In accordance with DALI standard protocol IEC 62386-102, IEC 62386-207 and in compliance with DALI products from other international incorporation.
  • DALI address can be manually assigned and shown in digital display or automatically assigned by DALI master.
  • Reverse-phase dimming or forward-phase dimming selectable.
  • Connect with external push switch to achieve on/off and 0-100% dimming function.
  • To dim and switch single color dimmable LED lamps, traditional incandescent and halogen lights.
  • Over-heat protection, recover automatically.

Technical Parameters

Input and Output

Input voltage| AC100-240V
Output voltage| AC100-240V
Output current| Max 1.5A
Output power| 150-360)W
Dimming level| 256 levels
Dimming range| 0 -100%
|

Environment

Operation temperature| Ta: -30 OC ~ +55OC
Case temperature (Max.)| Tc: +70OC
IP rating| IP20
Warranty and protection
Warranty| 5 years
protection| Over-heat
|

Safety and EMC

EMC standard (EMC)| ETSI EN 301 489-1 V2.2.3

ETSI EN 301 489-17 V3.2.4

Safety standard(LVD)| EN 62368-1:2020+A11:2020
Certiication| CE,EMC,LVD
Package
Size| L190x W48 x H25mm
Gross weight| 0.140kg

Mechanical Structures and Installations

iskydance-DT-AC-Triac -DALI-Dimmer-01

Wiring Diagram

  • Caution: Please carefully ensure all wire connections and polarities are correct and secure before applying power, otherwise this controller will be damaged.iskydance-DT-AC-Triac -DALI-Dimmer-02

Note: When calculating the maximum number of load lamps or drivers, the input power or input current parameters of a single lamp or driver must be used, the output power parameters can not be used.
In addition, the maximum surge current of the dimmer is 65A, the sum of surge current of multiple dimmable LED drivers should not exceed 2 times. otherwise, the product will be overloaded and damaged.

Compatible Load Types

Load Type Maximum Load Remarks
Dimmable LED lamps 200W  @ 220V

100W  @ 110V

| Due to variety of LED lamp designs, maximum number of LED lamps

is further dependent on power factor result when connected to dimmer.

Triac Dimmable LED drivers| 200W  @ 220V

100W  @ 110V

| Maximum permitted number of drivers is 200W divided by driver nameplate power rating, and make sure the surge current is no more than 2 times 65A.
Incandescent lighting, HV Halogen lamps| 400W  @ 220V

200W  @ 110V

|

Operation

Reverse-phase or forward-phase dimming setting
Long press two buttons at the same time for 2s, switch between reverse-phase dimming(“CR”) or forward-phase(“CF”) dimming.iskydance-DT-AC-Triac -DALI-
Dimmer-2

Minimum brightness setting

  • Under Reverse-phase or forward-phase dimming setting, Long press two buttons at the same time for 2s, digital display start ?ashes.
  • Short press left button to set “tens” position and right button to set “units” position.
  • The minimum brightness can be set to 1%~40%, the factory default is 10%.
  • Long press any of the two buttons for 2s or timeout 10s, quit Minimum brightness setting, digital display stop ?ashes.

Set DALI Address via buttons

  • Long press any of the two buttons for 2s, prepare for set the start DALI address, digital display start ?ashes.
  • Short press left button to set “tens” position and right button to set “units” position.
  • The address can be set from 00~63-FF. no DALI address is assigned for the dimmer, digital display shows “FF”.
  • Long press any of the two buttons for 2s or timeout 10s, quit start DALI address setting, digital display stop ?ashes.

DALI address assigned by DALI masters

  • DALI address can also be assigned by DALI Master controller automatically.
  • Please refer to user manuals of compatible DALI Masters for specific operations.
  • The digital display will show “AU” When the DALI master is assigning address.
  • After address is assigned, the digital display will show the start DALI address”xx”, xx is from 00 to 63.

Push-Dim Function
The provided Push-Dim interface allows for a simple dimming method using commercially available non-latching(momentary) wall switchs.

  • Short press:
    Turn on or off light.

  • Long press (1-6s):
    Press and hold to step-less dimming,
    With every other long press, the light level goes to the opposite direction.

  • Dimming memory:
    Light returns to the previous dimming level when switched off and on again, even at power failure.

  • Synchronization:
    If more than one controller are connected to the same push switch, do a long press for more
    than 10s,then the system is synchronized and all lights in the group dim up to 100%.
    This means there is no need for any additional synchrony wire in larger installations.
    We recommend the number of controllers connected to a push switch does not exceed 25 pieces, The maximum length of the wires from push to controller should be no more than 20 meters.

Safety & Warnings

  • DO NOT install with power applied to device.
  • DO NOT expose the device to moisture.

Guangzhou SkyacneCo.,Ltd

www.iskydance.cn

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

iskydance User Manuals

Related Manuals