IMMERGAS 3.021377 Hydraulic Separating Device Kit Instruction Manual
- June 4, 2024
- IMMERGAS
Table of Contents
HYDRAULIC SEPARATING DEVICE KIT
FOR 200KW POWER BOILER SETS
3.021377
THIS SHEET MUST BE LEFT WITH THE USER ALONG WITH THE BOILER INSTRUCTION BOOK
General warnings
All products are protected with suitable transport packaging. The material
must be stored in dry environments and protected against weathering. This
instruction manual provides technical information for installing the kit. As
for the other issues related to kit installation (e.g. safety at the work
site, environment protection, injury prevention), it is necessary to comply
with the provisions specified in the regulations in force and principles of
good practice. Improper installation or assembly of the appliance and/or
components, accessories, kit, and devices can cause unexpected problems to
people, animals, and objects. Read the instructions provided with the product
carefully to ensure a proper installation. Installation and maintenance must
be performed in compliance with the regulations in force, according to the
manufacturer’s instructions and by authorized professionally qualified staff,
intending staff with specific technical skills in the plant sector, as
envisioned by the Law.
Installation and maintenance must be performed in compliance with the
regulations in force, according to the manufacturer’s instructions and by
professionally qualified staff, intending staff with specific technical skills
in the plant sector, as envisioned by the Law.
GENERAL INFORMATION
This kit can be installed with a right or left outlet. It is also possible to
decide whether to install the separating device on the wall or floor.
The hydraulic separating device makes the primary circuit and the secondary
circuit independent.
INSTALLAZIONE A PARETE WALL INSTALLATION
Fig. 2
INSTALLAZIONE A BASAMENTO FLOOR-STANDING INSTALLATION
Kit composition:
Ref. | Qty | Description |
---|---|---|
I | 1 | Hydraulic separator device (content 25 liters) |
2 | 2 | Support for wall installation |
3 | 1 | Spacer for separating device |
4 | 2 | Support for floor installation |
5 | 4 | 72 x 55 x 2 flat gaskets |
6 | 6 | M6 X 15 Self-threading screws |
7 | 6 | 8 X 80 hex head screws |
8 | 6 | 12 x 60 nylon masonry plug |
9 | 2 | 2″ 1/2 brass nut |
KIT ASSEMBLY
Proceed as follows to assemble the kit:
Important: the fixing measurements indicated in the figure are indicative and
include the optional “ISPESL safety kits”.
For correct mounting, refer to its hydraulic configuration.
- Victrix 90 – 115 models wall installation
– Make n° 6 holes with Ø 12 using the measurements indicated in figure 1
referring to the fixing plate (ref. 3 fig. 2).
– Insert 6 plugs (8) into the holes.
– Fix the spacer (3) to the wall using the 6 screws with plug (7).
– Flank the two vertical supports (2) and fix them to the bracket (3) using
the 6 self-threading screws (6).
– Place the hydraulic separating device (1) on the supports (2).
– Make the hydraulic connections, positioning the relative gaskets (5).
Once the kit has been mounted completely, check the tightness of the hydraulic
circuit according to that prescribed by the Standard in force.
- Victrix 50 – 75 models wall installation
N.B.: the spacer (3) and the fastening screws (6) are not necessary for
this installation.
– Make n° 6 holes with Ø 12 using the measurements indicated in figure 1
referring to the support (2).
– Insert 6 plugs (8) into the holes.
– Flank the two vertical supports (2) and fix them to the wall using the 6
self-threading screws (7).
– Place the hydraulic separating device (1) on the supports (2).
– Make the hydraulic connections, positioning the relative gaskets (5).
Once the kit has been mounted completely, check the tightness of the hydraulic
circuit according to that prescribed by the Standard in force.
- Floor-standing installation
– Make n° 4 holes with Ø 12 using the measurements indicated in figure 1
referring to the support (4).
– The “XX” measurement represents the distance from the wall with respect to
the axis of the separating device. For Victrix 50 – 75 models, it is 436 mm,
for Victrix 90 – 115 models it is 470 mm
– Insert 4 plugs (8) into the holes.
– Flank the two supports (4) and fix them to the floor using the 4 self-
threading screws (7).
– Place the hydraulic separating device (1) on the supports (7).
– Make the hydraulic connections, positioning the relative gaskets (5).
Once the kit has been mounted completely, check the tightness of the hydraulic
circuit according to that prescribed by the Standard in force.
MAIN DIMENSIONS
Key:
- Vent valve
- Interception cock
- Attachment for probe (not supplied)
- Hydraulic separator device (content 25 liters)
- Draining valve
STD.009384/002
Read User Manual Online (PDF format)