MEAN WELL HDR-150 Ultra Slim Step Shape W DIN Rail Datasheet

May 15, 2024
MEAN WELL

MEAN WELL HDR-150 Ultra Slim Step Shape W DIN Rail

MEAN-WELL-HDR-150-Ultra-Slim-Step-Shape-W-DIN-Rail-
product

Product Information

Specifications

  • Model: HDR-150 series
  • Power Output: 150W
  • Input Voltage: 85-264VAC (277VAC operational)
  • Compliance: UL61010, UL62368-1, BS EN/EN61558, TPTC004, IEC62368-1
  • Dimensions: Ultra slim design with 105mm width (6SU)

Product Usage Instructions

Installation

  1. Ensure the power source is disconnected before installation.
  2. Mount the Ultra Slim Step Shape DIN Rail securely using appropriate fixtures.
  3. Connect the input power within the specified voltage range (85-264VAC).

Operation

  1. After installation, apply power to the unit within the specified input voltage range.
  2. Ensure proper ventilation around the unit for optimal performance.
  3. Monitor the device for any unusual behavior or overheating during operation.

Maintenance

  1. Regularly check for any loose connections or damage to the unit.
  2. Clean the unit periodically to prevent dust build-up that can affect performance.

Safety Precautions

  • Do not exceed the specified input voltage range to prevent damage to the unit.
  • Avoid exposing the unit to extreme temperatures or moisture.
  • If in doubt, consult a qualified technician for assistance.

FAQ

  • Q: What should I do if the unit overheats during operation?
    A: If the unit overheats, immediately disconnect the power source and allow it to cool down before investigating the cause. Check for any obstructions to ventilation and ensure proper airflow around the unit.

  • Q: Can I use this product outdoors?
    A: It is recommended to use the Ultra Slim Step Shape DIN Rail indoors or in environments protected from direct exposure to outdoor elements such as water, dust, or extreme temperatures.

150W Ultra Slim Step Shape DIN Rail

MEAN-WELL-HDR-150-Ultra-Slim-Step-Shape-W-DIN-Rail-
\(2\)

Features

  • Ultra slim design with 105mm(6SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • DIN rail TS-35/7.5 or 15 mountable
  • Over voltage category III
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description
HDR-150 is an economical ultra slim 150W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 105mm(6SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-150 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90.5%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. The complete protection functions and relevant certificates for home automation and industrial control apparatus (IEC62368-1, UL62368-1, UL61010, BS EN/EN61558-2-16) make HDR-150 a very competitive power supply solution for household and industrial applications.

Model Encoding

SPECIFICATION

MODEL HDR-150-12 HDR-150-15 HDR-150-24 HDR-150-48







**OUTPUT**

| DC VOLTAGE| 12V| 15V| 24V| 48V
**RATED CURRENT| 115VAC| 10.2A| 8.55A| 5.31A| 2.72A
230VAC| 11.3A| 9.5A| 6.25A| 3.2A
****
RATED POWER| 115VAC| 122.4W| 128.3W| 127.4W| 130.6W
230VAC| 135.6W| 142.5W| 150W| 153.6W
RIPPLE & NOISE (max.) **Note.2| 100mVp-p| 120mVp-p| 150mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 10.8~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms/230VAC           500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC          12ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )       120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 89%| 89.5%| 90.5%| 90.5%
AC CURRENT (Typ.)| 3A/115VAC          1.6A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC         70A/230VAC




PROTECTION

| **OVERLOAD**| 105 ~ 135% rated output power

  • Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed
  • Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed

**OVER VOLTAGE**| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 45℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters (Note 4 )
OVER VOLTAGE CATEGORY| Ⅲ; According to EN62368,EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters











SAFETY & **EMC**

( Note.7 )

| SAFETY STANDARDS| IEC62368-1, UL62368-1, UL61010, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, EAC TP TC 004 approved;

Design refer to BS EN/EN50178, TUV BS EN/EN62368-1

WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
**EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class B
Radiated| BS EN/EN55032(CISPR32)| Class B (note 5)
Harmonic Current (Note 6 )| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
****
EMC IMMUNITY| BS EN/EN55024, BS EN/EN61000-6-2
Parameter| Standard| Test Level /Note**
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11|

  • >95% dip 0.5 periods, 30% dip 25 periods,
  • >95% interruptions 250 periods

**OTHERS| MTBF| 3046.3K hrs min.       Telcordia SR-332 (Bellcore) ; 535.9K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 1059054.5mm (WHD)
PACKING**| 0.31Kg; 32pcs/11Kg/1.0CUFT





NOTE

|

  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
  5. When the input voltage is 230VAC,delivers EMI Class B for radiated emission for the power supply; When the input voltage is 110VAC, delivers EMI Class A for radiated emission for the power supply.
  6. Harmonic current test at 70% load .
  7. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block DiagramMEAN-WELL-HDR-150-Ultra-Slim-Step-Shape-W-DIN-Rail-
\(4\)

Derating Curve VS Ambient Temperature

Output Derating VS Input Voltage

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm) MEAN-WELL-HDR-150-Ultra-Slim-Step-Shape-W
-DIN-Rail- \(7\)

Installation Manual
Please refer to : http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals