The P6 Series single packaged air conditioners are high efficiency self contained cooling units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.

WARRANTY

  • This product offers a 10 year all parts warranty.
  • This product offers a 10 year Quality Pledge to replace the entire unit, if the unit’s major component (heat exchanger or compressor) fails within the first 10 years of operation, to the original owner.
  • Consumer product registration required for both 10 year All Parts Warranty and Quality Pledge within a limited period of time after the installation. See current warranty document or visit our consumer web site listed on the back of this document for warranty details.

FEATURES and BENEFITS

  • State-of-the-art Copeland Scroll compressor is standard equipment.
  • R-410A Refrigerant Environmentally friendly.
  • Proven, Industry Standard Components Easier service and availability.
  • TXV Externally equalized. Provides precise refrigerant control under varying load conditions.
  • High and Low Pressure Switches Added compressor protection.
  • Liquid Line Filter/Drier Insures clean and dry refrigeration system.
  • Externally Accessible Service Ports Quick access to refrigerant system without disrupting operation.
  • Compact Footprint/Low Profile Easy to handle and transport.
  • Convertible Air Delivery Horizontal or downflow to accommodate rooftop or horizontal application.
  • Heavy-Gauge, Full Perimeter Base Rails Facilitates forklift handling and curb mounting.
  • Galvanized Steel Cabinet Polyurethane finish provides 950 hours salt spray protection.
  • Wire Guard Coated with Earth Friendly Epoxy and Mesh Hail Guard Will never rust and protects the coil from being damaged by balls, lawnmowers, hail etc.
  • Corrosion-Resistant Drain Pan Quickly drains away evaporator condensate.
  • Quiet Operation and Low Vibration 20″ fan blade combined with custom venture condenser fan.
  • Access to Controls and Major Components Easy in and out service.
  • Service Access Panels Allows easy access to all major components and the compressor. Designed to make servicing easier for the Contractor.
  • Easy to Install Electric heat strip provides up to 20 KW of heat output.
  • Accessories Roof curbs, economizers, fresh air dampers and more.

MODEL IDENTIFICATION CODE

Model Identification Code

DIMENSIONS

Dimension

Model Number P6SD

|

Unit Weight

| Center of Gravity|

Height (in inches)

---|---|---|---

A

|

B

|

C

with base rails

X36

| 405| 29.5| 26.0| 37.7

X48

| 415| 29.5| 26.5|

37.7

X60| 480| 30.0|

27.5

| 41.7

Dimension
Dimension

SPECIFICATIONS

Model Number P6SD
X36K X48K
Performance
Capacity -Cooling BTUH 34,200
Efficiency – SEER 13.3
EER (Btuh/watt) 11.2
Electrical Rating – 60 Hz 1 187 – 253

Phase Operating Voltage Range
Compressor Data| | |
Volts| 208 I 230| 208 I 230| 208 I 230
Rated Load Amps| 18.6| 24.3| 29.3
Lock Rotor Amps| 79| 117| 134
Indoor Blower| | |
Type/ No. of Speeds Motor – HP/ RPM Motor-Amps| DD/3 1/4 – 1075 1.3| DD/3 1/2 – 1080 3.1| Fixed Torque 3/4 6.0
Outdoor Fan| | |
Motor – HP/ RPM| 1/4-1100| 1/4 – 1100| 1/4-1100
Motor-Amps| 1.2| 1.2| 1.2
Fan Diameter I CFM| 20/3600| 20/3800| 20/3800
Refrigerant Charge – Oz.| 110| 168| 192
Shipping Weight| 415| 425| 490

BLOWER PERFORMANCE

Model Number External Static Pressure Drop – inches water column
P6SD- 0.1
0.7 0.8
X36 High
Medium 1367
* Low 1153
X48 High
Medium 2026
* Low 1584
X60
TapT2 1580
* TapT3 1740
TapT4 1960
TapT5 2090
  • Denotes factory set cooling speed
    Denotes factory set electric heating speed
    NOTE:** Airflow performance is with a dry coil

MODEL IDENTIFICATION CODE
Model Identification Code

HEATER APPLICATION MATRIX

TONNAGE & PHASE| UNIT| NOMINAL KW| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
---|---|---|---|---|---
3 Ton, Single Phase| P6SD| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01 B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01 B| 917169B| 2
15| H3HK015H-21 B| 917172B| None
4 Ton, Single Phase| P6SD| 5| H3HK005H-01 B| 917166B| None
8| H3HK008H-01 B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01 B| 917169B| 2
15| H3HK015H-21 B| 917172B| None
20| H3HK020H-01 B| 917170B| None
20| H3HK020H-21 B| 917173B| None
5 Ton, Single Phase| P6SD| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| 2
15| H3HK015H-01 B| 917169B| 2
15| H3HK015H-21 B| 917172B| None
20| H3HK020H-01B| 917170B| 3
20| H3HK020H-21B| 917173B| 1

ELECTRICAL DATA

P6SD SERIES – 208/230V – SINGLE PHASE MODELS

MODEL NUMBER P6SD-| HEATER INSTALLED NOMINAL KW| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA| REC, WIRE GAGE (90 ° CCU)| MOP| CIRCUIT A (COMPRESSOR & FAN)| CIRCUIT B

(BLOWER & HEATER)

MCA| REC , WIRE GAGE (90 ° CCU)| MOP| MCA| REC, WIRE GAGE (90 ° CCU)| MOP
X36K| 0| 25.8| 10| 40| | | | | | –
5| 26.5| 10| 40| –| –| –| –| | –
8| 41.2| 8| 45| | | | | | –
10| 51.6| 8| 60| | | | | | –
15| 76.6| 4| 80| 50.0| 8| 60| 26.6| 10| 30
X48K| 0| 32.9| 8| 50| –| | –| –| | –
5| 32.9| 8| 50| –| | –| –| | –
8| 41.2| 8| 50| –| –| –| –| –| –
10| 51.6| 8| 60| –| –| –| –| –| –
15| 76.6| 4| 80| 51.6| 8| 50| 26 .6| 10| 30
20| 101.6| 3| 110| 50| 8| 50| 51.6| 8| 60
MODEL NUMBER P6SD-| HEATER INSTALLED NOMINAL KW| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA| REC, WIRE GAGE (90 ° CCU)| MOP| CIRCUIT A (C OM PRESSOR , B LOWER , & FAN)| CIRCUIT B (HEATER ONLY)| CIRCUITC (HEATER ONLY)
MCA| REC , WIRE GAGE (90 ° CCU)| MOP| MCA| REC, WIRE GAGE (90 ° CCU)| MOP| MCA| REC, WIRE GAGE (90 ° CCU)| MOP
X60K| 0| 43.8| 8| 70| –| –| | | –| | | |
5| 43.8| 8| 70| –| –| | | | | | |
8| 43.8| 8| 70| –| –| –| | | | –| –|
10| 51.5| 8| 70| 43.8| 8| 70| 50| 8| 60| | |
15| 76.5| 4| 80| 51.5| 8| 70| 25| 10| 30| | |
20| 101.5| 3| 110| 43.8| 8| 70| 50| 8| 60| 50| 8| 60

NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different circuits when adding a heater kit.

ACCESSORIES

Description Part Number
Roof Curb (8″) 547830
Roof Curb (14″) 547831
Roof Curb (18″) 547850
Roof Curb (24″) 547851
Supply/return transition, 16″ 547834
Supply/return transition, 18″ 547835
Concentric diffuser, flush, 16″ 547836
Concentric diffuser, flush, 18″ 547837
Concentric diffuser , step down 16″ 547838
Concentric diffuser , step down 18″ 547839
Manual Fresh Air Damper 547832
Motorized Fresh Air Damper 547840
Economizer, downflow w/filter (does not require filter kit) modulating 558870
Economizer, horizontal modulating 547841
Power Exhaust, downflow economizer (special order) 547842
Power Exhaust horizontal economizer (special order) 547843
HOOD TYPE HAIL GUARD 34″ X 76″ P6SD-X36, P6SD-X48 547846
HOOD TYPE HAIL GUARD 38″ X 76″ P6SD-X60 547847
DUCT SMOKE DETECTOR PHOTO ELEC 558863
MULTI SIGNAL CONTROL 547893
SAMPLING TUBE DST3, 2-4′ 558864
SAMPLING TUBE dst5, 4-8′ 558865
Filter Rack, All Downflow Applications (not required with economizer) 547885
Filter Kit (not required with economizer) P6SD-X36, P6SD-X48 547888
Filter Kit (not required with economizer) P6SD-X60 547889
Universal Hard Start Kit 912933
Low Ambient Kit 918837
Skirt Trim Kit 919729
Extreme High Wind Kit – Roof Curb Mount 903696
Extreme High Wind Kit – Ground Mount 903695
Heater Kit – 4-Pole single circuit adaptor 913350
Heater Kit – 6-Pole single circuit adaptor 913556
Heater Kit – Circuit breaker single phase (2-pole) 913554
Freeze stat Kit 917108
Duct Adopter, 14″ Round (2 each) 913812A
Control, CO2 sensor, wall mount 547848

COOLING EXPANDED RATINGS

P6SDX36

O.D.T| 85o F| 95 ° F| 105 ° F| 115 ° F
---|---|---|---|---
CFM| E.D.B.| E.W.B.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.
900| Rn| 62| 32.7| 26.3| 2.67| 31.2| 26.4| _2 Qi::;| 29.6| 27.2| 3.27| 27.9| 26.8| 3.64
80| 67| 35.6| 21.3| 2.70| 33.9| 20.7| 2.98| 32.1| 20.2| 3.30| 30.1| 19.5| 3.67
80| 72| 38.9| 16.3| 2.75| 37.1| 15.8| 3.03| 35.2| 15.2| 3.34| 33.1| 14.7| 3.71
75| 63| 33.1| 21.0| 2.68| 31.5| 21.1| 2.95| 29.8| 21.0| 3.28| 28.0| 20.6| 3.64
1000| 80| 62| 33.5| 28.0| 2.68| 31.9| 29.0| 2.96| 30.3| 29.0| 3.28| 28.7| 28.7| 3.65
80| 67| 36.2| 22.5| 2.71| 34.4| 22.0| 2.99| 32.6| 21.4| 3.31| 30.7| 20.9| 3.67
80| 72| 39.6| 17.1| 2.76| 37.8| 16.6| 3.04| 35.8| 16.0| 3.35| 33.7| 15.5| 3.72
75| 63| 33.7| 23.1| 2.68| 32.0| 22.9| 2.96| 30.4| 22.8| 3.28| 28.6| 22.2| 3.65
1100| 80| 62| 34.7| 31.2| 2.69| 33.1| 31.3| 2.97| 31.6| 31.6| 3.30| 29.9| 29.9| 3.66
80| 67| 37.3| 24.5| 2.73| 35.5| 23.9| 3.00| 33.6| 23.2| 3.32| 31.6| 22.6| 3.69
80| 72| 40.7| 18.2| 2.77| 38.8| 17.7| 3.05| 36.7| 17.2| 3.37| 34.5| 16.6| 3.73
75| 63| 34.8| 26.0| 2.70| 33.1| 25.6| 2.97| 31.3| 24.9| 3.29| 29.4| 24.2| 3.66

P6SDX48

O.D.T| 85o F| 95 ° F| 105 ° F| 115 ° F
---|---|---|---|---
CFM| E.D.B.| E.W.B.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.| T.C.| s.c.| K.W.
1250| 80| 62| 44.1| 35.7| 3.45| 42.2| 36.0| 3.84| 40.0| 37.1| 4.27| 37.8| 36.6| 4.77
80| 67| 47.9| 28.8| 3.50| 45.5| 28.0| 3.87| 43.1| 27.2| 4.31| 40.6| 26.7| 4.80
80| 72| 52.1| 21.9| 3.54| 49.5| 21.2| 3.92| 46.9| 20.5| 4.35| 44.2| 19.8| 4.85
75| 63| 52.1| 16.3| 3.54| 49.5| 16.7| 3.92| 47.0| 16.7| 4.35| 44.2| 16.4| 4.85
1400| Hal| 62| 4S.2| ‘<R.2| 3.46| 43.1| 39.S| 3,Ri:;| 41.0| – <-l. S| 4.29| 39,0| 39,0| 4.78
80| 67| 48.7| 30.6| 3.51| 46.3| 29.8| 3.88| 43.9| 29.4| 4.32| 41.4| 28.6| 4.81
80| 72| 52.9| 23.1| 3.54| 50.4| 22.4| 3.93| 47.7| 21.6| 4.36| 44.9| 20.9| 4.86
75| 63| 53.1| 18.2| 3.55| 50.5| 18.2| 3.93| 47.7| 17.9| 4.36| 45.0| 17.4| 4.86
1550| Rn| 62| 46.2| 41.8| 3.47| 44.2| 41.9| 3,86| 42.2| 42.2| 4.'<n| 40.1| 40.1| 4.Rn
80| 67| 49.6| 32.7| 3.51| 47.1| 32.0| 3.89| 44.6| 31.2| 4.33| 42.0| 30.4| 4.82
80| 72| 53.8| 24.2| 3.55| 51.1| 23.5| 3.95| 48.4| 22.8| 4.37| 45.5| 22.0| 4.86
75| 63| 53.8| 20.3| 3.55| 51.1| 19.8| 3.95| 48.4| 19.2| 4.37| 45.5| 18.4| 4.87

P6SDX60

O.D.T 85o F 95 ° F 105 ° F 115°F
CFM E.D.B. E.W.B. T.C. s.c.
T.C. s.c. K.W. T.C. s.c.
s.c. K.W.
1600 80 62 56.7 45.9
46.7 6.19
80 67 61.2 37.4 4.62
80 72 66.6 28.6 4.72
75 63 57.0 36.9 4.54
1750 80 62 57.8 48.3
49.2 6.24
80 67 62.0 39.2 4.67
80 72 67.1 29.8 4.77
75 63 57.8 40.1 4.59
1900 80 62 58.7 52.1
50.4 6.30
80 67 62.7 40.9 4.72
80 72 67.5 30.9 4.81
75 63 58.5 43.5 4.64

GENERAL TERMS OF LIMITED WARRANTY

NORDYNE will furnish a replacement for any part of this product which fails in normal use and service within the first ten years of installation, in accordance with the terms of the warranty.

For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the NORDYNE warranty department for a copy.
Symbols

Logo 8000 Phoenix Parkway I O’Fallon, MO 63368-3827

Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (09/2010)

CUSTOMERS SUPPORT

195D-091 O (Replaces 195D-0409)

www.frigidairehvac.com

FRIGIDAIRE is a registered trademark of Electrolux Home Products Inc. and used under a license from Electrolux Home Products, Inc.© Nortek Global HVAC, LLC. All Rights Reserved.

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Frigidaire User Manuals

Related Manuals