MEAN WELL UHP-1500-24 Switching power supplies User Guide
- May 15, 2024
- MEAN WELL
Table of Contents
UHP-1500 series
1500W Conduction Cooling with PFC Switching Supply
UHP-1500-24 Switching power supplies
|
---|---
https://www.meanwell.com/webapp/product/search.aspx?prod=UHP-1500&pdf=VUhQLTE1MDAtRS5QREY=&a=4|
https://www.youtube.com/watchv=0XCLiqb7le4&list=PLvUyt
_OJELVrHoIIRgvHF2NQ-j39-NH-J&index=7
Features
- Slim and Low profile (41mm)
- Fanless and conduction-cooled design
- Built-in active PFC function
- -30~+70℃ working temperature
- Output voltage and constant current level programmable
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Built-in remote ON-OFF control
- DC OK active signal
- Operating altitude up to 5000 meter (Note.8)
- LED indicator for power on
- Optional PMBus or CANBus protocol
- 5 years warranty
Applications
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments, equipment or apparatus
- Test and measurement instrument
- Laser related machine
- Charging related equipment
- Household appliances
- Power Sourcing Equipment of PoE (48V model: DC O/P range 48~57.6V)
GTIN CODE
MW Search:
https://www.meanwell.com/serviceGTIN.aspx
Description
UHP-1500 series is a 1500W single-output slim type power supply with 41mm of
low profile design. Adopting the full range 90~264VAC input, the entire series
provides an output voltage line of 24V and 48V. In addition to the high
efficiency up to 96%, that the whole series operates from -30℃ ~ 70℃ under air
convection without fan. UHP-1500 has the complete protection functions and 5G
anti-vibration capability; It is complied with the international safety
regulations such as TUV BS EN/EN62368-1, UL62368-1.
UHP-1500 series serves as a high performance power supply solution for various
industrial applications.
Model Encoding
Type | Communication Protocol | Note |
---|---|---|
Blank | None | In Stock |
PM | PMBus protocol | By request |
CAN | CANBus protocol | By request |
SPECIFICATION
MODEL | UHP-1500-24 | UHP-1500-48 |
---|---|---|
OUTPUT | DC VOLTAGE | 24V |
RATED CURRENT | 62.5A | 31.5A |
RATED POWER | 1500W | 1512W |
RIPPLE & NOISE (max.) Note.2 | 240mVp-p | 350mVp-p |
VOLTAGE ADJ.RANGE | By built-in potentiometer, SVR | |
24~28.8V | 48~57.6V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% |
LOAD REGULATION | ±0.5% | ±0.5% |
SETUP, RISE TIME Note.4 | 1800ms, 60ms/230VAC |
1800ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.) Note.4| 16ms/230VAC at 75% load
10ms/230VAC at full load ; 16ms/115VAC at 75% load
10ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.4| 90 ~ 264VAC 250 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.) Note.4| PF≥0.95/230VAC
PF≥0.99/115VAC at full load
EFFICIENCY (Typ.)| 95%| 96%
AC CURRENT (Typ.)| 11A/115VAC 8A/230VAC
INRUSH CURRENT (Typ.)| Cold start 30A/115VAC 60A/230VAC
LEAKAGE CURRENT| <0.75mA / 240VAC
PROTECTION| OVERLOAD| 105~125% rated current
Protection type : Constant current limiting, shut down O/P voltage after 5
sec.
After O/P voltage falls, re-power on to recover
SHORT CIRCUIT| Constant current limiting, unit will shutdown after 5 sec, re-
power on to recover.
OVER VOLTAGE| 30 ~ 35V| 60 ~ 67V
Protection type :Shut down O/P voltage,re-power on to recover
OVER TEMPERATURE| Protection type :Shut down O/P voltage, recovers
automatically after temperature goes down
FUNCTION
| OUTPUT VOLTAGE PROGRAMMABLE(PV) Note 5| Adjustment of output voltage is
allowable to 50 ~ 120% of nominal output voltage Please refer to the Function
Manual.
OUTPUT CURRENT PROGRAMMABLE(PC) Note 5| Adjustment of constant current level
is allowable to 20 ~ 100% of rated current. Please refer to the Function
Manual.
REMOTE ON/OFF CONTROL| Power ON : Short circuit Power OFF : Open
circuit
AUXILIARY POWER| 12V @ 0.4A tolerance ±10%, ripple=150mVp-p
DC-OK SIGNAL| The TTL signal out, PSU turn on = 4.4 ~ 5.5V ; PSU turn off =
-0.5 ~ 0.5V. Please refer to the Function Manual.
ENVIRONMENT
| WORKING TEMP.| -30 ~ +70℃(Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
(Note.7)| SAFETY STANDARDS| UL62368-1, Dekra seal BS EN/EN62368-1, EAC TP TC
004 approved
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG,O/P-FG:100M Ohms/500VDC/25℃/ 70%RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY| BS EN/EN55035, BS EN/EN61000-6-2
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-6-2| 2KV/Line-Line 4KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS| MTBF| 535.4K hrs min.
Telcordia SR-332 (Bellcore) ; 56.7K hrs min.
MIL-HDBK-217F (25℃)
DIMENSION| 29014041mm (LWH)
PACKING| 2.51kg ; 6pcs/16.06kg/0.86CUFT
NOTE
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient tempeture.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 1uf & 47uf parallel capacitor.
- Tolerance :includes set up tolerance, line regulation and load regulation.
- Derating may be needed under low input Please check the derating curve and Static characteristics for more details.
- PV/PC functions when users do not use
- Output will shut down after O/P voltage is below < 80% of Vset for 5 sec, re-power on to recover.
- The power supply is considered a component which will be installed into a final All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
- The ambient temperature derating of 5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
BLOCK DIAGRAM STATIC CHARACTERISTIC EFFICIENCY VS LOAD (48V MODEL) DERATING CURVE
FUNCTION MANUAL
1.Output Voltage Programming (or, PV / remote voltage programming / remote
adjust / margin programming / dynamic voltage trim)
※ In addition to the adjustment via the built-in potentiometer, the output
voltage can be trimmed by applying EXTERNAL VOLTAGE.
◎ The rated current should change with the Output Voltage Programming
accordingly.
2.Constant Current Programming (or, PC / remote current programming /
dynamic current trim)
※ The output current can be trimmed to 20~100% of the rated current by
applying EXTERNAL VOLTAGE. ◎ .Output will shut down after O/P voltage is below
< 80% of Vset for 5 sec, re-power on to recover
※ Covered by over temperature protection, auto de-rating function works under
operation either in PC mode or under control by communication protocol.
T : Maximum ambient temperature of full load.1(Typ.)
T : T1+5 .2(Typ.) ℃ 3.Remote ON-OFF Control
The power supply can be turned ON/OFF individually or along with other units
in parallel by using the “Remote ON-OFF” function.
Remote ON-OFF | Power Supply Status |
---|---|
Short circuit | ON |
Open circuit | OFF |
4.DC-OK Signal
DC-OK signal is a TTL level signal. The maximum sink current is 10mA and the
maximum external voltage is 5.6V.
DC-OK signal | Power Supply Status |
---|---|
“High” >4.4~5.5V | ON |
“Low” <-0.5~0.5V | OFF |
5.PMBus Communication Interface
UHP-1500 supports PMBus Rev. 1.1 with maximum 100KHz bus speed, allowing
information reading, status monitoring, output trimming, etc. For details,
please refer to the Function Manual.
MECHANICAL SPECIFICATION
AC Input Terminal(TB1) Pin NO. Assignment
Pin No. | Assignment | Terminal | Max mounting torque |
---|---|---|---|
1 | AC/L | DECA T25 | 18Kgf-cm |
2 | AC/N | ||
3 |
DC Output Terminal(TB2,TB3) Pin NO. Assignment
Pin No. | Assignment | Terminal | Max mounting torque |
---|---|---|---|
TB2 | +V | (MW) HS455A | 8Kgf-cm |
TB3 | -V |
※DIP SW:
Pin No. | Function | Description |
---|---|---|
1 | A0 | PMBus / CANBus interface address switch. |
2 | A1 | |
3 | A2 |
※Control Pin No. Assignment(CN71) : HRS DF11-12DP-2DS or equivalent
Mating Housing | HRS DF11-12DS or equivalent |
---|---|
Terminal | HRS DF11-**SC or equivalent |
Pin No. | Function |
Description
---|---|---
1| PV| Connection for output voltage programming.(Note1)
2| PC| Connection for constant current level programming.(Note.1)
3,4| GND (Signal)| Negative output voltage signal.
5| Remote ON-OFF| The unit can turn the output ON/OFF by dry contact
between Remote ON/OFF and 12-AUX.(Note.2)
Short (10.8 ~ 13.2V) : Power ON ; Open(0 ~ 0.5V) : Power OFF ; The maximum
input voltage is 13.2V
6| DC-OK| Low (-0.5 ~ 0.5V) : When the Vout≦80%±6%. High (4.4 ~ 5.5V) : When
Vout≧80%±6%.
The maximum sourcing current is 10mA and only for output.(Note.2)
7,8| +12V-AUX| Auxiliary voltage output, 10.6~13.2V, referenced to GND-AUX
(pin3 & 4).
The maximum load current is 0.4A. This output is not controlled by “Remote ON-
OFF”.
9,10| GND-AUX| Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
11| SDA| For PMBus model: Serial Data used in the PMBus interface. (Note.2)
CANH| For CANBus model: Data line used in CANBus interface. (Note.2)
12| SCL| For PMBus model: Serial Clock used in the PMBus interface. (Note.2)
CANL| For CANBus model: Data line used in CANBus interface. (Note.2)
Note 1: Non-isolated signal, referenced to [GND(signal)].
Note 2: Isolated signal, referenced to GND-AUX.
Operate with additional aluminum plate
In order to meet the“Derating Curve”and the “Static Characteristics”
,UHP-1500 series must be installed onto an aluminum plate(or the cabinet of
the same size) on the bottom.The size of the suggested aluminum plate is shown
as below. And for optimizing thermal performance, the aluminum plate must have
an even and smooth surface (or coated with thermal grease), and UHP-1500
series must be firmly mounted at the center of the aluminum plate.
File Name:UHP-1500-SPEC
2023-03-01
Documents / Resources
| MEAN
WELL UHP-1500-24 Switching power
supplies
[pdf] User Guide
UHP-1500-24 Switching power supplies, UHP-1500-24, Switching power supplies,
power supplies, supplies
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>