BEGA 50 965.5 Track Spotlight Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
50 965.5
Track spotlight for indoor use
Instructions for use
Application
Ceiling mounted track spotlight · indoor luminaire for 3-phase Eurostandard-
Plus ® track systems.
The optical system of the washer is swivelmounted and rotatable. Symmetrical
wide beam light distribution.
With BEGA Hybrid Optics ® : Highly efficient and low-loss light distribution,
thanks to reflector and optical lens.
Product description
Track spotlight with adapter
Cast aluminium luminaire housing, finish Colour velvet black, Polycarbonate
track adapter with integrated
LED power supply unit
Trim ring · Chrome finish
Clear safety glass
Optical silicone lens · BEGA Hybrid Optics ®
Reflector surface made of pure aluminium LED power supply unit 220-240 V y
50/60 Hz
DALI-controllable
Basic insulation is provided between the mains and control cables
Safety class II 2
**** – Conformity mark
Weight: 0.9 kg
This product contains light sources of energy efficiency classes E
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
Lamp
Module connected wattage | 12.3 W |
---|---|
Luminaire connected wattage | 14.5 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 60 °C |
50 965.5 K3
Module designation | LED-0986/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1685 lm |
Luminaire luminous flux | 1315 lm |
Luminaire luminous efficiency | 90,7 lm / W |
50 965.5 K4
Module designation | LED-0986/940 |
---|---|
Colour temperature | 4000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1710 lm |
Luminaire luminous flux | 1334 lm |
Luminaire luminous efficiency | 92 lm / W |
Light technique
Track spot · surface washer with adjustable optical system.
Optical system 0-60° swivel-mounted and infinitely rotatable 360° around the
vertical luminaire axis.
Symmetrical wide beam light distribution.
Half beam angle 32°
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
The track spotlight with adapter is ready for operation in 3-phase
EUROSTANDARD-PLUS ® track systems.
The mounting is done without tools in the bus bar.
IMPORTANT:
Ensure that the adapter’s two lateral stays are located on the same side as
the matching guide profile of the track before installing the adapter in the
3-phase EUROSTANDARDPLUS ® track system.
To select the phase ( 1 2 3 ) the turning knob on the rear side of the adapter
has to be operated accordingly.
Screw enclosed trim ring with attached reflector into the luminaire housing by
turning it clockwise until it stops, so that it is fixed by clamping.
Place the surface washer adapter flush on the conductor rail in the desired
position.
Push the two fixing levers on the underside of the adapter to the right until
they click into their end position.
Set the desired LED beam direction by turning and tilting the luminaire
housing.
Move the two fixing levers in opposite directions until they disengage to
unlock the adapter.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The replacement can be carried out by
a qualified person using standard tools.
Disconnect the system and open the luminaire.
Uninstall the reflector.
Please follow the installation instructions for the LED module.
Install the reflector. Defective glass must be replaced. Close the luminaire.
Spares
LED power supply unit
LED module 3000 K
LED module 4000 K
Reflector unit
Glass/Trim ring
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden
· info@bega.com
· www.bega.com
References