BEGA 51 013.6 Ceiling Luminaires Instructions

June 12, 2024
BEGA

BEGA 51 013.6 Ceiling Luminaires

Product Information

Leuchtmittel| Modul-Anschlussleistung| Leuchten-Anschlussleistung| Bemessungstemperatur| Umgebungstemperatur
---|---|---|---|---
51 013.6 K3| 26.4 W| 29.4 W| 25°C – 50°C| 3000 K
Colour temperature| Colour rendering index (CRI)| Module luminous flux| Luminaire luminous flux| Luminaire luminous efficiency
---|---|---|---|---
3000 K| CRI > 90| 3970 lm| 2348 lm| 79.9 lm/W

Product Usage Instructions

  1. Installation:
    • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
    • The synthetic cover is removed by turning it anti-clockwise as far as it will go while simultaneously pushing the synthetic cover up against the luminaire fitting.
  2. Safety:
    • The installation and operation of this luminaire are subject to national safety regulations.
    • Installation and commissioning may only be carried out by a qualified electrician.
    • The manufacturer accepts no liability for damage caused by improper use or installation.
    • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
  3. Overvoltage protection:
    • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
    • To achieve an additional protection against e.g. transients,etc., we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
  4. Spares:
    • Synthetic cover: 15 000 633 71 001 760 L14
    • Shield: 75 005 349 K3
    • LED unit 3000 K: 15 000 633 71 001 760 L14

Ceiling luminaire for indoor use

BEGA-51-013.6-Ceiling-Luminaires-FIG-1

Instructions for use

Application
Ceiling luminaire · indoor luminaire impact
resistant synthetic diffuser and metal housing
for non-glare light deflected downwards.

Product Description
  • Ceiling luminaire »STUDIO LINE«
  • Aluminium luminaire housing,
  • finish Colour velvet black
  • inside hue matt copper
  • Metal luminaire mounting plate,
  • finish Colour velvet black
  • Impact resistant synthetic diffuser, white,with bayonet closure
  • 2 mounting holes ø 5.5 mm
  • Distance apart 230 mm
  • 2 cable entries for through-wiring for mains cable up to ø 10,5 mm max. 5 x 1.5@ Connection terminal 2.5@
  • Earth conductor connection
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Impact strength IK10
  • Protection against mechanical
  • impacts < 20 joule
  • Safety mark
  • – Conformity mark
  • Weight: 2.6 kg
    This product contains light sources of energy efficiency class(es) D

Lamp

  • Module connected wattage 26.4 W
  • Luminaire connected wattage 29.4 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 50 °C

51 013.6 K3

  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 3970 lm
  • Luminaire luminous flux 2348 lm
  • Luminaire luminous efficiency 79,9 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

BEGA-51-013.6-Ceiling-Luminaires-FIG-4

  • Before installing onto the ceiling the luminaire mounting plate must be inserted into the luminaire housing.
  • Thereby pass the mains supply cable through the grommet into luminaire mounting plate. Fix monting plate inside the luminaire housing with enclosed or any other suitable fixing material on to the mounting surface. Dismantle the mains supply cable approx. 60 mm.
  • Make earth and electrical connection to the terminals.
  • For digital control please use the connecting terminal DA, DA.
  • In case this terminal is not used the luminaire will be operated at full light output.
  • In order to securely install the synthetic cover in the fitting, the top opening of the synthetic cover must be inserted into the luminaire housing at an angle.
  • Make sure that at least one of the recesses in the edge of the synthetic cover matches the position of one of the lugs on the fitting –see drawing.

IMPORTANT:

  • Turn the synthetic cover upwards into the fitting as far as it will go. Now secure the synthetic cover in the fitting by turning it clockwise.
  • Only then is the synthetic cover held securely in place and resistant to vibration.
  • The synthetic cover is removed by turning it anti-clockwise as far as it will go while simultaneously pushing the synthetic cover up against the luminaire fitting.

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacement of the LED unit

  • The designation of the LED unit is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement units correspond to those of the LED units originally fitted. The LED unit can be replaced by qualified persons using standard tools.
  • Disconnect from main supply.
  • Unscrew synthetic diffuser from luminaire housing by turning it counter-clockwise. Disassemble LED unit.
  • Assemble LED replacement unit.
  • Note installation instructions of the LED unit. Screw in synthetic diffuser by turning it clockwise.
  • A damaged synthetic diffuser must be replaced.

Spares
Synthetic cover 15 000 633
Shield 71 001 760 L14
LED unit 3000 K 75 005 349 K3

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com