BEGA 33 054 Recessed Luminaire Instruction Manual

June 12, 2024
BEGA

33.19 Technical amendments reserved
Recessed luminaire
33 054
BEGA 33 054 Recessed Luminaire -

Instructions for use

Application
Recessed luminaire for walls and staircases for flush or surface-mounted installation.
With asymmetrical light distribution for glarefree illumination of surfaces from low mounting height.

Product description
Luminaire made of aluminium alloy,
aluminium and stainless steel
BEGA Tricoat® coating technology
Clear safety glass
Silicone gasket
Fixing is achieved by using two adjustable
wedge-shaped claws
Required recessed opening 245 x 60 mm
Recessed depth 70 mm
2 cable entries for through-wiring of mains
supply cable ø 7-10.5 mm
Connection terminal 2.5@
Earth conductor connection
LED power supply unit
220-240 V x 0/50-60 Hz
DC 198-264 V
BEGA Thermal Switch®  Temporary thermal shutdown to protect temperature- sensitive components
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK09
Protection against mechanical
impacts < 10 joule
– Safety mark
**** – Conformity mark
Weight: 0.8 kg
This product contains light sources of energy efficiency classes C

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp|
---|---
Module connected wattage| 5.7 W
Luminaire connected wattage| 7.7 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 40 °C
When installed in heat-insulating material|  ta max = 35 °C
33 054 K3

Module designation| LED-0539/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 995 lm
Luminaire luminous flux| 410 lm
Luminaire luminous efficiency| 53,2 lm / W
33 054 K4

Module designation| LED-0539/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 1010 lm
Luminaire luminous flux| 416 lm
Luminaire luminous efficiency| 54 lm / W

Please note:
This luminaire is coated with BEGA Tricoat®. BEGA Tricoat® is a registered trademark for a technology that we use to achieve optimal corrosion resistance.
Even the best possible surface protection and the highest corrosion resistance can be rendered almost ineffective in some cases by aggressive media caused by leaching of building materials.
Where such media are suspected, a material analysis must be carried out before installation.
Always avoid excessive use of chemical cleaning agents in the vicinity of the luminaire.

Installation

The recessed opening will be covered by the frame of the luminaire housing.
Fixing of the luminaire is achieved by using two adjustable wedge-shaped claws.
Installation in solid, plastered walls:
The installation housing 10 425 is available for this purpose. If this is not used, an exact recessed opening of 245 x 60 mm with a minimum depth of 70 mm is required.
Installation in exposed brickwork:
The construction of an on-site recessed opening with the exact installation dimensions of 245 x 60 mm with a minimum depth of 70 mm is required. An installation housing cannot be used.
Installation in drywalling:
A recessed opening of 245 x 60 mm with a minimum depth of 70 mm is required.
The claws grip behind drywall.
Installation into insulated façades:
For installation in EWIS external wall insulation systems pleaseuse installation housing 13 520 in combination with a plaster frame 10 025 or 13 504.
Open luminaire:
Undo screws and remove housing cover.
Disconnect plug-connection of the LED connecting cable.
Disconnect the earth conductor connection from the plug connection.
Lead the mains supply cable through the cable entry into the luminaire housing.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
Connect the LED connection cable by means of a plug connector.
Put on earth conductor connection of the housing cover. Assemble housing cover.
Make sure that gasket is positioned correctly.
Tighten the screws evenly.
Insert luminaire housing into the recessed opening. Tighten screws of the claw fastener evenly.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free
cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Accessories

10 425 Installation housing
13 520 Installation housing for installation in insulated façades (EWIS)
10 025 Plaster frame
13 504 Plaster frame flush

A separate instructions for use can be provided upon request.

Spares

LED power supply unit DEV-0183/500
LED module 3000 K LED-0539/830
LED module 4000 K LED-0539/840
Gasket 83 001 526

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals