AIRZONE AZEZ8CB1IAQ Easyzone IAQ Slim + CMV IB8 GG0 Installation Guide

June 3, 2024
AIRZONE

AIRZONE AZEZ8CB1IAQ Easyzone IAQ Slim + CMV IB8 GG0 Installation Guide

EASYZONE IAQ

Airzone motorized plenum with neck that mechanically adapts to the main ducted AC units Airzone motorized plenum includes

  • Main control board (AZEZ8CB1IAQ) that controls the system through wired and wireless devices.
  • Communication gateway (for more information, see the technical datasheet ofthe gateway).
  • Round dampers of 150/200 mm in diameter.
  • Manual airflow control system.
  • Controlled mechanical ventilation (CMV) input of 150 mm in diameter (Available only in ST and SL).
  • Airzone particulate matter sensor.
  • Air purification system by ionization.

Depending on the motorized plenum (nº of dampers and settings) and the controlled indoor unit, the sound pressure may vary to ±3 dB(A) and the pressure drop may vary from 5 to 15 Pa. For further information about our products, go to myzone.airzone.es

TECHNICAL SPECIFICATIONS

NL

V max

| 110/230 Vac
---|---

I max

| 250 mA

Frequency

| 60/50 Hz

Stand-by consumption

| 4.85/1.68 W

Module over-current protection

| 250 mA

AZ1 – AZ2 – AZ3 – IU

  • Shielded twisted pair: 2 x 0.22 + 2 x 0.5mm2
  • V max: 12 Vdc

DM1

  • Shielded twisted pair: 2 x 0.22 + 2 x 0.5 mm2
  • Communications protocol: MODBUS RS-485
  • Maximum distance: 100 m

Communications via radio

Communications protocol

|

Airzone

---|---

Frequency

|

868 MHz

Radiation power

|

5 dBm

Maximum distance in open space

|

40 m

IO1 … IO8

Maximum number of outputs per damper

|

2

---|---

Maximum number of ionization modules per output

|

1

V max

|

34 Vdc

I max

|

270 mA

IAQ

V max

|

250 Vac / 24 Vdc

---|---

I max

|

12 A

Temperaturas operativas

Storage

|

-20 … 70 ºC

---|---

Operation

|

0 … 50 ºC

Mechanical aspects

Protection class

|

IP 21

---|---

Weight

|

616 g

Purification

Minimum size of particles detected

|

2.5 μm

---|---

Minimum- maximum detectable density

|

0 – 2000 μg/m3

Maximum- detection error consistency

|

±10 %

Sensor response time

|

1s

Time from first sensor reading

|

8s

Ion type

|

Negative

Quantity of ozone per ionizer

|

0.15 mg/h

Number of ions

|

8000000 io./cm3

ON/OFF MODULE

Motorized plenum

Motorized plenum

Motorized plenum

DEVICE ELEMENTS

|

Description

---|---

AZ1…AZ3

| Airzone connection bus

P3

|

Wireless module

SW1

|

SW1

DM1

|

Automation bus

IU

|

AC unit bus

IO1…IO8

|

Actuator and purification outputs

DI1

|

Alarm input (normally close)

AI1

|

Temperature probe

O1

|

AC start-stop relay

O2

|

CMV/Boiler

N L

|

Power

ON/OFF

|

Contact on/off (optional)

IAQ

|

Airzone particle sensor

SELF-DIAGNOSIS

| Meaning| |
---|---|---|---
D1| Data reception from automation bus| Blinking| Green
D2| Data transmission from automation bus| Blinking| Red
D3| Main control board activity| Blinking| Green
D4| Data transmission from connection bus| Blinking| Red
D5| Data reception from connection bus| Blinking| Green
D6| AC unit On/Off| Switches| Green
D7| CMV/Boiler| Switches| Green
D8| Data transmission from AC unit bus| Blinking| Red
D9| Data reception from AC unit bus| Blinking| Green
D10| Wireless data packets reception| Switches| Green
D11| Main control board power| Fixed| Red
D18| Associated element| Fixed| Green
D19| Association channel: active| Fixed| Red
| Open dampers| On| Green
A| Close dampers| On| Red
| Purifier activated| Fixed| Blue
|

N

| (kg)| W| H| L|

Ø

---|---|---|---|---|---|---

ST

|

3 4 5 6 7/8

| 11±1 15±1 18±1 21±1 28±2| 454 454 454 454 454| 300 300 300 300 515| 930 1140 1425 1638 1425|

200

SL

|

3 4 5

|

10±1 12±1 14±1

|

444 444 444

|

210 210 210

|

720 930 1140

|

150

BS

|

3 4 5 6

|

10±1 13±1 15±1 18±1

|

454 454 454 454

|

250 250 250 250

|

930 1140 1425 1638

|

200

Nº of dampers

If the system has CMV L = L+180 mm

ON/OFF MODULE

CONNECTION

Do not connect the “-“ pole to the “+” terminal. It may damage the device.

Connections
Connections
Connections

The Easyzone plenum is grounded via the indoor unit.

Airzon

EU.BAC

Type

|

Airzone Central V1.3

---|---

Licence

|

215562

Application

|

Variable air volume system (without h/c coil)

Heating Cooling

Control accuracy (K)

|

0.3 0.3

Gateway connection

Gateway connection

Consult the gateway’s technical datasheet to continue with the connection to the indoor unit.