General warnings.
All products are protected with suitable transport packaging. The material must be stored in dry environments and protected against weathering.
This instruction manual provides technical information for installing the kit. As for the other issues related to kit installation (e.g. safety in the work site, environment protection, injury prevention), it is necessary to comply with the provisions specified in the regulations in force and principles of good practice.
Improper installation or assembly of the appliance and/or components, accessories, kit and devices can cause unexpected problems to people, animals and objects. Read the instructions provided with the product carefully to ensure a proper installation.
Installation and maintenance must be performed in compliance with the regulations in force, according to the manufacturer’s instructions and by authorised professionally qualified staff, intending staff with specific technical skills in the plant sector, as envisioned by the Law.

IMMERGAS 3.023961 Wall-Hung Modular Condensing Boiler
1

IMMERGAS 3.023961 Wall-Hung Modular Condensing Boiler
2

Ref Kit components description Qty
1 Flange gasket DN 100 2
2 Thermometer pocket 1
3 Brass plug G1/2″ M 1
4 INAIL type-approved manometer-holder cock 1
5 INAIL type-approved thermometer 1
6 INAIL type-approved manual rearm thermostat 1
7 INAIL type-approved manual rearm pressure switch 1
8 Insulated return manifold DN 100 1
9 Insulated supply manifold DN 100 1
10 Damper coil 1
11 INAIL type-approved gauge 1
12 INAIL-approved minimum pressure switch 1
13 Nut M16 16
14 Washer 16
15 Brass plug G3/4″ M 2
16 Screw M16x65 16

M – System flow
R – System return

Kit Assembly

Connect the safety kit manifolds as shown in figure 2, making sure to interpose the gaskets (1).
Connect the wires of the thermostat (6) and the pressure switches (7 and 12) as shown in figure 4.
If assembling the INAIL safety devices kit on the left side, perform the installation as shown in figure 3.

Electrical connection
Make the electrical connection of the pressure switches (7 and 12) and the safety thermostat (6) according to the diagram in figure 4.
Attention: the boilers have an IPX5D electric insulation rating and can also be installed outdoors, without additional protections. However, if installed outdoors, the relevant piping should be insulated and the kit protected from the elements.

Attention: the sensitive elements of the automatic blocking thermal switches and of the original thermometer present in the kit comply with the provisions of collection “R”.

Obligations for the installer.
The boilers must be installed in the configurations and with their own original safety kits.
The factory declines all liability whenever the installer does not use the devices and INAIL-approved original kits or uses them improperly.
N.B.: before closing one or both the system cut-off cocks (34) figure 5, the boiler must be switched off.

IMMERGAS 3.023961 Wall-Hung Modular Condensing Boiler
3

Key:

  1. Generator
  2. Cascade and zone regulator
  3. Zone manager
  4. Modulating room thermostat
  5. External probe
  6. Zone 1 temperature probe (CMI-1)
  7. Zone 2 temperature probe (CMI-2)
  8. Common flow probe
  9. Storage tank unit temperature probe
  10. Zone 1 mixing valve (CMI-1)
  11. Zone 2 mixing valve (CMI-2)
  12. Zone 1 central heating circuit pump (CMI-1)
  13. Zone 2 central heating circuit pump (CMI-2)
  14. Zone 3 direct circuit pump (CD)
  15. Storage tank unit feeding pump
  16. Zone 1 safety thermostat (CMI-1)
  17. Zone 2 safety thermostat (CMI-2)
  18. Fuel shut-off valve bulb
  19. INAIL-approved pressure gauge-holder cock
  20. INAIL-approved thermometer
  21. INAIL-approved manual rearm pressure switch
  22. INAIL-approved manual rearm thermostat
  23. Attachment for expansion vessel
  24. Expansion vessel
  25. Manifold/mixer
  26. External storage tank unit
  27. Fuel shut-off valve
  28. Non return valve
  29.  Slurry collection system filter
  30. Manometer pocket
  31. Flue circuit flue adjusting device
  32. Stub pipe drain trap
  33. System cut-off valve
  34. Three-way draining valve
  35. Damper coil
  36. INAIL-approved pressure gauge
  37. INAIL-approved minimum pressure switch

IMMERGAS 3.023961 Wall-Hung Modular Condensing Boiler