- FEATURES
- APPLICATIONS
- Description
- Model Encoding
- SPECIFICATION
- BLOCK DIAGRAM
- DERATING CURVE
- STATIC CHARACTERISTICS
- DC OK RELAY CONTACT
- MECHANICAL SPECIFICATION
- INSTALLATION INSTRUCTION
- INSTALLATION MANUAL
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MEAN WELL WDR-60 60W Ultra Wide Input Industrial DIN Rail Power Supply
FEATURES
- 180550Vac ultra wide input for 1-phase or 2-phase
- 32mm slim width
- 4.7KVac IVO high isolation(Reinforced isolation)
- Protections: Short circuit /Overload/ Over voltage/ Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- 30+85 C ultra-wide operating temperature (>+60°C derating)
- Over voltage category I
- DC OK relay contact
- DC output voltage adjustable(+20%)
- 3 years warranty
APPLICATIONS
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
Description
WDR-60 series is a 60w DIN rail power supply with ultra-wide AC input range. It is suitable to be mounted on TS-35/7.5 or TS-35/15 rails. Main features are as following: it can accept 180-550Vac ultra-wide input voltage range for single phase or 2-phase system, easy to install DIN rail type, narrow width (32mm) in slim design, -30-+85°C wide range operating temp, 4.7KVAC high isolation voltage, operation at 2000m altitude, adjustable output voltage (+20% max.), high efticiency, low ripple & noise, Complete protections and so on. WDR-60 is compliant with BS EN/EN-61000-6-2 standard regarding immunity for industrial environments. It suitable for industrial automation, surveillance, telecommunication and more applications.
Model Encoding
SPECIFICATION
MODEL | WDR-60-5 | WDR-60-12 | WDR-60-24 | WDR-60-48 |
---|
OUTPUT
| DC VOLTAGE| 5V| 12V| 24V| 48V
RATED CURRENT| 10A| 5A| 2.5A| 1.25A
CURRENT RANGE| 0 ~ 10A| 0 ~ 5A| 0 ~ 2.5A| 0 ~ 1.25A
RATED POWER| 50W| 60W| 60W| 60W
RIPPLE & NOISE (max.) **Note.2| 100mVp-p| 120mVp-p| 150mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 5 ~ 6V| 12 ~ 15V| 24 ~ 29V| 48 ~ 57V
VOLTAGE TOLERANCE ****Note.3| ±2%| ±1.5%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE, HOLD UP TIME**| 1000ms, 70ms, 20ms/400Vac
2000ms, 70ms, 10ms/230Vac at full load
INPUT
| VOLTAGE RANGE Note.4| 180 ~ 550Vac or 254 ~ 780Vdc
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 83.5% / 400Vac| 86.5% / 400Vac| 89% / 400Vac| 90.5% /
400Vac
AC CURRENT| 0.4A/400Vac 0.7A/230Vac
INRUSH CURRENT (max.)| COLD START 50A /400Vac 30A/230Vac
LEAKAGE CURRENT| <2mA / 530Vac
PROTECTION
| ****
OVERLOAD
| 105 ~ 135% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault
condition is removed
Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed
OVER VOLTAGE
| 6.2 ~ 7.2V| 16 ~ 18V| 31 ~ 37V| 58 ~ 60.5V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Protection type : Shut down o/p voltage, re-power on
to recover
FUNCTION| DC OK SIGNAL| Relay contact rating(max.) : 30V / 1A
resistive
ENVIRONMENT
| WORKING TEMP.| -30 ~ +85℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP.| -40 ~ +85℃
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
OPERATING ALTITUDE Note.5| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178, EN60664-1,
EN62477-1, EN60204-1; altitude up to 2000 meters
SAFETY & EMC
(Note 7)
| SAFETY STANDARDS| UL61010, BS EN/EN61558-2-16, AS/NZS 62368.1, EAC TP
TC 004 approved; design refer to GL and BS EN/EN60204-1(By request)
WITHSTAND VOLTAGE| I/P-O/P:4.7KVAC I/P-FG:2.5KVAC O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class B
Radiated| BS EN/EN55032(CISPR32)| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY
| BS EN/EN55024, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, 10V/m, criteria A
EFT Bursts| BS EN/EN61000-4-4| Level 3, 2KV/5KHz, criteria A
Surge| BS EN/EN61000-4-5| Level 4, 2KV/Line-Line, 4KV/Line-Earth, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m, criteria A
Voltage Dips and interruptions
| ****
BS EN/EN61000-4-11
| >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
OTHERS
| MTBF| 313.68K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.45Kg; 28pcs/13.6Kg/1.24CUFT
NOTE
| 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
BLOCK DIAGRAM
DERATING CURVE
STATIC CHARACTERISTICS
DC OK RELAY CONTACT
Contact Close | PSU turns ON / DC OK. |
---|---|
Contact Open | PSU turns OFF / DC Fail. |
Contact Ratings (max.) | 30V/1A resistive load. |
MECHANICAL SPECIFICATION
INSTALLATION INSTRUCTION
INSTALLATION MANUAL
Please refer to : http://www.meanwell.com/manual.html
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>