Specifications

  • Model: EDR-150-24
  • DC Voltage: 24V
  • Rated Current: 6.5A / 230VAC, 5.2A / 115VAC
  • Rated Power: 156W / 230VAC, 125W / 115VAC
  • Ripple & Noise: 150mVp-p
  • Output Voltage Adjustment Range: 24 ~ 28V
  • Efficiency: 87%
  • Dimension: 40125.2113.5mm (WHD)

Product Usage Instructions

Installation

The EDR-150-24 power supply can be installed on DIN rail
TS-35/7.5 or TS-35/15 mounting rails. Ensure that the input power
matches the specified voltage range of 90-264VAC.

Connections

Connect the input power to the designated terminals as per the
user manual provided. Make sure to follow the correct polarity to
avoid damage.

Operation

Once installed and connected, the power supply can be turned on
by applying power to the input terminals within the specified
voltage range. The output voltage can be adjusted within the range
of 24-28V as needed.

Maintenance

Regularly check for any signs of overheating or abnormal
operation. Keep the unit clean and free from dust to ensure proper
cooling and performance.

FAQ

Q: Can the EDR-150-24 be used for outdoor applications?

A: No, the EDR-150-24 is designed for indoor use in industrial
settings and should not be exposed to outdoor elements.

Q: What is the warranty period for the EDR-150-24?

A: The product comes with a 2-year warranty from the date of
purchase.

Q: How can I adjust the output voltage of the power

supply?

A: The output voltage can be adjusted within the range of 24-28V
using the provided adjustment mechanisms on the unit.

“`

150W Single Output Industrial DIN RAIL

EDR-150-24
User’s Manual

Features
Universal AC input / Full range Protections: Short circuit / Overload / Over voltage
/ Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level 100% full load burn- in test 2 years warranty

R33100 RoHS

TPTC004

Bauart gepruft Sicherheit
egelma ge od o s be wac g
www.tuv.com ID 2000000000
BS EN/EN62368-1

IEC62368-1

Applications

Industrial control system

Semiconductor fabrication equipment

Factory automation

Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description
EDR-150-24 is one economical slim DIN rail power supply series, providing up to 156W at 230VAC input. This series is adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input f r o m 9 0 V A C t o 2 6 4 V A C a n d c o n f o r m s t o BS EN / E N 6 1 0 0 0 – 3 – 2 (8 0 % Lo a d ) , t h e n o r m t h e Eu r o p e a n Union regulates for harmonic current.
EDR-150-24 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 87%, the entire series can operate at the ambient temperature between -20 and 60 under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-150-24 a very competitive power supply solution for industrial applications.

Model Encoding EDR – 150- 24
Output voltage Output wattage Model name

Downloaded from Arrow.com.

File Name:EDR-150-24-SPEC 2024-05-06

150W Single Output Industrial DIN RAIL

EDR-150-24

SPECIFICATION

MODEL

EDR-150-24

DC VOLTAGE

24V

RATED CURRENT

6.5A / 230VAC 5.2A / 115VAC

CURRENT RANGE

0 ~ 6.5A / 230VAC 0 ~ 5.2A / 115VAC

RATED POWER

156W / 230VAC 125W / 115VAC

RIPPLE & NOISE (max.) Note.2 150mVp-p

OUTPUT

VOLTAGE ADJ. RANGE

24 ~ 28V

VOLTAGE TOLERANCE Note.3 ±1.0%

LINE REGULATION

±0.5%

LOAD REGULATION

±1.0%

SETUP, RISE TIME

1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load

HOLD UP TIME (Typ.)

16ms/230VAC 10ms/115VAC at full load

VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]

FREQUENCY RANGE

47 ~ 63Hz

INPUT

EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

87% 2.6A/115VAC 20A/115VAC

1.7A/230VAC 35A/230VAC

LEAKAGE CURRENT

<1mA / 240VAC

OVERLOAD PROTECTION

105 ~ 130% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed / 230VAC
Note.7
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed / 115VAC

OVER VOLTAGE

29 ~ 33V Protection type : Shut down o/p voltage, re-power on to recover

OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION

Shut down o/p voltage, re-power on to recover -20 ~ +60 (Refer to “Derating Curve”) 20 ~ 95% RH non-condensing -40 ~ +85, 10 ~ 95% RH ±0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY STANDARDS

WITHSTAND VOLTAGE

SAFETY & ISOLATION RESISTANCE

EMC
(Note 4)

EMC EMISSION

Ul508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS15598-1 approved;(meet BS EN/EN60204-1) I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2, Class A (80% Load), BS EN/EN61000-3-3, EAC TP TC 020, CNS15936 Class A

EMC IMMUNITY MTBF

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020 2717.1K hrs min. Telcordia SR-332 (Bellcore) ; 472.5K hrs min. MIL-HDBK-217F (25)

OTHERS NOTE

DIMENSION

40125.2113.5mm (WHD)

PACKING

0.6Kg; 20pcs/13Kg/1.16CUFT

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1F & 47F parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets

EMC directives. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.

7. Hiccup mode at 90~100VAC, recovers automatically after fault condition is removed. 8. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).

Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Downloaded from Arrow.com.

File Name:EDR-150-24-SPEC 2024-05-06

150W Single Output Industrial DIN RAIL

EDR-150-24

Block Diagram

EMI FILTER

I/P

&

RECTIFIERS

FG

O.L.P. O.T.P.

POWER SWITCHING
PWM CONTROL

RECTIFIERS &
FILTER

O.C.P.
DETECTION CIRCUIT
O.V.P.

fosc : 70KHz
+V -V

Derating Curve

Static Characteristics

230VAC 100
80 115VAC
60 50 40
20

230VAC 115VAC

(156W)100 90
(125W)80 70 60 50 40

-20 -10 0

10

20

30

40

50

AMBIENT TEMPERATURE ()

60 70 (VERTICAL)

90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz

LOAD (%) LOAD (%)

Downloaded from Arrow.com.

File Name:EDR-150-24-SPEC 2024-05-06

150W Single Output Industrial DIN RAIL
Mechanical Specification

EDR-150-24
Case No.992D Unit:mm

35 125.2

113.5 Side View
Installation Instruction

Top View 40
1234
TB2 +V ADJ. +
DC OK
TB1 123 Front View
Bottom View

Side View
Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 AC/N or DC 3 AC/L or DC +
Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 DC OUTPUT -V 3,4 DC OUTPUT+V

35

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)

Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Downloaded from Arrow.com.

File Name:EDR-150-24-SPEC 2024-05-06

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals