rutec 80795-V2 DALI-2 Push Dimm-Actor Instruction Manual

June 9, 2024
rutec

80795-V2 DALI-2 Push Dimm-Actor
Instruction Manualrutec 80795-V2 DALI-2 Push Dimm-
Actorrutec 80795-V2 DALI-2 Push Dimm-Actor - icon
1 DALI-2 Push Dimm-Actor
80795-V2

80795-V2 DALI-2 Push Dimm-Actor

The rutec DALI-2 Push dimming actor has one channel with one address for single-colour controls and enables digital or analogue dimming with soft control behaviour. The DALI address can be addressed automatically with the help of DALI Masters. The DALI-2 Push dimming actor, can be regulated with the help of DALI signals or a push-button control.

DIP SCHWITCHES SETTING OPTIONS:

Articel no.| Input Voltage| Output Voltage| Output Power| Output Current
---|---|---|---|---
80795-V2| 200-240V AC| 5-52 V DC max| 15 W max| 100-700 mA

PRUDUCT DIMENSIONS:

rutec 80795-V2 DALI-2 Push Dimm-Actor - fig1

DIP SWITCH SETTINGS:

Use the dip switch to set the required current value in the de-energised state.rutec 80795-V2 DALI-2 Push Dimm-Actor - fig 3

OUTPUT POWER:

m z’s-st melt-9C° M tiOL-L M EL-SZIL M SL-S’L M SL-SeL 1nod
A ZS-5 A ZS-5 A ZS-S A ZS-5 A 05-5 A E7-S Mon
VW OW. VW OSL Vw 00Z Vw OSZ VW 00E VW OSE Viol
M SL-Z m seitn-stz Ansysiz M 5EP7L-SLIZ M SL-E M 56’7L-StE M SL-SIE
--- --- --- --- --- --- ---
A 8E-S A EE-S A 0E-S A tz-s A SZ-S A EZ-S A U-S
Val 007 VW O97 Val 009 VW OSS Val 009 VW 059 Val OOL

WIRING DIAGRAM:

rutec 80795-V2 DALI-2 Push Dimm-Actor - fig 2

PUSH BUTTON (PUSH DIM) OPERATION:

rutec 80795-V2 DALI-2 Push Dimm-Actor - fig 4

OPERATING INSTRUCTIONS:

1. automatic setting:
The DALI-2 master unit assigns the addresses automatically. For the function, refer to the operating instructions of the master controller.
2. push-dim
As soon as the terminals Da+(L’) and Da-(N) have been connected with the 230 V AC pushbutton, the display changes to PD which stands for the operating mode “Push-Dimm”.

  • Pressing briefly switches the outputs on/off.
  • Pressing and holding dims the light strip to the desired brightness value.
  • Press and hold again to dim the continuous row again.
  • The dimming range is 1-100

The “push dim” mode has a memory effect so that after a short-circuit or loss of voltage/voltage recovery, the light is switched to the voltage recovery, the light returns to the last known brightness value.

SAFETY INSTRUCTIONS:

  1. Be sure to have a professional electrician complete installation. There is no warranty coverage for any lights installed without observing european safety directives.
  2. The LED controller is not waterproof. Please protect the controller from direct sunlight and avoid rain. For outdoor installation, please ensure that the controller is installed in a waterproof housing.
  3. Always ensure that the unit is installed in a location with good ventilation to ensure correct operating temperature.
  4. Check that the voltage and the power adapter are suitable for the controller and that the designation of the anode and cathode matches those of the controller.
  5. Please ensure that an appropriate cable diameter is used for the connection between the controller and the LED.
  6. Never connect the cables when the power is on, check that the connections are correct and check for short circuits before switching on the power.
  7. Please do not carry out any repairs yourself. This will invalidate the manufacturer’s warranty.

Dispose of electrical and electronic devices in an environmentally friendly manner.

Carl-Zeiss-Str. 15
28857 Syke
DALI-2_Dimm-Aktor_BA_80795-V2_08/2022