AIRZONE AZAI6WSCGG3 Support Aidoo Wi-Fi Control Instruction Manual
- May 15, 2024
- AIRZONE
Table of Contents
AIRZONE AZAI6WSCGG3 Support Aidoo Wi-Fi Control
Product Usage Instructions
Connection and Setup
- Ensure the device is within the Wi-Fi range.
- Power the device using the recommended voltage range (12 – 16 V).
- Download and install the Airzone Cloud App on your iOS or Android device.
- Follow the in-app instructions to connect the device to your Wi-Fi network.
Remote Control
- You can remotely manage and integrate units using the Airzone Cloud App.
- Make sure you are connected to the internet to access the remote control features.
Troubleshooting
- If you encounter any issues with the device, refer to the user manual for troubleshooting steps.
- For further assistance, contact customer support.
FAQ
- Q: What should I do if the device is not connecting to Wi-Fi?
- A: Check if the device is within the Wi-Fi range and that you have entered the correct network credentials. Restart the device and try reconnecting.
- Q: How can I reset the device?
- A: To reset the device, locate the reset button and hold it for 10 seconds. The device will restart and reset to factory settings.
- Q: Can I use the device with other compatible units?
- A: Yes, the AIDOO WI-FI GG3 is designed to work with other compatible units. Refer to the user manual for more information on compatibility.
AIDOO WI-FI GG3
Device to manage and integrate units remotely from the Cloud. Online control with the “Airline Cloud” App (available for iOS and Android). Wireless Wi-Fi connection. Externally powered by the indoor unit.
Features
- Control of the parameters of the unit.
- Communication errors detection.
- Temperature and operating mode time schedules.
- Multi-user and multi-session.
- Port for integration via Modbus protocol.
For further information about our products, go to airzonecontrol.com.
TECHNICAL SPECIFICATIONS
- Type of power supply: Vdc
- V max 18 V
- I max 137.5 mA
- V in 12 – 16 V
- Consumption: 0.85 W
- Type of cable: Conector GG3
- GG3 connector
- Conector GG3
- Wire length: 2.5 m (8.2 ft)
WI-FI Communication
- Protocol: WI-FI – CERTIFIED TM 802.11b/g/n (802.11n up to 150 Mbps)
- Model: ESP-WROOM-32
- Communication frequency: 2.4 GHz
- Maximum power – Antenna power: 20 dBm
- Sensitivity: – 97 dBm
- IP address: DHCP
Bluetooth Communication
- Protocol: Bluetooth v4.2 BR/EDR and BLE specification
- Bluetooth class: Class-1, class-2 and class-3 transmitter
RS-485 Port
- Shielded twisted pair: 2 x 0.22 + 2 x 0.5 mm2 (AWG 23 – 2 wired + AWG 20 – 2 wired)
- Communication protocol: RS-485 Par – 19200 bps
Operating temperatures
- Storage: – 20 … 70 ºC (- 4 … 158 ºF)
- Operation: 0 … 45 ºC (32 … 113 ºF)
- Operating humidity rango: 5 … 90 % (non-condensing)
Mechanical aspects
- Protection class: IP 41
- Weight: 130 g (0.29 lb)
Dimensions
- Check the indoor units compatible:
FCC / ISED
- This device complies with FCC / ISED regulatory notices.
DEVICE ELEMENTS
Nº Description
- Cable GG3
- RS-485 port
- Indoor unit port
- Device reboot
- Association process reset
- Power supply
- External power input
SELF-DIAGNOSIS
Nº | Significado / Meaning / Significado |
---|
| Connecting to WI-FI network
| Blinking| ****
Green
Connected to WI-FI network| Steady
Connected to the server| Steady| Blue
Not configured| Off| ****
–
****| Cloud communication| Blinking| Red
****| Microprocessor activity| Blinking| Green
****| Power supply| Steady| Red
****| Data transmission to the indoor unit| Blinking| Red
****| Data reception from the indoor unit| Blinking| Green
ASSEMBLY AND CONNECTION
Important: Wired controller required XK46 or equivalent. The unit controller must remain working in parallel with your Aidoo.
- Perform the assembly following the next step:
- Screw attachment.
- Double-sided adhesive attachment.
- Disconnect the indoor unit.
- Connect the Aidoo to the terminals of the indoor unit using the supplied number cable, H1 and H2.
- Connect the Aidoo to power supply. Power the indoor unit. Check the LEDs (see Self-diagnosis section).
- Download the app and follow the steps bellow for its setting. Access the support section to see the user manual.
Important: The equipment shall be supplied by a limited power source meeting class PS2 of the standard IEC 62368-1.
Read User Manual Online (PDF format)